Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | bb45f1da-8cc1-46d6-83b6-a1b3baf6ac67 Italy (IT) |
| Simplified SCIP: | 06a16227-9a23-4383-a0e5-7b7175dca117 Belgium (BE) e56b0d92-46c4-4721-970f-3af3b889864e Spain (ES) 0fc7925a-dcc0-4543-9d65-15d0e9522adb France (FR) 6d3efead-2c74-4337-8835-080e289b47a4 Germany (DE) d23204a9-469f-4a2e-a9c1-81106c28d8cd Czech Republic (CZ) dd717899-506f-4f7c-8d96-b08a31f29bda Croatia (HR) 95ca9790-495b-479b-8d24-2348be24b5cc Germany (DE) fefd45ff-5354-4cb5-9ee8-8fd8e9e845e6 Denmark (DK) a8c86710-5d69-43e7-953c-796232bdbcd1 Germany (DE) 624a7f18-ebf7-436d-88ca-75a07a63c7ab Sweden (SE) 586a90a7-18f8-455d-98a8-f4e432b26fe3 Poland (PL) 8e60a9c0-db05-4620-8a18-6ab9d9a3be1e Estonia (EE) 3c533264-addc-44ac-8251-fb304cb503b6 Greece (GR) 95a52950-6026-4eaf-a420-63e651313792 Belgium (BE) f9c309e9-d281-4301-879a-417a66bdbd5c Germany (DE) 1ac3a81d-e4cc-451d-946f-5bce449aa7cf France (FR) 2612acbc-c08b-4c40-9ed5-59287e2be748 Poland (PL) fe69ad38-e8e0-47bc-a9b7-3c53b49672ae Hungary (HU) 82760656-0550-4b3a-84bc-25a3f98b5c9e Portugal (PT) bbd1646d-d373-4851-bb91-b2ff51bf9de0 Germany (DE) b0598f26-f85c-4e4d-97cf-1274950ae30b Sweden (SE) cf070818-0ede-42d5-b70a-9bb9b0e27a41 Netherlands (NL) 5d2d773d-1c51-4406-8052-2af850322ac6 Norway (NO) baba48c7-474d-4919-9638-cff3a8cb00cc Hungary (HU) 7268b0d5-b5bf-4500-b2ef-13fc5aea72b8 Finland (FI) 8a4bcb19-74bc-4cb1-bd90-b1a712ead71c Bulgaria (BG) 843937e6-dbd9-4007-acff-baf15d2b4c44 Poland (PL) |
| Ordering | |
| Order Code US and Canada: | XT1NE4040AFF000XXX |
| E-Number (Finland): | 3640540 |
| EAN: | 8015644013141 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 101.6 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.4 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.43 kg |
| Package Level 1 EAN: | 8015644013141 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0080 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 4 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 2.6 W |
| Rated Current (In): | 40 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 450 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 28…40 A |
| Short-Circuit Performance Level: | N |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |