ABB AF40-30-11-13 100-250V50/60HZ-DC Contactor

General Information

Extended Product Type: AF40-30-11-13
Product ID: 1SBL347001R1311
EAN: 3471523132139
Catalog Description: AF40-30-11-13 100-250V50/60HZ-DC Contactor
Long Description: The AF40-30-11-13 is a 3 pole – 690 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 18.5 kW / 400 V AC (AC-3) or 30 hp / 480 V UL and switching power circuits up to 70 A (AC-1) or 60 A UL general use. Thanks to the AF technology, the contac…Show moretor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.Show less
SKU: e01bb73522ba Categories: ,

Description

Ordering
Minimum Order Quantity: 1 piece
Popular Downloads
Data Sheet, Technical Information: 1SBC100214C0202 – Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) – Edition 2024
Instructions and Manuals: Installation instructions AF(C)40(B)…96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
CAD Dimensional Drawing: Information – 2D and 3D files for CAD systems
Dimensions
Product Net Width: 67 mm
Product Net Depth / Length: 111 mm
Product Net Height: 125.5 mm
Product Net Weight: 0.99 kg
Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Number of Poles: 3P
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 70 A
(690 V) 60 °C 60 A
(690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie): (415 V) 60 °C 40 A
(440 V) 60 °C 40 A
(500 V) 60 °C 35 A
(690 V) 60 °C 25 A
(380 / 400 V) 60 °C 40 A
(220 / 230 / 240 V) 60 °C 40 A
Rated Operational Current AC-3e (Ie): (415 V) 60 °C 40 A
(440 V) 60 °C 40 A
(500 V) 60 °C 35 A
(690 V) 60 °C 25 A
(380 / 400 V) 60 °C 40 A
(220 / 230 / 240 V) 60 °C 40 A
Rated Operational Current AC-15 (Ie): (500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 70 A
(110 V) 2 Poles in Series, 60 °C 60 A
(110 V) 2 Poles in Series, 70 °C 50 A
(110 V) 3 Poles in Series, 40 °C 70 A
(110 V) 3 Poles in Series, 60 °C 60 A
(110 V) 3 Poles in Series, 70 °C 50 A
(220 V) 3 Poles in Series, 40 °C 70 A
(220 V) 3 Poles in Series, 60 °C 60 A
(220 V) 3 Poles in Series, 70 °C 50 A
(72 V) 1-Pole, 40 °C 70 A
(72 V) 1-Pole, 60 °C 60 A
(72 V) 1-Pole, 70 °C 50 A
(72 V) 2 Poles in Series, 40 °C 70 A
(72 V) 2 Poles in Series, 60 °C 60 A
(72 V) 2 Poles in Series, 70 °C 50 A
(72 V) 3 Poles in Series, 40 °C 70 A
(72 V) 3 Poles in Series, 60 °C 60 A
(72 V) 3 Poles in Series, 70 °C 50 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 70 A
(110 V) 2 Poles in Series, 60 °C 60 A
(110 V) 2 Poles in Series, 70 °C 50 A
(110 V) 3 Poles in Series, 40 °C 70 A
(110 V) 3 Poles in Series, 60 °C 60 A
(110 V) 3 Poles in Series, 70 °C 50 A
(220 V) 3 Poles in Series, 40 °C 70 A
(220 V) 3 Poles in Series, 60 °C 60 A
(220 V) 3 Poles in Series, 70 °C 50 A
(72 V) 1-Pole, 40 °C 70 A
(72 V) 1-Pole, 60 °C 60 A
(72 V) 1-Pole, 70 °C 50 A
(72 V) 2 Poles in Series, 40 °C 70 A
(72 V) 2 Poles in Series, 60 °C 60 A
(72 V) 2 Poles in Series, 70 °C 50 A
(72 V) 3 Poles in Series, 40 °C 70 A
(72 V) 3 Poles in Series, 60 °C 60 A
(72 V) 3 Poles in Series, 70 °C 50 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 70 A
(110 V) 2 Poles in Series, 60 °C 60 A
(110 V) 2 Poles in Series, 70 °C 50 A
(110 V) 3 Poles in Series, 40 °C 70 A
(110 V) 3 Poles in Series, 60 °C 60 A
(110 V) 3 Poles in Series, 70 °C 50 A
(220 V) 3 Poles in Series, 40 °C 70 A
(220 V) 3 Poles in Series, 60 °C 60 A
(220 V) 3 Poles in Series, 70 °C 50 A
(72 V) 1-Pole, 40 °C 70 A
(72 V) 1-Pole, 60 °C 60 A
(72 V) 1-Pole, 70 °C 50 A
(72 V) 2 Poles in Series, 40 °C 70 A
(72 V) 2 Poles in Series, 60 °C 60 A
(72 V) 2 Poles in Series, 70 °C 50 A
(72 V) 3 Poles in Series, 40 °C 70 A
(72 V) 3 Poles in Series, 60 °C 60 A
(72 V) 3 Poles in Series, 70 °C 50 A
Rated Operational Current DC-13 (Ie): (24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe): (400 V) 18.5 kW
(415 V) 22 kW
(440 V) 22 kW
(500 V) 22 kW
(690 V) 22 kW
(380 / 400 V) 18.5 kW
(220 / 230 / 240 V) 11 kW
Rated Operational Power AC-3e (Pe): (415 V) 22 kW
(440 V) 22 kW
(500 V) 22 kW
(690 V) 22 kW
(380 / 400 V) 18.5 kW
(220 / 230 / 240 V) 11 kW
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 690 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 6 kV
Maximum Electrical Switching Frequency: (AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Rated Control Circuit Voltage (Uc): 50 Hz 100 … 250 V
60 Hz 100 … 250 V
DC Operation 100 … 250 V
Coil Consumption: Average Holding Value 50 / 60 Hz 4 V·A
Average Holding Value 50 Hz 4 V·A
Average Holding Value 60 Hz 4 V·A
Average Holding Value DC 2 W
Average Holding Value, from Warm State 2 W
Power Loss: at 6 A per Pole 0.1 W
at Rated Operating Conditions AC-1 per Pole 3 W
at Rated Operating Conditions AC-3 per Pole 1 W
Operate Time: Between Coil De-energization and NC Contact Closing 19 … 105 ms
Between Coil De-energization and NO Contact Opening 17 … 100 ms
Between Coil Energization and NC Contact Opening 38 … 95 ms
Between Coil Energization and NO Contact Closing 42 … 100 ms
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied): 2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 4 … 35 mm²
Flexible with Insulated Ferrule 1/2x 4 … 35 mm²
Rigid Stranded 1/2x 6 … 35 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Rigid 1/2x 1 … 2.5 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 1.5 mm²
Rigid Solid 1/2x 1 … 2.5 mm²
Rigid Stranded 1/2x 1 … 2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 16 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver: Pozidriv PZ
Tightening Torque: Auxiliary Circuit 1.2 N·m
Control Circuit 1.2 N·m
Main Circuit 4 N·m
Terminal Type: Screw Terminals
Product Name: Block Contactor
Technical UL/CSA
NEMA Size: 2
Continuous Current Rating NEMA: 45 A
Horsepower Rating NEMA: (115 V AC) Single Phase 3 Hp
(200 V AC) Three Phase 10 Hp
(230 V AC) Single Phase 7-1/2 Hp
(230 V AC) Three Phase 15 Hp
(460 V AC) Three Phase 25 Hp
(575 V AC) Three Phase 25 Hp
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 60 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 3 hp
(200 … 208 V AC) Three Phase 10 hp
(220 … 240 V AC) Three Phase 15 hp
(240 V AC) Single Phase 7-1/2 hp
(440 … 480 V AC) Three Phase 30 hp
(550 … 600 V AC) Three Phase 40 hp
Connecting Capacity Main Circuit UL/CSA: Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA: Rigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 35 in·lb
Full Load Amps Motor Use: (120 V AC) Single Phase 34 A
(200 … 208 V AC) Three Phase 32.2 A
(220 … 240 V AC) Three Phase 42 A
(240 V AC) Single Phase 40 A
(440 … 480 V AC) Three Phase 41 A
(550 … 600 V AC) Three Phase 40 A
Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay -40 … 70 °C
Close to Contactor without Thermal O/L Relay -40 … 70 °C
Close to Contactor for Storage -60 … +80 °C
Climatic Withstand: Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible: Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Closed, Shock Direction: A 25 g
Closed, Shock Direction: B1 25 g
Closed, Shock Direction: B2 15 g
Closed, Shock Direction: C1 25 g
Closed, Shock Direction: C2 25 g
Open, Shock Direction: B1 5 g
Resistance to Vibrations: 3g Closed Position & 3g Open Position 5 … 300 Hz
Pollution Degree: 3
Material Compliance
Conflict Minerals Reporting Template (CMRT): CMRT – Conflict Minerals Reporting Template
REACH Declaration: REACH – Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information: RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP: bba93f86-cab1-4bdf-98ab-334e20efebe9 France (FR)
Simplified SCIP: aab41b3b-f288-46ae-b2a9-06e5f0b4471b Germany (DE)
4cb5d32e-29e0-4631-a0a4-af9ef3b0eea0 Hungary (HU)
8870b071-fc03-4cf2-95d9-54102176a134 Spain (ES)
109b52fa-80da-4dbb-a67d-1e0dbe015481 Belgium (BE)
4b433990-61a0-428b-8d4c-7e537c2c769a Hungary (HU)
518243f6-bedf-44e1-9109-1cf79ae8ecbb Estonia (EE)
527e7616-d3ca-4045-acfa-81dea5cffa55 Greece (GR)
c25e8e6c-ba6c-4c5f-a742-75212abf86c8 Portugal (PT)
6a54e910-6e1d-48da-b1cd-e0aac9c0b2c7 Bulgaria (BG)
03b61e36-715c-40e0-90a8-ec718552d68f Poland (PL)
50d16ee4-9f75-44eb-9b03-b4e649f32257 Finland (FI)
580aaa2e-4e3b-4357-99c4-d2c79a273474 Germany (DE)
6b98ee8b-c69a-41c2-9dc1-5ca099b085ff Norway (NO)
e49814bb-2f00-4505-bc1f-cac94c92c89e Belgium (BE)
39f7085c-b580-4a36-a322-6deb6bbfee18 Italy (IT)
33e3abc9-d491-4037-8812-094130f748bf Poland (PL)
a9f4599f-4ce0-40e3-ba3d-67d507cecba9 France (FR)
eb0cd70f-e340-44d0-9a25-6a9f16a2202e Sweden (SE)
fb1128a1-c3c1-47a7-a1c6-05ed233d9ceb Germany (DE)
217ec338-1b73-4044-9791-ab6d2afadb2f Germany (DE)
e29fd3d2-c7d3-45e8-886d-590dfc194a4c Denmark (DK)
429eb4d1-7c50-486e-965f-a2c15ca0b21e Germany (DE)
e8de44f6-c08e-414e-aa2e-23205315eb28 Croatia (HR)
f8c26055-6f16-4130-b9a4-013e9ed58758 Czech Republic (CZ)
8b2fea28-3b77-460b-b679-d0ba79a8bf6d Poland (PL)
4bdaa5ea-c540-4347-899e-a74f681b3d8f Netherlands (NL)
8cb1740b-9b65-4e96-bd26-79a9684c7a42 Sweden (SE)
Toxic Substances Control Act – TSCA: Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B: Business To Business
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutions: Yes
End Of Life Disassembling Instructions: End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration – EPD: Environmental Product Declaration AF40, AF52, AF65 (CN)
Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %): FSC Recycled Paper – 94.6 %
Sustainable Material Content in Product (wt. %): Recycled Metal – 28.2 %
Certificates and Declarations
A2L Certificate – UL: 9AKK108469A4890;9AKK108469A4892
ABS Certificate: ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate: BV_2634H36994B1
CB Certificate: CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate: CQC Certificate, Contactor, AF:40-30-::-::, AF40-40-::-::, AF40-22-::-::, AF:52-30-::-::, AF52-40-::-::,AF:65-30-::-::, Made in France
CQC Certificate: CQC Certificate, Contactor, AF:40-30-::-::, AF40-40-::-::, AF40-22-::-::, AF:52-30-::-::, AF52-40-::-::,AF:65-30-::-::, Made in France
CQC Certificate, Contactor, AF40, AF52, AF65, AFC40, AFC52, AFC65, Made in China
Declaration of Conformity – CCC: CCC Declaration of Conformity, Contactor, AF:40-30-::-::, AF40-40-::-::, AF40-22-::-::, AF:52-30-::-::, AF52-40-::-::,AF:65-30-::-::, Made in France
CCC Declaration of Conformity, Contactor, AF(C)40, AF52(C), AF65(C),AFC78 Made in China
Declaration of Conformity – CE: EU Declaration of Conformity AF09… AF96-30-.., AF09…38(Z)-30..K 3-pole Contactors
Declaration of Conformity – UKCA: UK Declaration of Conformity AF09… AF96-30-.., AF09…38(Z)-30..K 3-pole Contactors
DNV Certificate: DNV Certificate AF(S)09…96 3-pole & AF09…80 4-pole contactors with screw, spring, push-in terminals
KC Certificate: KC Certificate AF40 3-pole Contactors
LR Certificate: LRS Certificate AF(S)09..(K) … AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate: Rina Certificate for AF09…AF96 contactors, NF contactor relays and accessories, screw and spring terminals
RMRS Certificate: RMRS Certificate AF(S)09(S)…AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate: UL-US-L312527-1141-10303102-9
UL-CA-L312527-4141-10303102-9
UL Listing Card: UL_E312527
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 150 mm
Package Level 1 Depth / Length: 150 mm
Package Level 1 Height: 97 mm
Package Level 1 Gross Weight: 1.09 kg
Package Level 1 EAN: 3471523132139
Package Level 2 Units: box 10 piece
Package Level 2 Width: 250 mm
Package Level 2 Depth / Length: 300 mm
Package Level 2 Height: 300 mm
Package Level 2 Gross Weight: 10.9 kg
Package Level 3 Units: 240 piece
External Classifications and Standards
Object Classification Code: Q
ETIM 7: EC000066 – Power contactor, AC switching
ETIM 8: EC000066 – Power contactor, AC switching
ETIM 9: EC000066 – Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4758 >> Iec Contactors
E-Number (Finland): 3707004