ABB AF09-30-01-13 100-250V50/60HZ-DC Contactor

General Information

Extended Product Type: AF09-30-01-13
Product ID: 1SBL137001R1301
EAN: 3471523110137
Catalog Description: AF09-30-01-13 100-250V50/60HZ-DC Contactor
Long Description: The AF09-30-01-13 is a 3 pole – 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor ha…Show mores a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.Show less
SKU: c5bc12cdcb17 Categories: ,

Description

Ordering
Minimum Order Quantity: 1 piece
Popular Downloads
Data Sheet, Technical Information: 1SBC100214C0202 – Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) – Edition 2024
Instructions and Manuals: Installation instructions AF(C)09…38(Z)(B) Contactors, NF(C)(Z)(B)22…80E Contactor relays and CA4, CAL4, CAT4, CC4, LDC4 Accessories
CAD Dimensional Drawing: Information – 2D and 3D files for CAD systems
Dimensions
Product Net Width: 45 mm
Product Net Depth / Length: 77 mm
Product Net Height: 86 mm
Product Net Weight: 0.27 kg
Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 1
Number of Poles: 3P
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie): (415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie): (415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-15 (Ie): (500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie): (110 V) 1-Pole, 40 °C 10 A
(110 V) 1-Pole, 60 °C 10 A
(110 V) 1-Pole, 70 °C 10 A
(110 V) 2 Poles in Series, 40 °C 25 A
(110 V) 2 Poles in Series, 60 °C 25 A
(110 V) 2 Poles in Series, 70 °C 22 A
(110 V) 3 Poles in Series, 40 °C 25 A
(110 V) 3 Poles in Series, 60 °C 25 A
(110 V) 3 Poles in Series, 70 °C 22 A
(220 V) 2 Poles in Series, 40 °C 10 A
(220 V) 2 Poles in Series, 60 °C 10 A
(220 V) 2 Poles in Series, 70 °C 10 A
(220 V) 3 Poles in Series, 40 °C 25 A
(220 V) 3 Poles in Series, 60 °C 25 A
(220 V) 3 Poles in Series, 70 °C 22 A
(72 V) 1-Pole, 40 °C 25 A
(72 V) 1-Pole, 60 °C 25 A
(72 V) 1-Pole, 70 °C 22 A
(72 V) 2 Poles in Series, 40 °C 25 A
(72 V) 2 Poles in Series, 60 °C 25 A
(72 V) 2 Poles in Series, 70 °C 22 A
(72 V) 3 Poles in Series, 40 °C 25 A
(72 V) 3 Poles in Series, 60 °C 25 A
(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie): (110 V) 1-Pole, 40 °C 6 A
(110 V) 1-Pole, 60 °C 6 A
(110 V) 1-Pole, 70 °C 6 A
(110 V) 2 Poles in Series, 40 °C 25 A
(110 V) 2 Poles in Series, 60 °C 25 A
(110 V) 2 Poles in Series, 70 °C 22 A
(110 V) 3 Poles in Series, 40 °C 25 A
(110 V) 3 Poles in Series, 60 °C 25 A
(110 V) 3 Poles in Series, 70 °C 22 A
(220 V) 2 Poles in Series, 40 °C 6 A
(220 V) 2 Poles in Series, 60 °C 6 A
(220 V) 2 Poles in Series, 70 °C 6 A
(220 V) 3 Poles in Series, 40 °C 25 A
(220 V) 3 Poles in Series, 60 °C 25 A
(220 V) 3 Poles in Series, 70 °C 22 A
(72 V) 1-Pole, 40 °C 25 A
(72 V) 1-Pole, 60 °C 25 A
(72 V) 1-Pole, 70 °C 22 A
(72 V) 2 Poles in Series, 40 °C 25 A
(72 V) 2 Poles in Series, 60 °C 25 A
(72 V) 2 Poles in Series, 70 °C 22 A
(72 V) 3 Poles in Series, 40 °C 25 A
(72 V) 3 Poles in Series, 60 °C 25 A
(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie): (110 V) 1-Pole, 40 °C 4 A
(110 V) 1-Pole, 60 °C 4 A
(110 V) 1-Pole, 70 °C 4 A
(110 V) 2 Poles in Series, 40 °C 10 A
(110 V) 2 Poles in Series, 60 °C 10 A
(110 V) 2 Poles in Series, 70 °C 10 A
(110 V) 3 Poles in Series, 40 °C 25 A
(110 V) 3 Poles in Series, 60 °C 25 A
(110 V) 3 Poles in Series, 70 °C 22 A
(220 V) 2 Poles in Series, 40 °C 4 A
(220 V) 2 Poles in Series, 60 °C 4 A
(220 V) 2 Poles in Series, 70 °C 4 A
(220 V) 3 Poles in Series, 40 °C 9 A
(220 V) 3 Poles in Series, 60 °C 9 A
(220 V) 3 Poles in Series, 70 °C 9 A
(72 V) 1-Pole, 40 °C 9 A
(72 V) 1-Pole, 60 °C 9 A
(72 V) 1-Pole, 70 °C 9 A
(72 V) 2 Poles in Series, 40 °C 25 A
(72 V) 2 Poles in Series, 60 °C 25 A
(72 V) 2 Poles in Series, 70 °C 22 A
(72 V) 3 Poles in Series, 40 °C 25 A
(72 V) 3 Poles in Series, 60 °C 25 A
(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-13 (Ie): (24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe): (400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
Rated Operational Power AC-3e (Pe): (415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 690 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 6 kV
Maximum Electrical Switching Frequency: (AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 300 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Rated Control Circuit Voltage (Uc): 50 Hz 100 … 250 V
60 Hz 100 … 250 V
DC Operation 100 … 250 V
Power Loss: at 6 A per Pole 0.1 W
at Rated Operating Conditions AC-1 per Pole 0.8 W
at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate Time: Between Coil De-energization and NC Contact Closing 13 … 98 ms
Between Coil De-energization and NO Contact Opening 11 … 95 ms
Between Coil Energization and NC Contact Opening 38 … 90 ms
Between Coil Energization and NO Contact Closing 40 … 95 ms
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied): 2 x M4 screws placed diagonally
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 0.75 … 6 mm²
Flexible with Insulated Ferrule 1x 0.75 … 4 mm²
Flexible with Insulated Ferrule 2x 0.75 … 2.5 mm²
Rigid Solid 1/2x 1 … 4 mm²
Rigid Stranded 1/2x 1 … 6 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Rigid Solid 1/2x 1 … 2.5 mm²
Rigid Stranded 1/2x 1 … 2.5 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 1.5 mm²
Rigid Solid 1/2x 1 … 2.5 mm²
Rigid Stranded 1/2x 1 … 2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque: Auxiliary Circuit 1.2 N·m
Control Circuit 1.2 N·m
Main Circuit 1.5 N·m
Terminal Type: Screw Terminals
Product Name: Block Contactor
Technical UL/CSA
NEMA Size: 00
Continuous Current Rating NEMA: 9 A
Horsepower Rating NEMA: (115 V AC) Single Phase 1/3 Hp
(200 V AC) Three Phase 1-1/2 Hp
(230 V AC) Single Phase 1 Hp
(230 V AC) Three Phase 1-1/2 Hp
(460 V AC) Three Phase 2 Hp
(575 V AC) Three Phase 2 Hp
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 25 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 3/4 hp
(200 … 208 V AC) Three Phase 2 hp
(220 … 240 V AC) Three Phase 2 hp
(240 V AC) Single Phase 1-1/2 hp
(440 … 480 V AC) Three Phase 5 hp
(550 … 600 V AC) Three Phase 7-1/2 hp
Connecting Capacity Main Circuit UL/CSA: Rigid Solid 1/2x 16-10 AWG
Rigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA: Rigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA: Rigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Full Load Amps Motor Use: (120 V AC) Single Phase 13.8 A
(200 … 208 V AC) Three Phase 7.8 A
(220 … 240 V AC) Three Phase 6.8 A
(240 V AC) Single Phase 10 A
(440 … 480 V AC) Three Phase 7.6 A
(550 … 600 V AC) Three Phase 9 A
Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay -25 … 60 °C
Close to Contactor without Thermal O/L Relay -40 … 70 °C
Close to Contactor for Storage -60 … +80 °C
Climatic Withstand: Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible: Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Closed, Shock Direction: B1 25 g
Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
Resistance to Vibrations: 4g Closed Position & 2g Open position 5 … 300 Hz
Pollution Degree: 3
Material Compliance
Conflict Minerals Reporting Template (CMRT): CMRT – Conflict Minerals Reporting Template
REACH Declaration: REACH – Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information: RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP: 8fc576d5-55a2-4153-bcd9-2c28c4558636 China (CN)
Simplified SCIP: f6621b5c-f6d7-492c-a62e-9e0c5879c198 Belgium (BE)
c2abfd30-af97-4008-b825-8a26346d4dcf Sweden (SE)
eb47294d-c148-4b27-8db9-16f8a28dabdc Germany (DE)
fdf01702-9f66-4856-a4cd-30c9d7a8a4b1 France (FR)
999187cf-3024-4f63-8b1e-ca7a8680179d Germany (DE)
82c4d031-7160-4e48-8b86-4cb2edc5a37a France (FR)
8d182c1b-e349-45a9-983d-976307d7f710 Poland (PL)
67ab2761-2ce3-47cc-9dc0-8e3f2a7d337c Poland (PL)
768106af-0faa-4768-9e65-a8a59507f2b3 Poland (PL)
64581e41-d15b-4166-9afd-1e80f61205ea Netherlands (NL)
0276ffb6-cbb8-4a73-840a-cf49e6e6a806 Estonia (EE)
e69ff59b-ba15-4d57-985f-2b72913b5c25 Finland (FI)
b14a48f0-3679-45c4-9fdb-3264430ea704 Hungary (HU)
1e80d9ea-34d9-4271-9374-81a62d951fd8 Hungary (HU)
6ffe24b0-ab27-448d-b9f6-db6075a501c0 Norway (NO)
604ceebc-7e94-4178-bee5-856128e14b54 Sweden (SE)
280b3671-1076-4b6c-b9da-038a8674de4e Germany (DE)
7b145b21-5835-4ec0-8fbe-4daac73c9551 Denmark (DK)
b6793331-ab67-488d-8978-4d217d11a7ec Germany (DE)
4f46cefb-cc98-41e3-85c0-3cd7f9823805 Portugal (PT)
572e025f-5000-4df8-b5a8-643c40102808 Belgium (BE)
2f75d400-1cab-440b-9dd6-a37d734081d8 Bulgaria (BG)
33f73846-940a-4aa8-baa5-59c0e221a123 Greece (GR)
58cdfd48-11e0-45f6-a657-79adb0d15c3e Spain (ES)
75fc3b83-2839-4bc0-b0f8-c1da98779e1f Croatia (HR)
411e5121-dc85-4741-8ae9-d00b342f2ed2 Czech Republic (CZ)
831aa781-398b-4459-89b7-5c98e8e9d99e Germany (DE)
Toxic Substances Control Act – TSCA: Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B: Business To Business
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
End Of Life Disassembling Instructions: End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration – EPD: Environmental Product Declaration – AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR)
Environmental Product Declaration – AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %): Recycled Cardboard – 86 %
Sustainable Material Content in Product (wt. %): Recycled Metal – 28 %
Certificates and Declarations
A2L Certificate – UL: 9AKK108469A4875;9AKK108469A4879
ABS Certificate: ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate: BV Certificate AF(C)09…AF(C)38 3-pole and 4-pole contactors with screw and Push-in Spring terminals
CB Certificate: CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate: CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate: CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate, Contactor, AF09,AF12,AF16, Made in China
Declaration of Conformity – CCC: CCC Declaration of Conformity, Contactor, AF:09, AF:12, AF:16, Made in France
CCC Declaration of Conformity, Contactor, AF09,AF12,AF16, Made in China
Declaration of Conformity – CE: EU Declaration of Conformity AF09… AF96-30-.., AF09…38(Z)-30..K 3-pole Contactors
Declaration of Conformity – UKCA: UK Declaration of Conformity AF09… AF96-30-.., AF09…38(Z)-30..K 3-pole Contactors
DNV Certificate: DNV Certificate AF(S)09…96 3-pole & AF09…80 4-pole contactors with screw, spring, push-in terminals
GOST Certificate: GOST_POCCFR.ME77.B07175.pdf
KC Certificate: KC Certificate AF09 3-pole contactors
LR Certificate: LRS Certificate AF(S)09..(K) … AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate: Rina Certificate for AF(S)09…AF(S)96 contactors, NF contactor relays and accessories with screw,spring and push-in terminals
RMRS Certificate: RMRS Certificate AF(S)09(S)…AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate: UL-US Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)…AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block
UL-CA Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)…AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block
UL Listing Card: E312527
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 87 mm
Package Level 1 Depth / Length: 79 mm
Package Level 1 Height: 47 mm
Package Level 1 Gross Weight: 0.27 kg
Package Level 1 EAN: 3471523110137
Package Level 2 Units: box 27 piece
Package Level 2 Width: 250 mm
Package Level 2 Depth / Length: 300 mm
Package Level 2 Height: 315 mm
Package Level 2 Gross Weight: 7.29 kg
Package Level 3 Units: 1296 piece
External Classifications and Standards
Object Classification Code: Q
ETIM 7: EC000066 – Power contactor, AC switching
ETIM 8: EC000066 – Power contactor, AC switching
ETIM 9: EC000066 – Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4758 >> Iec Contactors
E-Number (Finland): 3706204
E-Number (Sweden): 3210010