ABB B6-40-00-85 Mini Contactor 380 … 415 V AC – 4 NO – 0 NC – Screw Terminals

General Information

Extended Product Type: B6-40-00-85
Product ID: GJL1211201R8005
EAN: 4013614156489
Catalog Description: B6-40-00-85 Mini Contactor 380 … 415 V AC – 4 NO – 0 NC – Screw Terminals
Long Description: The B6-40-00 mini contactor is a compact 4 pole contactor with screw terminals. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 4 kW (AC-3) and 20 A (AC-1) or switching of control signals. Further features are the silent coil, a switch position indication and the integrated possibility for rail or wall mounting.
SKU: fa2e5ee9a618 Categories: ,

Description

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85365080
Popular Downloads
Data Sheet, Technical Information: 1SBC100214C0202
Instructions and Manuals: 2CDC102047M6801
CAD Dimensional Drawing: 2CDC001079B0201
Dimension Diagram: GJL1200436F0001
Dimensions
Product Net Width: 52.5 mm
Product Net Height: 57.5 mm
Product Net Depth / Length: 46.7 mm
Product Net Weight: 0.175 kg
Technical
Number of Poles: 4
Mini Contactor Type: Mini Contactor
Rated Operational Voltage: Main Circuit 690 V AC
Main Circuit 220 V DC
Rated Frequency (f): Control Circuit 400 Hz
Control Circuit 50 Hz
Control Circuit 60 Hz
Main Circuit 50 Hz
Main Circuit 60 Hz
Main Circuit DC
Rated Impulse Withstand Voltage (Uimp): Main Circuit 6 kV
Rated Insulation Voltage (Ui): 690 V
acc. to UL/CSA 600 V
Number of Main Contacts NC: 0
Number of Main Contacts NO: 4
Rated Operational Current AC-1 (Ie): (220 / 240 V) 40 °C 20 A
(220 / 240 V) 55 °C 16 A
(380 / 440 V) 40 °C 20 A
(380 / 440 V) 55 °C 16 A
(690 V) 40 °C 6 A
(690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe): (230 V) Three Phase 2.2 kW
(400 V) Three Phase 4 kW
(500 V) Three Phase 4 kW
(690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Number of Auxiliary Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Conventional Free-air Thermal Current (Ith): Main Circuit 20 A
Rated Control Circuit Voltage (Uc): 380 … 415 V AC
Coil Operating Limits: (acc. to IEC 60947-4-1) for AC supply 0.85 … 1.1 x Uc (at θ ‰¤ 55 °C)
Degree of Protection: Control Circuit Terminals IP20
Main Circuit Terminals IP20
Mechanical Durability: 10000000 cycle
Maximum Electrical Switching Frequency: (AC-1) 300 cycles per hour
(AC-3) 600 cycles per hour
(DC-1) 600 cycles per hour
(DC-3) 600 cycles per hour
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 1 … 2.5 mm²
Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm²
Flexible 1/2x 1 … 2.5 mm²
Rigid 1/2x 1 … 4 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 1 … 2.5 mm²
Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm²
Flexible 1/2x 1 … 2.5 mm²
Rigid 1/2x 1 … 4 mm²
Wire Stripping Length: Main Circuit 9 mm
Tightening Torque: Control Circuit 0.8 … 1.1 N·m
Main Circuit 0.8 … 1.1 N·m
Recommended Screw Driver: M3
Pozidriv 1
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss: at Rated Operating Conditions AC-1 per Pole 1 W
Standards: IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
Technical UL/CSA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V AC
Full Load Amps Motor Use: (115 V AC) Single Phase 5.8 A
(200 V AC) Three Phase 4.8 A
(220 … 240 V AC) Three Phase 6.8 A
(230 V AC) Single Phase 4.9 A
(440 … 480 V AC) Three Phase 4.8 A
(550 … 600 V AC) Three Phase 1.7 A
Horsepower Rating UL/CSA: (115 V AC) Single Phase 0.25 Hp
(200 V AC) Three Phase 1 Hp
(220 … 240 V AC) Three Phase 2 Hp
(230 V AC) Single Phase 0.5 Hp
(440 … 480 V AC) Three Phase 3 Hp
(550 … 600 V AC) Three Phase 1 Hp
General Use Rating UL/CSA: (300 V AC) 12 A
Connecting Capacity Main Circuit UL/CSA: Stranded 1/2x 22-10 AWG
Tightening Torque UL/CSA: Control Circuit 7 in·lb
Main Circuit 7 in·lb
Environmental
Ambient Air Temperature: Operation -20 … +55 °C
Storage -40 … +80 °C
Maximum Operating Altitude Permissible: 2000 m
Resistance to Shock acc. to IEC 60068-2-27: 11 ms Pulse 15g
Resistance to Vibrations: 5g 5 … 150 Hz
Material Compliance
Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
REACH Declaration: 2CMT2021-006202
RoHS Information: 2CMT2021-006277
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act – TSCA: 2CMT2023-006525
WEEE B2C / B2B: Business To Business
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
Certificates and Declarations
A2L Certificate €“ IEC: 1SAA938000-4601
BV Certificate: 1SAA920000-0204
CB Certificate: 1SAA938000-2002
CQC Certificate: CQC2003010304064033
Declaration of Conformity – CCC: 2020980304001854
Declaration of Conformity – CE: 1SAD101100-3101
Declaration of Conformity – UKCA: 1SAD201100-3101
DNV GL Certificate: 1SAA938000-0306
EAC Certificate: 1SAA920000-2702
KC Certificate: 1SAA938000-1501
LR Certificate: 1SAA938000-0504
RMRS Certificate: 1SAA938000-0704
UL Certificate: E191658-19881208
Container Information
Package Level 1 Units: box 10 piece
Package Level 1 Width: 115 mm
Package Level 1 Height: 54 mm
Package Level 1 Depth / Length: 280 mm
Package Level 1 Gross Weight: 1.82 kg
Package Level 1 EAN: 4013614413230
Classifications
Object Classification Code: Q
ETIM 4: EC000066 – Magnet contactor, AC-switching
ETIM 5: EC000066 – Magnet contactor, AC-switching
ETIM 6: EC000066 – Power contactor, AC switching
ETIM 7: EC000066 – Power contactor, AC switching
ETIM 8: EC000066 – Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
E-Number (Sweden): 3210046

Downloads

Certificate Datasheet