ABB F202 AC-25/0.3 Residual Current Circuit Breaker 2P Type AC 300 mA

General Information

Extended Product Type: F202 AC-25/0.3
Product ID: 2CSF202001R3250
EAN: 8012542780601
Catalog Description: F202 AC-25/0.3 Residual Current Circuit Breaker 2P Type AC 300 mA
Long Description: The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications.

Description

ABB EcoSolutions
ABB EcoSolutions: Yes
EcoSolutions Profile: 9AKK108469A3794
Circular Value
Circular Design Principles Recyclability Rate: Design for Closing Resource Loops – Standard EN45555 – 52.5 %
Group Waste to Landfill Target: No non-hazardous waste is sent to a landfill
Sustainable Material Content in Packaging: Recycled Paper – 78 %
Offered with Extended Lifetime: Product Durability
End of Life Instructions: 9AKK108468A4361
Eco Transparency
Environmental Product Declaration – EPD: 9AKK108467A3700
Technical
Standards: IEC/EN 61008
UL 1053
Type of Residual Current: Type AC
Rated Voltage (Ur): 230 V
Rated Operational Voltage: 230 V
Rated Insulation Voltage (Ui): 500 V
Rated Impulse Withstand Voltage (Uimp): 4 kV
Rated Current (In): 25 A
Rated Residual Current: 300 mA
Rated Conditional Short-Circuit Current (Inc): 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics): 1 kA
Maximum Surge Current: 0.25 kA
Leakage Current Type: AC
Rated Frequency (f): 50 €¦ 60 Hz
Power Loss: at Rated Operating Conditions per Pole 1 W
Power Supply Connection: Arbitrary
Electrical Endurance: 10000 cycle
Number of Poles: 2
Operating Characteristic: Instantaneous
Mounting Type: DIN-Rail
Options Provided: None
Accessories Available: Yes
Connecting Capacity: Busbar 10 mm²
Rigid 25 … 25 mm²
Flexible 25 … 25 mm²
Rated Cross-Section: 4 – Multi-Wired 0…25 mm²
1 – Solid-Core 25…25 mm²
Material Compliance
RoHS Information: 9AKK106713A5602
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Date: 20211115
REACH Declaration: 9AKK108467A9482
REACH Information: True – contains substances > 0.1 mass percentage
REACH Date: 20240429
Conflict Minerals Reporting Template (CMRT): 9AKK108468A3363
Environmental
Ambient Temperature: -25…55 °C
Ambient Air Temperature: Operation -25…55 °C
Degree of Protection: IP2X
Pollution Degree: 2
Resistance to Vibrations: 20 Cycles with Load 0.8 In: 1g or 1mm 50 €¦ 150 €¦ 5 Hz
Resistance to Shock acc. to IEC 60068-2-27: 25g 2 shocks 13 ms
Environmental Information: Refer to RoHS
Technical UL/CSA
Maximum Operating Voltage UL/CSA: 277 V AC
Short-Circuit Current Rating (SCCR): 300 mA
Dimensions
Width in Number of Modular Spacings: 2
Product Net Width: 0.035 m
Product Net Height: 0.085 m
Product Net Depth / Length: 0.069 m
Product Net Weight: 0.200 kg
Built-In Depth (t2): 69 mm
Dimension Diagram: 9AKK106354A0758
Ordering
Package Level 1 Units: box 1 piece
Package Level 1 Gross Weight: 0.235 kg
Certificates and Declarations
Declaration of Conformity – CE: 9AKK106713A5602
Installation
Instructions and Manuals: 9AKK107991A6127
Popular Downloads
Data Sheet, Technical Information: 9AKK107991A8329
Classifications
ETIM 8: EC000003 – Residual current circuit breaker (RCCB)
ETIM 9: EC000003 – Residual current circuit breaker (RCCB)
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B: Business To Consumer
CN8: 85363030
UNSPSC: 39121601
eClass: V11.0 : 27142201
IDEA Granular Category Code (IGCC): 4875 >> Residual current circuit breaker (RCCB)
Object Classification Code: F

Downloads

Certificate Datasheet