ABB AF400-30-11-69 48-130V50/60HZ-DC Contactor

General Information

Extended Product Type: AF400-30-11-69
Product ID: 1SFL577001R6911
EAN: 7320500217832
Catalog Description: AF400-30-11 48-130V 50/60Hz / 48-130V DC Contactor
Long Description: The AF400-30-11-69 is a 3 pole – 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 200 kW / 400 V AC (AC-3) or 350 hp / 480 V UL and switching power circuits up to 600 A (AC-1) or 550 A UL general use. Thanks to the AF technology, th…Show moree contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.Show less
SKU: ce36f0a686db Categories: ,

Description

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Data Sheet, Technical Information: 1SBC100214C0202 – Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) – Edition 2024
Instructions and Manuals: 1SFC380023-en
CAD Dimensional Drawing: Information – 2D and 3D files for CAD systems
Dimension Diagram: 53540919-59
Dimensions
Product Net Width: 186 mm
Product Net Depth / Length: 216 mm
Product Net Height: 278 mm
Product Net Weight: 10.6 kg
Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Number of Poles: 3P
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 600 A
Rated Operational Current AC-1 (Ie): (1000 V) 40 °C 600 A
(1000 V) 55 °C 500 A
(1000 V) 70 °C 400 A
(690 V) 40 °C 600 A
(690 V) 55 °C 500 A
(690 V) 70 °C 400 A
Rated Operational Current AC-3 (Ie): (415 V) 55 °C 400 A
(440 V) 55 °C 400 A
(500 V) 55 °C 400 A
(690 V) 55 °C 350 A
(1000 V) 55 °C 155 A
(380 / 400 V) 55 °C 400 A
(220 / 230 / 240 V) 55 °C 400 A
Rated Operational Current DC-1 (Ie): (110 V) 1-Pole, 40 °C 600 A
(110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
(600 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Current DC-3 (Ie): (110 V) 1-Pole, 40 °C 600 A
(110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
(600 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Current DC-5 (Ie): (110 V) 1-Pole, 40 °C 600 A
(110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
(600 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Power AC-3 (Pe): (415 V) 220 kW
(440 V) 220 kW
(500 V) 250 kW
(690 V) 315 kW
(1000 V) 220 kW
(380 / 400 V) 200 kW
(220 / 230 / 240 V) 110 kW
Rated Breaking Capacity AC-3: 8 x Ie AC-3
Rated Making Capacity AC-3: 10 x Ie AC-3
Short-Circuit Protective Devices: gG Type Fuses 630 A
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 4400 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 840 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 4600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3500 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): Main Circuit 8 kV
Maximum Electrical Switching Frequency: (AC-1) 300 cycles per hour
(AC-2 / AC-4) 60 cycles per hour
(AC-3) 300 cycles per hour
Mechanical Durability: 3 million
Maximum Mechanical Switching Frequency: 300 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. … 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc): 50 Hz 48 … 130 V
60 Hz 48 … 130 V
DC Operation 48 … 130 V
Coil Consumption: Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A
Holding at Max. Rated Control Circuit Voltage DC 5 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 1215 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 1215 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 1150 V·A
Power Loss: at Rated Operating Conditions per Pole 16 W
Operate Time: Between Coil De-energization and NC Contact Closing 45 … 55 ms
Between Coil De-energization and NO Contact Opening 48 … 58 ms
Between Coil Energization and NC Contact Opening 45 … 115 ms
Between Coil Energization and NO Contact Closing 50 … 120 ms
Connecting Capacity Main Circuit: Bar 47 mm²
Rigid Al-Cable 240 mm²
Rigid Cu-Cable 240 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 2.5 mm²
Flexible 2×0.75 … 2.5 mm²
Solid 2 x 1 … 4 mm²
Stranded 2 x 1 …. 4 mm²
Connecting Capacity: Bar 47 mm²
Rigid Al-Cable 2×240 mm²
Rigid Cu-Cable 240 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening Torque: Cable Lug 35 N·m
Main Circuit 35 N·m
Terminal Type: Main Circuit: Bars
Product Name: Block Contactor
Technical UL/CSA
Maximum Operating Voltage UL/CSA: Main Circuit 1000 V
General Use Rating UL/CSA: (600 V AC) 550 A
Horsepower Rating UL/CSA: (200 V AC) Three Phase 125 hp
(208 V AC) Three Phase 125 hp
(220 … 240 V AC) Three Phase 150 hp
(440 … 480 V AC) Three Phase 350 hp
(550 … 600 V AC) Three Phase 400 hp
Full Load Amps Motor Use: (440 … 480 V AC) Three Phase 414 A
(550 … 600 V AC) Three Phase 382 A
Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 … 1.1 Uc) -25 … 50 °C
Close to Contactor without Thermal O/L Relay (0.85 … 1.1 Uc) -40 … 70 °C
Close to Contactor for Storage -40 … 70 °C
Maximum Operating Altitude Permissible: Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Shock Direction: A 5 g
Shock Direction: B1 5 g
Shock Direction: B2 5 g
Shock Direction: C1 5 g
Shock Direction: C2 5 g
Material Compliance
Conflict Minerals Reporting Template (CMRT): CMRT – Conflict Minerals Reporting Template
REACH Declaration: REACH – Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information: RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act – TSCA: Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B: Business To Business
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutions: Yes
ABB Site Meeting Group Waste To Landfill Target: Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions: End-of-life instruction – AF(S)400(B)-::;AF(S)460(B)-::;AF460N6
Environmental Product Declaration – EPD: Environmental Product Declaration, Contactors, AF(S)400-AF(S)460 (SE)
Improved Energy Efficiency for Customers: Product Efficiency – Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops – Standard EN45555 – 63.1 %
Sustainable Material Content in Product (wt. %): Recycled Metal – 37 %
Certificates and Declarations
ABS Certificate: ABS Certificate, Contactor, AF400…AF2050 (Sweden)
BV Certificate: BV Certificate, Contactor, AF400 … AF2850
CB Certificate: SE-82316
CCS Certificate: CCS Certificate, Contactor, AF116 to AF2850 (Sweden)
CQC Certificate: CQC Certificate, AC Contactor, AF400-30-:-:,AF460-30-:-:,AFS400-30-:-:, AFS460-30-:-:, Made in Sweden
CQC Certificate, Contactor, AF400, AF460, Made in China
Declaration of Conformity – CCC: CCC Declaration of Conformity, AC Contactor, AF400-30-:-:,AF460-30-:-:,AFS400-30-:-:, AFS460-30-:-:, Made in Sweden
CCC Declaration of Conformity, Contactor, AF400, AF460, Made in China
Declaration of Conformity – CE: CE Declaration of Conformity – Contactor – AF400…AF2850
Declaration of Conformity – UKCA: UK Declaration of Conformity – Contactors >100A
DNV Certificate: DNV_E-10966
DNV GL Certificate: DNV Certificate, Contactor, AF400…AF2850
EAC Certificate: 9AKK107046A8618
GL Certificate: GL_42988-02HH
LOVAG Certificate: SE-0115101
LR Certificate: Lloyds register Certificate, Contactor, AF400…AF2850
PRS Certificate: PRS Certificate – AF116…AF1650
RINA Certificate: RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate: 9AKK107045A6978
UL Certificate: cULus Certificate, Contactor, AF400, AF460, AFS400, AFS460
UL Listing Card: UL_E36588
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 280 mm
Package Level 1 Depth / Length: 375 mm
Package Level 1 Height: 310 mm
Package Level 1 Gross Weight: 12 kg
Package Level 1 EAN: 7320500217832
External Classifications and Standards
Object Classification Code: Q
ETIM 7: EC000066 – Power contactor, AC switching
ETIM 8: EC000066 – Power contactor, AC switching
ETIM 9: EC000066 – Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4758 >> Iec Contactors
E-Number (Norway): 4115287
E-Number (Sweden): 3228334

Downloads