ABB AF1350-30-11-70 100-250V50/60HZ-DC Contactor

General Information

Extended Product Type: AF1350-30-11-70
Product ID: 1SFL657001R7011
EAN: 7320500250143
Catalog Description: AF1350-30-11 100-250V 50/60Hz / 100-250V DC Contactor
Long Description: The AF1350-30-11-70 is a 3 pole – 1000 V IEC or 1000 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 475 kW / 400 V AC (AC-3) or 800 hp / 480 V UL and switching power circuits up to 1350 A (AC-1) or 1350 A UL general use. Thanks to the AF technology…Show more, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.Show less
SKU: d4e682b7042a Categories: ,

Description

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Data Sheet, Technical Information: 1SBC100214C0202 – Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) – Edition 2024
Instructions and Manuals: Operating instruction, Contactors AF1350, AF1650,AF2050
CAD Dimensional Drawing: Information – 2D and 3D files for CAD systems
Dimension Diagram: Dimension Drawing, Contactor, AF1350, AF1650
Dimensions
Product Net Width: 438 mm
Product Net Depth / Length: 244 mm
Product Net Height: 392 mm
Product Net Weight: 32 kg
Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Number of Poles: 3P
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1350 A
Rated Operational Current AC-1 (Ie): (1000 V) 40 °C 1350 A
(1000 V) 55 °C 1150 A
(1000 V) 70 °C 1000 A
(690 V) 40 °C 1350 A
(690 V) 55 °C 1150 A
(690 V) 70 °C 1000 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 55 °C 860 A
Rated Operational Current DC-1 (Ie): (220 V) 3 Poles in Series, 40 °C 1350 A
(600 V) 3 Poles in Series, 40 °C 1350 A
(850 V) 3 Poles in Series, 40 °C 1350 A
Rated Operational Current DC-3 (Ie): (220 V) 3 Poles in Series, 40 °C 1350 A
(600 V) 3 Poles in Series, 40 °C 1350 A
(850 V) 3 Poles in Series, 40 °C 1350 A
Rated Operational Current DC-5 (Ie): (220 V) 3 Poles in Series, 40 °C 1350 A
(600 V) 3 Poles in Series, 40 °C 1350 A
(850 V) 3 Poles in Series, 40 °C 1350 A
Rated Operational Power AC-3 (Pe): (415 V) 500 kW
(440 V) 560 kW
(500 V) 560 kW
(690 V) 800 kW
(1000 V) 560 kW
(380 / 400 V) 475 kW
(220 / 230 / 240 V) 257 kW
Rated Making Capacity AC-3: 10 x Ie AC-3
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 8000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 4500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 10000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 6000 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 10000 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp): Main Circuit 8 kV
Maximum Electrical Switching Frequency: (AC-1) 60 cycles per hour
(AC-2 / AC-4) 60 cycles per hour
(AC-3) 60 cycles per hour
Mechanical Durability: 0.5 million
Maximum Mechanical Switching Frequency: 300 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. … 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc): 50 Hz 100 … 250 V
60 Hz 100 … 250 V
DC Operation 100 … 250 V
Coil Consumption: Holding at Max. Rated Control Circuit Voltage 50 Hz 48 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 48 V·A
Holding at Max. Rated Control Circuit Voltage DC 20.5 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 2450 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 2450 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 2290 V·A
Power Loss: at Rated Operating Conditions per Pole 80 W
Operate Time: Between Coil De-energization and NC Contact Closing 35 … 55 ms
Between Coil De-energization and NO Contact Opening 35 … 55 ms
Between Coil Energization and NC Contact Opening 50 … 80 ms
Between Coil Energization and NO Contact Closing 50 … 80 ms
Connecting Capacity Main Circuit: Bar 100 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 1x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Flexible 2×0.75 … 2.5 mm²
Solid 2 x 1 … 4 mm²
Stranded 1 x 1 …. 4 mm²
Connecting Capacity: Bar 100 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening Torque: Cable Lug 45 N·m
Terminal Type: Main Circuit: Bars
Product Name: Block Contactor
Technical UL/CSA
Maximum Operating Voltage UL/CSA: Main Circuit 1000 V
General Use Rating UL/CSA: (1000 V AC) 1350 A
(600 V AC) 1350 A
Horsepower Rating UL/CSA: (220 … 240 V AC) Three Phase 400 hp
(440 … 480 V AC) Three Phase 800 hp
(550 … 600 V AC) Three Phase 1000 hp
Full Load Amps Motor Use: (440 … 480 V AC) Three Phase 954 A
(550 … 600 V AC) Three Phase 944 A
Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 … 1.1 Uc) -25 … 50 °C
Close to Contactor without Thermal O/L Relay (0.85 … 1.1 Uc) -40 … 70 °C
Close to Contactor for Storage -40 … 70 °C
Maximum Operating Altitude Permissible: Without Derating 3000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT): CMRT – Conflict Minerals Reporting Template
REACH Declaration: REACH – Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information: RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act – TSCA: Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B: Business To Business
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
End Of Life Disassembling Instructions: End-of-life instruction – AF1350(B)(T), AF1650(B)(T), AF1650N8, AF2050(B)(T), AF2650(B)(T), AF2850(B)(T)
Environmental Product Declaration – EPD: Environmental product declaration AF1350(T), AF1650(T)(N), AF2050(T), AF2650(T), AF2850 (SE)
Environmental product declaration AF1350, AF1650, AF2050, AF2650 (CN) Contactors
Certificates and Declarations
ABS Certificate: ABS Certificate, Contactor, AF400…AF2050 (Sweden)
BV Certificate: BV Certificate, Contactor, AF400 … AF2850
CB Certificate: SEMKO_SE-74013
CCS Certificate: CCS Certificate, Contactor, AF116 to AF2850 (Sweden)
CQC Certificate: CQC Certificate, AC Contactor, AF1350-30-:-:, AF1650-30-:-:, AF2050-30-:-:, AF1350T-30-:-:, AF1650T-30-:-:, AF2050T-30-:-:, Made in Sweden
CQC Certificate, Contactor, AF1350, AF1650, AF2050, Made in China
Declaration of Conformity – CCC: CCC Declaration of Conformity, AC Contactor, AF1350-30-:-:, AF1650-30-:-:, AF2050-30-:-:, AF1350T-30-:-:, AF1650T-30-:-:, AF2050T-30-:-:, Made in Sweden
CCC Declaration of Conformity, Contactor, AF1350, AF1650, AF2050, Made in China
Declaration of Conformity – CE: CE Declaration of Conformity – Contactor – AF400…AF2850
Declaration of Conformity – UKCA: UK Declaration of Conformity – Contactors >100A
DNV GL Certificate: DNV Certificate, Contactor, AF400…AF2850
EAC Certificate: 9AKK107046A8618
GL Certificate: GL_20263-04HH
LOVAG Certificate: SE-202726
LR Certificate: Lloyds register Certificate, Contactor, AF400…AF2850
PRS Certificate: PRS Certificate – AF116…AF1650
RINA Certificate: RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate: 9AKK107045A6978
UL Certificate: cULus Certificate, Contactor, AF1350, AF1650, AF2050 (NLDX)
UL Listing Card: UL_E73397
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 555 mm
Package Level 1 Depth / Length: 365 mm
Package Level 1 Height: 500 mm
Package Level 1 Gross Weight: 34 kg
Package Level 1 EAN: 7320500250143
Package Level 2 Units: 1 piece
External Classifications and Standards
Object Classification Code: Q
ETIM 7: EC000066 – Power contactor, AC switching
ETIM 8: EC000066 – Power contactor, AC switching
ETIM 9: EC000066 – Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4758 >> Iec Contactors
E-Number (Finland): 3709257
E-Number (Norway): 4115388
E-Number (Sweden): 4115388

Downloads