Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | 3bb20cfc-7083-4831-8a5f-6054dd508236 Italy (IT) |
| Simplified SCIP: | 3934955e-58c9-4d96-9f50-eae65e58c63c Germany (DE) 1fbc0a20-3b02-4587-9f4c-7f9cfac73274 France (FR) 4cc6f899-d5ef-433a-a0ce-72acb32f7c5f Hungary (HU) 1eba0e6b-9bd9-49f4-a41d-3265890cb7c6 Spain (ES) ad4398b2-2f39-4271-a88a-3590a4b6458a Belgium (BE) d74811d4-a212-4daf-8156-8a4bc9fa3876 Czech Republic (CZ) ac7d32d5-f35e-411a-96f4-3b5fc249b722 Croatia (HR) 1ced2162-5ba6-45a8-9c57-d8bb4c027438 Sweden (SE) 47a312b1-6132-496e-ab8a-cf514d24c5d8 Germany (DE) 74206dc9-a8d4-4e65-904d-b4a749d91b32 Denmark (DK) 30b6650c-3ca1-40d3-a419-b65baff53027 Germany (DE) 642b0283-8f82-4808-953d-bc134f5b3604 France (FR) 1428167b-999f-4124-85e9-135cb1e79913 Greece (GR) fc03168f-c0d5-439c-9ce1-16c0d44231bc Belgium (BE) 9eaacf65-ef8f-4df2-8242-8dc53c235e6c Sweden (SE) 6814870a-108c-44e0-9a91-dd7aaf5dc19c Finland (FI) abb08200-d402-49b8-ac93-9b3c083f27a6 Netherlands (NL) 78d058ae-56ca-4f74-929e-02718f00d9ff Norway (NO) c9e98a9c-5380-4502-b7ac-e9ae1c9e3f05 Estonia (EE) a8e58da8-6afd-4230-836e-2ec90c7a3ce5 Hungary (HU) 0cc665f2-5192-4db0-9dbe-30b69a8c5620 Poland (PL) 39f4a141-2a7a-4976-adc1-84e5449fe7db Bulgaria (BG) cabdcf5a-c05f-4326-9f0c-451135e7227b Poland (PL) bac84bcd-3332-4efe-85ef-e4883bd639a8 Poland (PL) 86f2b063-ac4e-469b-a25e-dd307bbe26dd Portugal (PT) 5725a9e8-ee35-4a12-a76b-937034ff4219 Germany (DE) 107e117e-82b3-4565-8ccd-57e8e4af5dd2 Germany (DE) |
| Ordering | |
| Order Code US and Canada: | XT1CE4025AFF000XXX |
| E-Number (Finland): | 3640514 |
| EAN: | 8015644012946 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 101.6 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.4 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.435 kg |
| Package Level 1 EAN: | 8015644012946 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0080 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 4 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 2 W |
| Rated Current (In): | 25 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 450 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 17.5…25 A |
| Short-Circuit Performance Level: | C |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |