ABB AF52-30-11-12 48-130V50/60HZ-DC Contactor

General Information

Extended Product Type: AF52-30-11-12
Product ID: 1SBL367001R1211
EAN: 3471523132429
Catalog Description: AF52-30-11-12 48-130V50/60HZ-DC Contactor
Long Description: The AF52-30-11-12 is a 3 pole – 690 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 22 kW / 400 V AC (AC-3) or 40 hp / 480 V UL and switching power circuits up to 100 A (AC-1) or 80 A UL general use. Thanks to the AF technology, the contact…Show moreor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.Show less
SKU: 114114df0db4 Categories: ,

Description

Ordering
Minimum Order Quantity: 1 piece
Popular Downloads
Data Sheet, Technical Information: 1SBC100214C0202 – Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) – Edition 2024
Instructions and Manuals: Installation instructions AF(C)40(B)…96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
CAD Dimensional Drawing: Information – 2D and 3D files for CAD systems
Dimensions
Product Net Width: 67 mm
Product Net Depth / Length: 111 mm
Product Net Height: 125.5 mm
Product Net Weight: 1.01 kg
Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Number of Poles: 3P
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 100 A
(690 V) 60 °C 80 A
(690 V) 70 °C 70 A
Rated Operational Current AC-3 (Ie): (415 V) 60 °C 53 A
(440 V) 60 °C 53 A
(500 V) 60 °C 45 A
(690 V) 60 °C 35 A
(380 / 400 V) 60 °C 53 A
(220 / 230 / 240 V) 60 °C 53 A
Rated Operational Current AC-3e (Ie): (415 V) 60 °C 53 A
(440 V) 60 °C 53 A
(500 V) 60 °C 45 A
(690 V) 60 °C 35 A
(380 / 400 V) 60 °C 53 A
(220 / 230 / 240 V) 60 °C 53 A
Rated Operational Current AC-15 (Ie): (500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 100 A
(110 V) 2 Poles in Series, 60 °C 80 A
(110 V) 2 Poles in Series, 70 °C 70 A
(110 V) 3 Poles in Series, 40 °C 100 A
(110 V) 3 Poles in Series, 60 °C 80 A
(110 V) 3 Poles in Series, 70 °C 70 A
(220 V) 3 Poles in Series, 40 °C 100 A
(220 V) 3 Poles in Series, 60 °C 80 A
(220 V) 3 Poles in Series, 70 °C 70 A
(72 V) 1-Pole, 40 °C 100 A
(72 V) 1-Pole, 60 °C 80 A
(72 V) 1-Pole, 70 °C 70 A
(72 V) 2 Poles in Series, 40 °C 100 A
(72 V) 2 Poles in Series, 60 °C 80 A
(72 V) 2 Poles in Series, 70 °C 70 A
(72 V) 3 Poles in Series, 40 °C 100 A
(72 V) 3 Poles in Series, 60 °C 80 A
(72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 100 A
(110 V) 2 Poles in Series, 60 °C 80 A
(110 V) 2 Poles in Series, 70 °C 70 A
(110 V) 3 Poles in Series, 40 °C 100 A
(110 V) 3 Poles in Series, 60 °C 80 A
(110 V) 3 Poles in Series, 70 °C 70 A
(220 V) 3 Poles in Series, 40 °C 100 A
(220 V) 3 Poles in Series, 60 °C 80 A
(220 V) 3 Poles in Series, 70 °C 70 A
(72 V) 1-Pole, 40 °C 100 A
(72 V) 1-Pole, 60 °C 80 A
(72 V) 1-Pole, 70 °C 70 A
(72 V) 2 Poles in Series, 40 °C 100 A
(72 V) 2 Poles in Series, 60 °C 80 A
(72 V) 2 Poles in Series, 70 °C 70 A
(72 V) 3 Poles in Series, 40 °C 100 A
(72 V) 3 Poles in Series, 60 °C 80 A
(72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 100 A
(110 V) 2 Poles in Series, 60 °C 80 A
(110 V) 2 Poles in Series, 70 °C 70 A
(110 V) 3 Poles in Series, 40 °C 100 A
(110 V) 3 Poles in Series, 60 °C 80 A
(110 V) 3 Poles in Series, 70 °C 70 A
(220 V) 3 Poles in Series, 40 °C 100 A
(220 V) 3 Poles in Series, 60 °C 80 A
(220 V) 3 Poles in Series, 70 °C 70 A
(72 V) 1-Pole, 40 °C 100 A
(72 V) 1-Pole, 60 °C 80 A
(72 V) 1-Pole, 70 °C 70 A
(72 V) 2 Poles in Series, 40 °C 100 A
(72 V) 2 Poles in Series, 60 °C 80 A
(72 V) 2 Poles in Series, 70 °C 70 A
(72 V) 3 Poles in Series, 40 °C 100 A
(72 V) 3 Poles in Series, 60 °C 80 A
(72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Current DC-13 (Ie): (24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe): (400 V) 22 kW
(415 V) 30 kW
(440 V) 30 kW
(500 V) 30 kW
(690 V) 30 kW
(380 / 400 V) 22 kW
(220 / 230 / 240 V) 15 kW
Rated Operational Power AC-3e (Pe): (415 V) 30 kW
(440 V) 30 kW
(500 V) 30 kW
(690 V) 30 kW
(380 / 400 V) 22 kW
(220 / 230 / 240 V) 15 kW
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 690 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 6 kV
Maximum Electrical Switching Frequency: (AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Rated Control Circuit Voltage (Uc): 50 Hz 48 … 130 V
60 Hz 48 … 130 V
DC Operation 48 … 130 V
Coil Consumption: Average Holding Value 50 / 60 Hz 4 V·A
Average Holding Value 50 Hz 4 V·A
Average Holding Value 60 Hz 4 V·A
Average Holding Value DC 2 W
Average Holding Value, from Warm State 2 W
Power Loss: at 6 A per Pole 0.1 W
at Rated Operating Conditions AC-1 per Pole 6.3 W
at Rated Operating Conditions AC-3 per Pole 1.7 W
Operate Time: Between Coil De-energization and NC Contact Closing 19 … 105 ms
Between Coil De-energization and NO Contact Opening 17 … 100 ms
Between Coil Energization and NC Contact Opening 38 … 95 ms
Between Coil Energization and NO Contact Closing 42 … 100 ms
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied): 2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 4 … 35 mm²
Flexible with Insulated Ferrule 1/2x 4 … 35 mm²
Rigid Stranded 1/2x 6 … 35 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Rigid 1/2x 1 … 2.5 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 1.5 mm²
Rigid Solid 1/2x 1 … 2.5 mm²
Rigid Stranded 1/2x 1 … 2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 16 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver: Pozidriv PZ
Tightening Torque: Auxiliary Circuit 1.2 N·m
Control Circuit 1.2 N·m
Main Circuit 4 N·m
Terminal Type: Screw Terminals
Product Name: Block Contactor
Technical UL/CSA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 80 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 3 hp
(200 … 208 V AC) Three Phase 15 hp
(220 … 240 V AC) Three Phase 20 hp
(240 V AC) Single Phase 10 hp
(440 … 480 V AC) Three Phase 40 hp
(550 … 600 V AC) Three Phase 50 hp
Connecting Capacity Main Circuit UL/CSA: Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA: Rigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 35 in·lb
Full Load Amps Motor Use: (120 V AC) Single Phase 34 A
(200 … 208 V AC) Three Phase 48.3 A
(220 … 240 V AC) Three Phase 54 A
(240 V AC) Single Phase 50 A
(440 … 480 V AC) Three Phase 52 A
(550 … 600 V AC) Three Phase 52 A
Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay -40 … 70 °C
Close to Contactor without Thermal O/L Relay -40 … 70 °C
Close to Contactor for Storage -60 … +80 °C
Climatic Withstand: Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible: Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Closed, Shock Direction: A 25 g
Closed, Shock Direction: B1 25 g
Closed, Shock Direction: B2 15 g
Closed, Shock Direction: C1 25 g
Closed, Shock Direction: C2 25 g
Open, Shock Direction: B1 5 g
Resistance to Vibrations: 3g Closed Position & 3g Open Position 5 … 300 Hz
Pollution Degree: 3
Material Compliance
Conflict Minerals Reporting Template (CMRT): CMRT – Conflict Minerals Reporting Template
REACH Declaration: REACH – Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information: RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP: 84c7f357-1853-47f7-bbd3-7b49b035ac15 France (FR)
Simplified SCIP: 49876f32-8762-4643-9b04-543d89e93a95 Germany (DE)
aac63bd3-8589-4ab6-ac83-a6907f48a470 Norway (NO)
a955b49e-16d8-4d74-a814-96cff1a1ea61 Hungary (HU)
eeced8db-0c74-442e-8b17-ce1c1b4f53fe Estonia (EE)
7d7a3700-71e7-4c38-a027-1c0ef90978a1 Greece (GR)
1bd77b53-7f36-4f22-a703-8fb89ca04acd Portugal (PT)
389e97ad-17de-4efa-9693-2297d057950f Bulgaria (BG)
0acf96de-4928-4125-af7b-9179b76d4f35 Poland (PL)
00777a4b-a1a5-45fb-8437-50ec5f06ef2c Denmark (DK)
eabac23c-19bc-4320-8000-12012cafc0bf Germany (DE)
f16dd249-9fd1-4096-b729-04ac1633d942 Croatia (HR)
6e36aeb8-31e0-4f03-a8a8-8026a50c5d4e Czech Republic (CZ)
51973ce0-afba-425b-bf34-389ef11332f3 Poland (PL)
3afb91e8-e981-4da8-b619-51b23644a2d4 Netherlands (NL)
b88dd937-ea30-4b03-82a8-fc41db2e52cc Sweden (SE)
8ebeb442-20b2-4318-9912-7e95ebd361c8 Poland (PL)
e3647e26-9b46-46e7-b370-aec3bb82dea7 France (FR)
dbb0cd41-5d9c-4b6c-aa2e-2591d0b15485 Sweden (SE)
d9e4007a-532b-4253-8125-cf18a329f014 Germany (DE)
f9a3892d-6b16-40fb-b34b-c14e77336761 Germany (DE)
ab0c05c3-cc96-48d1-a5b4-e40f3791a277 Hungary (HU)
e53b5698-0ea5-4862-92e1-d07763c1fe76 Spain (ES)
b11419f4-93f8-4cee-aa8e-7aea68f61aa6 Belgium (BE)
f563e6b0-3415-4462-bd75-a4a17c257047 Finland (FI)
5bdcb09e-ccc1-40bb-b35f-1beb75a167ff Belgium (BE)
51540c72-d0f9-44d7-961f-f3399a3b2341 Italy (IT)
8e55e821-742d-42d7-851c-4f6f3fdceec1 Germany (DE)
Toxic Substances Control Act – TSCA: Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B: Business To Business
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutions: Yes
End Of Life Disassembling Instructions: End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration – EPD: Environmental Product Declaration AF40, AF52, AF65 (CN)
Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %): FSC Recycled Paper – 94.6 %
Sustainable Material Content in Product (wt. %): Recycled Metal – 28.2 %
Certificates and Declarations
A2L Certificate – UL: 9AKK108469A4890;9AKK108469A4892
ABS Certificate: ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate: BV_2634H36994B1
CB Certificate: CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate: CQC Certificate, Contactor, AF:40-30-::-::, AF40-40-::-::, AF40-22-::-::, AF:52-30-::-::, AF52-40-::-::,AF:65-30-::-::, Made in France
CQC Certificate: CQC Certificate, Contactor, AF:40-30-::-::, AF40-40-::-::, AF40-22-::-::, AF:52-30-::-::, AF52-40-::-::,AF:65-30-::-::, Made in France
CQC Certificate, Contactor, AF40, AF52, AF65, AFC40, AFC52, AFC65, Made in China
Declaration of Conformity – CCC: CCC Declaration of Conformity, Contactor, AF:40-30-::-::, AF40-40-::-::, AF40-22-::-::, AF:52-30-::-::, AF52-40-::-::,AF:65-30-::-::, Made in France
CCC Declaration of Conformity, Contactor, AF(C)40, AF52(C), AF65(C),AFC78 Made in China
Declaration of Conformity – CE: EU Declaration of Conformity AF09… AF96-30-.., AF09…38(Z)-30..K 3-pole Contactors
Declaration of Conformity – UKCA: UK Declaration of Conformity AF09… AF96-30-.., AF09…38(Z)-30..K 3-pole Contactors
DNV Certificate: DNV Certificate AF(S)09…96 3-pole & AF09…80 4-pole contactors with screw, spring, push-in terminals
KC Certificate: KC Certificate AF52 3-pole Contactors
LR Certificate: LRS Certificate AF(S)09..(K) … AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate: Rina Certificate for AF09…AF96 contactors, NF contactor relays and accessories, screw and spring terminals
RMRS Certificate: RMRS Certificate AF(S)09(S)…AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate: UL-US-L312527-1141-10303102-9
UL-CA-L312527-4141-10303102-9
UL Listing Card: UL_E312527
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 150 mm
Package Level 1 Depth / Length: 150 mm
Package Level 1 Height: 97 mm
Package Level 1 Gross Weight: 1.11 kg
Package Level 1 EAN: 3471523132429
Package Level 2 Units: box 10 piece
Package Level 2 Width: 250 mm
Package Level 2 Depth / Length: 300 mm
Package Level 2 Height: 300 mm
Package Level 2 Gross Weight: 11.1 kg
Package Level 3 Units: 240 piece
External Classifications and Standards
Object Classification Code: Q
ETIM 7: EC000066 – Power contactor, AC switching
ETIM 8: EC000066 – Power contactor, AC switching
ETIM 9: EC000066 – Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4758 >> Iec Contactors
E-Number (Finland): 3707022

Downloads