Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | bc495a05-c140-4988-9a16-a75662da70e2 Italy (IT) |
| Simplified SCIP: | ddae66c2-806b-433d-b0a2-0db487196333 Poland (PL) 122696f2-3fa0-4945-afb1-410ceb6762e8 Netherlands (NL) 9d52a2a2-4fb6-44a0-a705-f65f8ff4be20 Poland (PL) c361546f-306a-4455-9f5f-241e24d22663 Bulgaria (BG) 942fcae2-db75-42f4-bd74-89204158abed Spain (ES) 9e46ddc5-ee73-4d48-949a-668636faf426 Belgium (BE) 0fa78f38-ea3b-4be1-b4ef-6fb3654fac5e Germany (DE) 944d09ba-f5f8-4f94-8c15-41460326a0b0 Sweden (SE) e07051f8-5614-4721-9f3d-5b05cbbe51d4 Greece (GR) 1ff2493b-dd4b-4ad1-9224-5f6804904a02 Portugal (PT) f27b2979-3d6a-4238-ae4b-3c9800cb0795 Denmark (DK) 58c725e8-585c-431b-b2c4-5f49a34d5723 Germany (DE) 7d8febd2-0e5a-40e1-b06a-797d0f179bb2 Croatia (HR) 8f3f0fa5-68a6-45f8-8b84-4cc619fcf13f Germany (DE) 946f6757-10e1-43a2-8fdb-01b82bda1e44 Hungary (HU) 5595a4f6-e801-4228-8452-7ebe621ef40d Sweden (SE) caef1e41-57e1-4860-9c80-347c923506b5 France (FR) b50eaabb-fb5d-47d7-b9de-125008569443 Hungary (HU) 30d55ba4-87a2-4332-b85b-fd6ef2e0ed5f Germany (DE) 34c93eb5-cd33-47a1-a4d5-95b33745f90e Norway (NO) 5fbd1ffd-7557-4a7b-8ffc-5e057bfa07c6 Poland (PL) 6b97ba35-0f47-4a3f-8cf0-b5fcbf01abf9 Finland (FI) e5165853-a978-4a23-9093-7e879bbb452c Belgium (BE) 7a3ea3b7-fc81-4249-8880-d25479827c02 Germany (DE) 28222e96-8a15-4e07-8024-e0a6b949d329 Estonia (EE) 9cf04b3e-483c-4cb2-ba47-11645a801d33 Czech Republic (CZ) |
| Ordering | |
| Order Code US and Canada: | XT1BE4050AFF000XXX |
| E-Number (Finland): | 3640508 |
| EAN: | 8015644694524 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 101.6 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.4 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.441 kg |
| Package Level 1 EAN: | 8015644694524 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0080 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 4 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 3.7 W |
| Rated Current (In): | 50 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 500 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.25 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 35…50 A |
| Short-Circuit Performance Level: | B |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |