Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
EcoSolutions Profile: | 9AKK108469A3794 |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 52.5 % |
Group Waste to Landfill Target: | No non-hazardous waste is sent to a landfill |
Sustainable Material Content in Packaging: | Recycled Paper – 78 % |
Offered with Extended Lifetime: | Product Durability |
End of Life Instructions: | 9AKK108468A4361 |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108467A3700 |
Technical | |
Standards: | IEC/EN 61008 UL 1053 |
Type of Residual Current: | Type AC |
Rated Voltage (Ur): | 230 V |
Rated Operational Voltage: | 230 V |
Rated Insulation Voltage (Ui): | 500 V |
Rated Impulse Withstand Voltage (Uimp): | 4 kV |
Rated Current (In): | 25 A |
Rated Residual Current: | 300 mA |
Rated Conditional Short-Circuit Current (Inc): | 10 kA |
Rated Service Short-Circuit Breaking Capacity (Ics): | 1 kA |
Maximum Surge Current: | 0.25 kA |
Leakage Current Type: | AC |
Rated Frequency (f): | 50 €¦ 60 Hz |
Power Loss: | at Rated Operating Conditions per Pole 1 W |
Power Supply Connection: | Arbitrary |
Electrical Endurance: | 10000 cycle |
Number of Poles: | 2 |
Operating Characteristic: | Instantaneous |
Mounting Type: | DIN-Rail |
Options Provided: | None |
Accessories Available: | Yes |
Connecting Capacity: | Busbar 10 mm² Rigid 25 … 25 mm² Flexible 25 … 25 mm² |
Rated Cross-Section: | 4 – Multi-Wired 0…25 mm² 1 – Solid-Core 25…25 mm² |
Material Compliance | |
RoHS Information: | 9AKK106713A5602 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
RoHS Date: | 20211115 |
REACH Declaration: | 9AKK108467A9482 |
REACH Information: | True – contains substances > 0.1 mass percentage |
REACH Date: | 20240429 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108468A3363 |
Environmental | |
Ambient Temperature: | -25…55 °C |
Ambient Air Temperature: | Operation -25…55 °C |
Degree of Protection: | IP2X |
Pollution Degree: | 2 |
Resistance to Vibrations: | 20 Cycles with Load 0.8 In: 1g or 1mm 50 €¦ 150 €¦ 5 Hz |
Resistance to Shock acc. to IEC 60068-2-27: | 25g 2 shocks 13 ms |
Environmental Information: | Refer to RoHS |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA: | 277 V AC |
Short-Circuit Current Rating (SCCR): | 300 mA |
Dimensions | |
Width in Number of Modular Spacings: | 2 |
Product Net Width: | 0.035 m |
Product Net Height: | 0.085 m |
Product Net Depth / Length: | 0.069 m |
Product Net Weight: | 0.200 kg |
Built-In Depth (t2): | 69 mm |
Dimension Diagram: | 9AKK106354A0758 |
Ordering | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Gross Weight: | 0.235 kg |
Certificates and Declarations | |
Declaration of Conformity – CE: | 9AKK106713A5602 |
Installation | |
Instructions and Manuals: | 9AKK107991A6127 |
Popular Downloads | |
Data Sheet, Technical Information: | 9AKK107991A8329 |
Classifications | |
ETIM 8: | EC000003 – Residual current circuit breaker (RCCB) |
ETIM 9: | EC000003 – Residual current circuit breaker (RCCB) |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
WEEE B2C / B2B: | Business To Consumer |
CN8: | 85363030 |
UNSPSC: | 39121601 |
eClass: | V11.0 : 27142201 |
IDEA Granular Category Code (IGCC): | 4875 >> Residual current circuit breaker (RCCB) |
Object Classification Code: | F |