Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | dfffc0b3-275c-4afb-85d2-fb95dc5c1a90 Italy (IT) |
| Simplified SCIP: | d8f3ceae-ac79-493c-abf5-30fb8f5c5fd8 Germany (DE) 07d83eab-e766-44eb-ade5-6f4efbf3d099 Poland (PL) 8d8ff8a0-f0fa-423d-b019-88da3d01f3c8 Norway (NO) 0df604d1-dea7-4d0b-b460-df618976cd0e Finland (FI) fbda3a53-01f7-4a6d-ab8d-ae4eff52baed Netherlands (NL) a3a08ef1-5cfc-4642-b459-3ffbcbf989b4 Germany (DE) 9ca0f39e-a1d5-4b5e-b628-3a858888df61 Denmark (DK) b2eb429f-aba8-4a51-8dec-22f5686f9ced Germany (DE) 13d894ec-98dc-4540-aa67-20ca86ae4636 Croatia (HR) 64e7ad0d-89db-41a1-b23f-a5c3e7543cf2 Czech Republic (CZ) 3ca9d06b-7af7-4e1a-b458-44dd79e4166b Poland (PL) e1e8ccfd-e67e-46a5-9fa0-b5bbaf1ee632 Netherlands (NL) 1aee0c1b-19b1-49f6-8772-3e44b970c5e6 Netherlands (NL) b85c8bd5-b064-48bb-a79d-07712b1d3b74 Estonia (EE) 8fcb9348-1666-4fca-b96c-3fe1ff34398a Greece (GR) 97000770-294d-43c2-a581-b758391bce74 Portugal (PT) c7cc62ca-74b7-4858-9811-756a4541c687 Bulgaria (BG) 1d06ee5b-04b6-473c-ac30-79908273713a Sweden (SE) a55ab81b-f486-4cb9-bfec-974145cbaf3d Poland (PL) 23e3c382-3a3b-4708-a045-f10377c33a6b France (FR) 2ca0c4dc-5dfc-4ab4-a72a-f5ba8b518c91 Sweden (SE) bca5eac6-b106-47cf-b1fd-0f56213d94ba Germany (DE) cda3b236-f5ae-4c05-adbc-a026c1c8b322 Germany (DE) 6728e3db-d91f-4c09-9911-cf2c315015c1 France (FR) 605f2fd8-645d-4fab-b7db-cae0aaf621ff Netherlands (NL) 7a2eae21-ee98-44fe-ba3d-de24092dd143 Spain (ES) 3d17c99b-c081-4669-a654-d02e7277633f Netherlands (NL) |
| Ordering | |
| Order Code US and Canada: | XT1BE4160AFF000XXX |
| EAN: | 8015644007287 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 101.6 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.4 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.454 kg |
| Package Level 1 EAN: | 8015644007287 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0080 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 4 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 15 W |
| Rated Current (In): | 160 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 1600 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.25 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 112…160 A |
| Short-Circuit Performance Level: | B |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |