Description
| Technical | |
| Standards: | IEC/EN 60898-1 |
| Tripping Characteristic: | C |
| Rated Operational Voltage: | acc. to IEC 60898-1 230 V AC |
| Operational Voltage: | Maximum (Incl. Tolerance) 253 V AC Minimum 12 V AC |
| Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp): | 4 kV at 2000 m 5 kV at Sea Level 6.2 kV |
| Dielectric Test Voltage: | 50/60 Hz, 1 min: 2 kV |
| Input Voltage Type: | AC |
| Rated Current (In): | 50 A |
| Rated Short-Circuit Capacity: | (AC) 6 kA (230 / 400 V AC) 6 kA (230 V) 6 kA |
| Rated Conditional Short-Circuit Current (Inc): | (230 V) 6 kA |
| Rated Frequency (f): | 50 / 60 Hz |
| Power Loss: | 3.25 W at Rated Operating Conditions per Pole 3.25 W |
| Power Supply Connection: | Arbitrary |
| Contact Position Indication: | ON / OFF |
| Energy Limiting Class: | 3 |
| Electrical Endurance: | 10000 AC cycle |
| Mechanical Endurance: | 20000 cycle |
| Number of Protected Poles: | 1 |
| Number of Poles: | 1 |
| Overvoltage Category: | III |
| Tightening Torque: | 2 N·m |
| Actuator Type: | Toggle |
| Screw Terminal Type: | Cage Terminal |
| Actuator Marking: | I / O |
| Actuator Material: | Insulation Group II, Black, Sealable |
| Housing Material: | Insulation Group II, RAL 7035 |
| Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Mounting Position: | any |
| Recommended Screw Driver: | Pozidriv 2 |
| Accessories Available: | No |
| Connecting Capacity: | Conductor 25 / 25 mm² Flexible with Ferrule 0.75 … 16 mm² Flexible 0.75 … 16 mm² Rigid 0.75 … 25 mm² Stranded 0.75 … 25 mm² |
| Installation Size: | acc. to DIN 43880 1 |
| Terminal Type: | Screw Terminals |
| Material Compliance | |
| RoHS Information: | 2CDK400030D0201 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date: | 0335 |
| REACH Declaration: | 9AKK108468A9644 |
| REACH Information: | True – contains substances > 0.1 mass percentage |
| REACH Date: | 20231212 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108468A3363 |
| Environmental | |
| Ambient Air Temperature: | Operation -25 … +55 °C Storage -40 … +70 °C |
| Reference Ambient Air Temperature: | 30 °C |
| Degree of Protection: | IP20 Enclosure with Cover IP40 |
| Pollution Degree: | 2 |
| Environmental Conditions: | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
| Resistance to Vibrations: | 20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27: | 25g 2 shocks 13 ms |
| Environmental Information: | 2CDK400030D0201 |
| Dimensions | |
| Width in Number of Modular Spacings: | 1.0 |
| Product Net Width: | 17.5 mm |
| Product Net Height: | 85 mm |
| Product Net Depth / Length: | 69 mm |
| Product Net Weight: | 0.125 kg |
| Pole Net Weight: | 0.125 kg |
| Built-In Depth (t2): | 69 mm |
| Ordering | |
| Package Level 1 Units: | carton 10 piece |
| Package Level 1 Gross Weight: | 1.29 kg |
| Certificates and Declarations | |
| Certification Agency: | EN IEC |
| Declaration of Conformity – CE: | 2CDK400607D2703 |
| Installation | |
| Instructions and Manuals: | 2CDS207105P0001 |
| Popular Downloads | |
| Data Sheet, Technical Information: | 2CSC400030D0202 |
| Classifications | |
| ETIM 8: | EC000042 – Miniature circuit breaker (MCB) |
| ETIM 9: | EC000042 – Miniature circuit breaker (MCB) |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B: | Business To Business |
| CN8: | 8536 20 10 |
| UNSPSC: | 39121603 |
| eClass: | V11.0 : 27141901 |
| IDEA Granular Category Code (IGCC): | 4897 >> Miniature circuit breakers |
| Object Classification Code: | F |