Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | f8a3db18-b215-4bf0-a188-36b92353ada8 Italy (IT) |
| Simplified SCIP: | 4e7a6161-4fb1-4b8a-8a4b-542662f9e352 Germany (DE) 61163b89-f1d3-4644-940f-389133811615 Norway (NO) 2f6d6e62-1dcc-47cf-ad5c-29c527733f13 France (FR) 8f5b62da-4d76-4087-8af5-5e267aa1bcbd Netherlands (NL) a5b18f3c-1c9e-449f-b68a-6bd7c7c24284 Estonia (EE) b5e666e4-dbce-4a12-99f4-267847012e0c Greece (GR) 159b8e0c-28d9-4a88-aa7e-aee17a1f5e01 Portugal (PT) 49caf4a0-669f-44aa-8705-1686cc584012 Bulgaria (BG) 1dee6090-aae8-48be-9df2-02b6bafff9eb Sweden (SE) f5ac57bd-6df7-45cd-8a34-b9742ee54117 Poland (PL) 04919024-e6ac-4bbc-8560-440eb1c781e5 Netherlands (NL) 4ed2cdb0-2e6d-42d6-8906-e2c821f942f9 Germany (DE) 8ae58a5c-dcda-4cc8-a917-fbc2e4708463 Denmark (DK) e2db9e39-108b-408e-8012-427eb24260d6 Germany (DE) 7f31893f-1c43-4c83-ac6e-7eaf2f302bc0 Croatia (HR) b25a6819-161b-437b-86d0-3a810a0bf6eb Czech Republic (CZ) 6f0de107-6c8e-40e8-9ae7-2e6b31050fbe Netherlands (NL) 8a56db9b-06ae-49ad-86d5-90505b400768 France (FR) ccb3f727-1d52-4e59-b8bc-31ce6d2020ae Sweden (SE) ac17958f-7474-4c63-8477-7c0aa63eaf38 Germany (DE) 86c9d61c-adcf-4e9d-bf83-3823fb1f79d4 Germany (DE) 6a7802f3-2cc5-4734-a714-cda6e80b692e Netherlands (NL) 73a11258-c80d-4439-ac10-7ff065d2f0d1 Spain (ES) 31622732-cbc3-4f89-aa69-1a71dd936b0a Netherlands (NL) cd86e4f0-784b-4f10-80b3-3648eb7dcd8a Poland (PL) aa099d69-662c-40b5-9eca-e20ca28f62b2 Poland (PL) 127662e9-0342-459b-9ee2-630c6b565474 Finland (FI) |
| Ordering | |
| Order Code US and Canada: | XT1CE3063AFF000XXX |
| E-Number (Finland): | 3638776 |
| EAN: | 8015644012199 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 76.2 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.1 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.135 kg |
| Package Level 1 EAN: | 8015644012199 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0008 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 3 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 4.3 W |
| Rated Current (In): | 63 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 630 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 44.1…63 A |
| Short-Circuit Performance Level: | C |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |