ABB XT1N 160 TMD 32-450 4p F F

General Information

Extended Product Type: XT1N 160 TMD 32-450 4p F F
Product ID: 1SDA067419R1
EAN: 8015644013134
Catalog Description: XT1N 160 TMD 32-450 4p F F
Long Description: C.BREAKER TMAX XT1N 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32-450 A

Description

ABB EcoSolutions
ABB EcoSolutions: Yes
Circular Value
Circular Design Principles Recyclability Rate: Design for Closing Resource Loops – Standard EN45555 – 55.9 %
End of Life Instructions: 9AKK108468A2347
Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
Eco Transparency
Environmental Product Declaration – EPD: 9AKK108468A1890
9AKK108468A7793
Environmental
Environmental Information: 9AKK108467A6707
Material Compliance
REACH Declaration: 9AKK108466A1425
RoHS Information: 9AKK108466A1424
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
Toxic Substances Control Act – TSCA: 9AKK108467A8326
SCIP: f9bd9468-5125-4431-8584-a57b00bea951 Italy (IT)
Simplified SCIP: a6cdfadd-e966-4693-b691-e54ccb40925a Belgium (BE)
a90c82eb-b939-4187-9eb5-541db46c0370 France (FR)
b6e43b65-ba0d-4289-8c2f-fec23cb26b73 Spain (ES)
e89f486c-28e2-4e40-bd40-34ee27366375 Germany (DE)
8fa8b81b-84ed-4353-a426-5d89492bd813 Czech Republic (CZ)
325b21bf-6b47-47b3-876c-e43123a11e41 Germany (DE)
d2dd1ec9-bc62-4226-9658-2220ad1a4204 Croatia (HR)
0b06b3b9-00c8-4421-b742-67fc2c9bb176 Germany (DE)
94dac7fb-2160-4d83-9374-1a7a08924203 Sweden (SE)
62f1a221-6a1a-4f97-abe6-478502816b25 Hungary (HU)
ce10055e-1964-442f-b72a-c68b67c2495e Germany (DE)
0f806b46-eb93-46d8-9f3e-909ad906e508 Portugal (PT)
827ba498-b24a-4ade-a6d7-07aabe245409 Poland (PL)
23a869b6-9efb-4426-9fbd-0e9c66238e8b Poland (PL)
19c6c082-7a0f-43f7-b23f-76ec4a9f4e33 Bulgaria (BG)
998fabec-f3f1-423e-b293-941c68e3d327 France (FR)
e03713e9-d8fa-4413-bef5-f80de83f8837 Germany (DE)
9ce5449e-6dec-4eb9-be25-3d0ebd8ac527 Greece (GR)
d1ade6f7-8b28-4c13-b4f0-3911ee7648e8 Denmark (DK)
0db44ebf-bb02-44a7-a0ed-84a75cd1f43b Estonia (EE)
747672de-9ea5-4e0c-83bf-d44dc599a20d Belgium (BE)
1b40320d-ce6a-4bb7-bc0a-95aa81fae957 Hungary (HU)
f22229db-3fe4-46e9-b7fc-51079f8a6102 Poland (PL)
c01722b9-e994-42b1-a489-df33c5b0dbf2 Finland (FI)
3f871474-4709-46ac-a549-0741e68ce02d Netherlands (NL)
89f15a33-e498-4a1b-ba2a-67b747aa7a50 Norway (NO)
88a860a6-8abb-43a2-8500-84ad904739da Sweden (SE)
Ordering
Order Code US and Canada: XT1NE4032AFF000XXX
E-Number (Finland): 3640539
EAN: 8015644013134
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 101.6 mm
Product Net Height: 130 mm
Product Net Depth / Length: 70 mm
Product Net Weight: 1.4 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Depth / Length: 143 mm
Package Level 1 Gross Weight: 1.446 kg
Package Level 1 EAN: 8015644013134
Additional Information
Circuit Breaker Type to be Associated: Power Distribution
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: Automatic Circuit Breaker
Version: F
CAD Dimensional Drawing: 1SDH001295R0080
Technical
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: 240 cycles per hour
25000 cycle
Number of Poles: 4
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Order Multiple: 1 piece
Power Loss: at Rated Operating Conditions per Pole 2.1 W
Rated Current (In): 32 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 450 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 50 kA
(230 V AC) 50 kA
(240 V AC) 50 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 18 kA
(500 V AC) 15 kA
(525 V AC) 11 kA
(690 V AC) 5 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 65 kA
(230 V AC) 65 kA
(240 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(525 V AC) 22 kA
(690 V AC) 6 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 22.4…32 A
Short-Circuit Performance Level: N
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m
Certificates and Declarations
ATEX Certificate: No certification needed
Data Sheet, Technical Information: 1SDC210100D0206
1SDC210099D0206
Declaration of Conformity – CE: 9AKK106713A5532
GL Certificate: 1SDL000163R0103
LR Certificate: 1SDL000163R0100
UL Certificate: No certification needed
VDE Certificate: No certification needed
Dimension Diagram: 1SDH000719R0100
Mechanical Drawings: 1SDH000719R0100
Wiring Diagram: 1SDM000068R0001
Instructions and Manuals: 1SDH000719R0001
Classifications
ETIM 8: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
UNSPSC: 39120000
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
eClass: V11.1 : 27370409

Downloads

Datasheet