ABB AF140-40-00-11 24-60V50/60HZ 20-60VDC Contactor

General Information

Extended Product Type: AF140-40-00-11
Product ID: 1SFL447101R1100
EAN: 7320500503607
Catalog Description: AF140-40-00-11 Contactor
Long Description: The AF140-40-00-11 is a 4 pole – 690 V IEC or 600 V UL contactor with double clamp, controlling motors up to 75 kW / 400 V AC (AC-3) / and switching power circuits up to 200 A (AC-1) or 175 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 H…Show morez and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.Show less
SKU: 67bf742eba55 Categories: ,

Description

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Data Sheet, Technical Information: 1SBC100214C0202 – Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) – Edition 2024
Instructions and Manuals: Operating instruction, Contactor, AF(S)116, AF140, AF(S)146
CAD Dimensional Drawing: Information – 2D and 3D files for CAD systems
Dimension Diagram: Dimension Drawing. Contactor,AF116,AF140,AF146
Dimensions
Product Net Width: 120 mm
Product Net Depth / Length: 128 mm
Product Net Height: 150 mm
Product Net Weight: 2.05 kg
Technical
Number of Main Contacts NO: 4
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 0
Number of Poles: 4P
Rated Operational Voltage: Main Circuit 690 V
Rated Frequency (f): Main Circuit 50 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 200 A
(690 V) 60 °C 175 A
(690 V) 70 °C 160 A
Rated Operational Current AC-3 (Ie): (415 V) 55 °C 140 A
(440 V) 55 °C 140 A
(380 / 400 V) 55 °C 140 A
(220 / 230 / 240 V) 55 °C 140 A
Rated Operational Power AC-3 (Pe): (415 V) 75 kW
(440 V) 90 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 37 kW
Rated Breaking Capacity AC-3: 8 x Ie AC-3
Rated Making Capacity AC-3: 10 x Ie AC-3
Short-Circuit Protective Devices: gG Type Fuses 250 A
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): Main Circuit 8 kV
Maximum Electrical Switching Frequency: (AC-1) 300 cycles per hour
Mechanical Durability: 5 million
Maximum Mechanical Switching Frequency: 300 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. … 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc): 50 Hz 24 … 60 V
60 Hz 24 … 60 V
DC Operation 20 … 60 V
Coil Consumption: Holding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 210 W
Power Loss: 18 W
at Rated Operating Conditions per Pole 18 W
Operate Time: Between Coil De-energization and NO Contact Opening 40 … 70 ms
Between Coil Energization and NO Contact Closing 20 … 55 ms
Connecting Capacity Main Circuit: Flexible 2 x 10 … 70 mm²
Rigid Cu-Cable 2 x 10 … 95 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 2.5 mm²
Flexible 1×0.75 … 2.5 mm²
Solid 2 x 1 … 4 mm²
Stranded 2 x 1 …. 4 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening Torque: Cable Lug 9 N·m
Main Circuit 8 N·m
Terminal Type: Double Clamp
Product Name: Block Contactor
Technical UL/CSA
NEMA Size: 4
Horsepower Rating NEMA: (200 V AC) Three Phase 40 Hp
(230 V AC) Three Phase 50 Hp
(460 V AC) Three Phase 100 Hp
(575 V AC) Three Phase 100 Hp
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 200 A
Horsepower Rating UL/CSA: (200 … 208 V AC) Three Phase 15 Hp
(200 V AC) Three Phase 40 hp
(208 V AC) Three Phase 40 hp
(220 … 240 V AC) Three Phase 20 Hp
(220 … 240 V AC) Three Phase 50 hp
(440 … 480 V AC) Three Phase 40 Hp
(440 … 480 V AC) Three Phase 100 hp
(550 … 600 V AC) Three Phase 50 Hp
(550 … 600 V AC) Three Phase 125 hp
Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 … 1.1 Uc) -25 … 50 °C
Close to Contactor without Thermal O/L Relay (0.85 … 1.1 Uc) -40 … 70 °C
Close to Contactor for Storage -40 … 70 °C
Maximum Operating Altitude Permissible: Without Derating 3000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT): CMRT – Conflict Minerals Reporting Template
REACH Declaration: REACH – Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information: RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act – TSCA: Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B: Business To Business
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutions: Yes
ABB Site Meeting Group Waste To Landfill Target: Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions: End-of-life instruction – AF(S)116(B)-::(RT) to AF(S)205(B)-::(RT)
Environmental Product Declaration – EPD: Environmental Product Declaration, AF(S)116-AF(S)146 (SE) Contactors
Improved Energy Efficiency for Customers: Product Efficiency – Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops – Standard EN45555 – 87.8 %
Sustainable Material Content in Product (wt. %): Recycled Metal – 37 %
Certificates and Declarations
ABS Certificate: ABS Approval, Contactor, AF116 … AF370 (Sweden)
BV Certificate: BV Certificate, Contactor, AF116-30 … AF370-30…AF116-40…AF370-40
CB Certificate: SEMKO_SE-77317
CQC Certificate: CQC Certificate, AC Contactor, AF116-:-:-:, AF140-:-:-:, AF146-:-:-:, AF116B-:-:-:, AF140B-:-:-:, AF146B-:-:-:, AFS116-30-:-:,AFS140-30-:-:, AFS146-30-:-:, Made in Sweden
Declaration of Conformity – CCC: CCC Declaration of Conformity, AC Contactor, AF116-:-:-:, AF140-:-:-:, AF146-:-:-:, AF116B-:-:-:, AF140B-:-:-:, AF146B-:-:-:, AFS116-30-:-:,AFS140-30-:-:, AFS146-30-:-:, Made in Sweden
Declaration of Conformity – CE: CE Declaration of Conformity – Contactor – AF116B…RT to AF370B…RT
Declaration of Conformity – UKCA: UK Declaration of Conformity – Contactors >100A
DNV GL Certificate: DNV-certificate, Contactors, AF116-30…AF370-30 and AF116-40…AF370-40
EAC Certificate: 9AKK107046A8618
KC Certificate: KC Certificate, Contactor, AF116-40…AF140-40 (Sweden)
LR Certificate: Lloyds register Certificate, Contactor, AF116-30 … AF370-30, AF116-40…AF370-40
PRS Certificate: PRS Certificate – AF116…AF1650
RINA Certificate: RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate: 9AKK107045A6978
UL Certificate: cULus Certificate, Contactor, AF116-40, AF140-40 (4-pole)
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 147 mm
Package Level 1 Depth / Length: 197 mm
Package Level 1 Height: 155 mm
Package Level 1 Gross Weight: 2.25 kg
Package Level 1 EAN: 7320500503607
External Classifications and Standards
Object Classification Code: Q
ETIM 7: EC000066 – Power contactor, AC switching
ETIM 8: EC000066 – Power contactor, AC switching
ETIM 9: EC000066 – Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4758 >> Iec Contactors
E-Number (Finland): 3706081

Downloads