Description
Ordering | |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85365080 |
Product Main Type: | KC6 |
Popular Downloads | |
Data Sheet, Technical Information: | 1SBC100214C0202 |
Instructions and Manuals: | 2CDC102047M6801 |
CAD Dimensional Drawing: | 2CDC001079B0201 |
Dimension Diagram: | GJL1200436F0001 |
Dimensions | |
Product Net Width: | 52.5 mm |
Product Net Depth / Length: | 46.5 mm |
Product Net Height: | 57.5 mm |
Product Net Weight: | 0.175 kg |
Technical | |
Coil Consumption: | Average Holding Value DC 3.5 W Average Pull-in Value DC 3.5 W |
Coil Operating Limits: | (acc. to IEC 60947-5-1) for DC supply 0.85 … 1.1 x Uc (at θ ‰¤ 55 °C) |
Connecting Capacity Auxiliary Circuit: | Flexible with Ferrule 1/2x 1 … 2.5 mm² Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm² Flexible 1/2x 1 … 2.5 mm² Rigid 1/2x 1 … 4 mm² |
Connecting Capacity Control Circuit: | Flexible with Ferrule 1/2x 1 … 2.5 mm² Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm² Flexible 1/2x 1 … 2.5 mm² Rigid 1/2x 1 … 4 mm² |
Maximum Electrical Switching Frequency: | (AC-15) 600 cycles per hour (DC-13) 600 cycles per hour |
Mechanical Durability: | 10000000 cycle |
Mini Contactor Type: | Mini Contactor Relay |
Minimum Mounting Distance: | Other Device Same Type, Horizontal 0 mm |
Minimum Switching Capacity: | 17 V 5 mA |
Mounting Position: | 1 … 6 |
Mounting Type: | DIN-Rail Screw |
Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Number of Auxiliary Contacts NC: | 2 |
Number of Auxiliary Contacts NO: | 2 |
Number of Main Contacts NC: | 0 |
Number of Main Contacts NO: | 0 |
Number of Poles: | 4 |
Power Loss: | at Rated Operating Conditions per Pole 0.32 W |
Rated Control Circuit Voltage (Uc): | 48 V DC |
Rated Frequency (f): | Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC Control Circuit DC Main Circuit 60 Hz Main Circuit 50 Hz Main Circuit DC |
Rated Impulse Withstand Voltage (Uimp): | Auxiliary Circuit 6 kV |
Rated Insulation Voltage (Ui): | 690 V acc. to UL/CSA 600 V |
Rated Operational Current AC-15 (Ie): | (24 V) 4 A (120 V) 4 A (240 V) 4 A (400 V) 3 A (500 V) 2 A |
Rated Operational Current DC-13 (Ie): | (24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A |
Rated Operational Voltage: | Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC |
Recommended Screw Driver: | M3 Pozidriv 1 |
Short-Circuit Protective Devices: | gG Type Fuses 6 A |
Standards: | IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L |
Terminal Type: | Screw Terminals |
Tightening Torque: | Auxiliary Circuit 0.8 … 1.1 N·m Control Circuit 0.8 … 1.1 N·m Main Circuit 0.8 … 1.1 N·m |
Wire Stripping Length: | Auxiliary Circuit 9 mm |
Technical UL/CSA | |
Connecting Capacity Auxiliary Circuit UL/CSA: | Stranded 1/2x 22-10 AWG |
Contact Rating UL/CSA: | A600 |
General Use Rating UL/CSA: | (600 V AC) 5 A |
Maximum Operating Voltage UL/CSA: | 600 V AC |
Pilot Duty UL/CSA: | A600 |
Tightening Torque UL/CSA: | Auxiliary Circuit 7 in·lb Control Circuit 7 in·lb |
Environmental | |
Ambient Air Temperature: | Operation -25 … +55 °C Storage -40 … +80 °C |
Conventional Free-air Thermal Current (Ith): | Auxiliary Circuit 6 A |
Degree of Protection: | Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 |
Maximum Operating Altitude Permissible: | 2000 m |
Resistance to Shock acc. to IEC 60068-2-27: | 11 ms Pulse 15g |
Resistance to Vibrations: | 3g 3 … 150 Hz |
Material Compliance | |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
REACH Declaration: | 2CMT2021-006202 |
RoHS Information: | 2CMT2021-006277 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Toxic Substances Control Act – TSCA: | 2CMT2023-006525 |
WEEE B2C / B2B: | Business To Business |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
Certificates and Declarations | |
A2L Certificate €“ IEC: | 1SAA938000-4601 |
CB Certificate: | 1SAA938001-2001 |
CQC Certificate: | CQC2003010304064035 |
Declaration of Conformity – CCC: | 2020980304001309 |
Declaration of Conformity – CE: | 1SAD101100-3101 |
Declaration of Conformity – UKCA: | 1SAD201100-3101 |
EAC Certificate: | 1SAA938001-2701 |
RMRS Certificate: | 1SAA938001-0704 |
UL Certificate: | E48139-19881213 |
Container Information | |
Package Level 1 Units: | box 10 piece |
Package Level 1 Width: | 115 mm |
Package Level 1 Depth / Length: | 280 mm |
Package Level 1 Height: | 54 mm |
Package Level 1 Gross Weight: | 1.82 kg |
Package Level 1 EAN: | 4013614411052 |
Classifications | |
eClass: | V11.0 : 27371001 |
ETIM 6: | EC000196 – Contactor relay |
ETIM 7: | EC000196 – Contactor relay |
ETIM 8: | EC000196 – Contactor relay |
ETIM 9: | EC000196 – Contactor relay |
IDEA Granular Category Code (IGCC): | 4763 >> Power contactor, DC switching |
Object Classification Code: | K |
UNSPSC: | 39121529 |