ABB UA16-30-10 110V 50Hz / 110-120V 60Hz

General Information

Extended Product Type: UA16-30-10 110V 50Hz / 110-120V 60Hz
Product ID: 1SBL181022R8410
EAN: 3471522254849
Catalog Description: UA16-30-10 110V 50Hz / 110-120V 60Hz Contactor
Long Description: UA16 3-pole contactors for capacitor switching, can be used for the switching of capacitor banks whose inrush current peaks are less than or equal to 100 times nominal rms current. The table below gives the permissible powers according to operational voltage and temperature close to the contactor. I…Show moret also specifies the maximum peak current Î values accepted by the contactor. The capacitors must be discharged (maximum residual voltage at terminals ≤ 50 V) before being re-energized when the contactors are making. In these conditions, electrical durability of contactors is equal to 100 000 operating cycles. The UA.. series 3-pole contactors are of the block type design. – Main poles and auxiliary contacts: 3 main poles, 1 built-in auxiliary contact – Control circuit: AC operated with laminated magnet circuit – Accessories: a wide range of accessories is available.Show less
SKU: b22c8575879b Categories: ,

Description

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Data Sheet, Technical Information: 1SBC100214C0202 – Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) – Edition 2024
Instructions and Manuals: Operating Instructions A9 … A16, UA16, AE9 … AE16, TAE9 … TAE16, N22E … N80E, NE12 … NE30E
CAD Dimensional Drawing: Information – 2D and 3D files for CAD systems
Dimensions
Product Net Width: 44 mm
Product Net Depth / Length: 74 mm
Product Net Height: 74 mm
Product Net Weight: 0.34 kg
Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 0
Number of Poles: 3P
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (Ie): (500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie): (24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 2 / 144 W
(110 V) 1.1 A / 121 W
(125 V) 1.1 / 138 W
(220 V) 0.55 A / 121 W
(250 V) 0.55 / 138 W
Rated Operational Power AC-6b (Pe): (230 / 240 V) 40 °C, 50 / 60 Hz 7.5 kvar
(230 / 240 V) 55 °C, 50 / 60 Hz 6.7 kvar
(230 / 240 V) 70 °C, 50 / 60 Hz 6 kvar
(400 / 415 V) 40 °C, 50 / 60 Hz 12.5 kvar
(400 / 415 V) 70 °C, 50 / 60 Hz 10 kvar
(400 / 415 V) 55 °C, 50 / 60 Hz 11.7 kvar
(440 V) 40 °C, 50 / 60 Hz 13.7 kvar
(440 V) 55 °C, 50 / 60 Hz 13 kvar
(440 V) 70 °C, 50 / 60 Hz 11 kvar
(500 / 550 V), 40 °C, 50 / 60 Hz 15.5 kvar
(500 / 550 V) 55 °C, 50 / 60 Hz 14.7 kvar
(500 / 550 V) 70 °C, 50 / 60 Hz 12.5 kvar
(690 V) 40 °C, 50 / 60 Hz 21.5 kvar
(690 V) 55 °C, 50 / 60 Hz 20 kvar
(690 V) 70 °C, 50 / 60 Hz 17 kvar
Short-Circuit Protective Devices: Auxiliary Circuit – gG Type Fuses 10 A
gG Type Fuses 1.5 … 1.8 A
Rated Short-time Withstand Current Low Voltage (Icw): for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 1000 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Minimum Switching Capacity: 17 / 5 VLT4K
Rated Control Circuit Voltage (Uc): 50 Hz 110 V
60 Hz 110 … 120 V
Coil Consumption: Average Holding Value 50 / 60 Hz 8 V·A
Average Pull-in Value 50 Hz 74 V·A
Average Pull-in Value 60 Hz 70 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 70 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 80 V·A
Power Loss: at Rated Operating Conditions per Pole 0.1 W
at 6 A per Pole 0.1 W
Operate Time: Between Coil De-energization and NO Contact Opening 4 … 11 ms
Between Coil Energization and NO Contact Closing 10 … 26 ms
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied): 2 x M4 screws placed diagonally
Connecting Capacity Main Circuit: Flexible with Cable End 1/2x 0.75 … 2.5 mm²
Rigid Solid 1/2x 1 … 4 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Cable End 1/2x 0.75 … 2.5 mm²
Rigid Solid 1/2x 1 … 4 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Connecting Terminals (delivered in open position) Main Poles: M 3.5 (+,-) pozidriv 2 screws with cable clamp
Terminal Type: Screw Terminals
Product Name: Block Contactor
Technical UL/CSA
Connecting Capacity Main Circuit UL/CSA: 1/2x 18-10 AWG
Environmental
Ambient Air Temperature: Close to Contactor for Storage -60 … +80 °C
Near Contactor for Operation in Free Air (0.85 … 1.1 Uc) -40 … +55 °C
Near Contactor for Operation in Free Air (Uc) -40 … 70 °C
Climatic Withstand: acc. to IEC 60068-2-30 and 60068-2-11 – UTE C 63-100 specification II
Maximum Operating Altitude Permissible: Without Derating 3000 m
Pollution Degree: 3
Material Compliance
Conflict Minerals Reporting Template (CMRT): CMRT – Conflict Minerals Reporting Template
REACH Declaration: REACH – Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information: RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act – TSCA: Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B: Business To Business
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
Certificates and Declarations
CB Certificate: CB Test Certificate UA16 Contactors
CCC Certificate: CCC Certificate for UA16 contactor
CCC Certificate for UA16 contactor Made in China
CQC Certificate: CQC Certificate, Contactors for capacitor switching, UA16, Made in Bulgaria
CQC Certificate, Contactor, UA16-30-10,UA16-30-01, Made in China
Declaration of Conformity – CCC: CCC Declaration of Conformity, Contactors for capacitor switching, UA16, Made in Bulgaria
CCC Declaration of Conformity, Contactor, UA16-30-10,UA16-30-01, Made in China
Declaration of Conformity – CE: EU Declaration of Conformity UA16 to UA75, UA16..RA to UA75..RA 3pole contactors
Declaration of Conformity – UKCA: UK Declaration of Conformity UA16 to UA75, UA16..RA to UA75..RA 3pole contactors
GOST Certificate: GOST_POCCFRME77B07175
UL Certificate: UL Certificate of Compliance A/AL/TAL/AE9…16, UA16..(RA) contactors
UL Certificate of Compliance A/AL/TAL/AE9…16, UA16..(RA) contactors
UL Listing Card: UL_E312527
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 78 mm
Package Level 1 Depth / Length: 76 mm
Package Level 1 Height: 47 mm
Package Level 1 Gross Weight: 0.34 kg
Package Level 1 EAN: 3471522254849
Package Level 2 Units: box 63 piece
Package Level 2 Width: 300 mm
Package Level 2 Depth / Length: 245 mm
Package Level 2 Height: 308 mm
Package Level 2 Gross Weight: 21.42 kg
Package Level 3 Units: 1220 piece
External Classifications and Standards
Object Classification Code: Q
ETIM 7: EC001079 – Capacitor contactor
ETIM 8: EC001079 – Capacitor contactor
ETIM 9: EC001079 – Capacitor contactor
eClass: V11.0 : 27371006
UNSPSC: 39121529