Description
| Technical | |
| Standards: | IEC/EN 61008 |
| Type of Residual Current: | Type AC |
| Rated Voltage (Ur): | 230/400 V |
| Rated Operational Voltage: | 230 / 400 V AC |
| Rated Insulation Voltage (Ui): | 500 V |
| Rated Impulse Withstand Voltage (Uimp): | 4 kV |
| Rated Current (In): | 125 A |
| Rated Residual Current: | 100 mA |
| Rated Conditional Short-Circuit Current (Inc): | 10 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics): | 1 kA |
| Maximum Surge Current: | 0.25 kA |
| Leakage Current Type: | AC |
| Rated Frequency (f): | 50 Hz |
| Power Loss: | at Rated Operating Conditions per Pole 7.5 W |
| Power Supply Connection: | Arbitrary |
| Electrical Endurance: | 10000 cycle |
| Number of Poles: | 4 |
| Operating Characteristic: | Instantaneous |
| Position of Neutral Terminals: | Right |
| Mounting Type: | DIN-Rail |
| Options Provided: | None |
| Accessories Available: | Yes |
| Connecting Capacity: | Busbar 10 mm² Rigid 35 … 35 mm² Flexible 35 … 35 mm² |
| Rated Cross-Section: | 4 – Multi-Wired 0…25 mm² 1 – Solid-Core 35…35 mm² |
| Material Compliance | |
| RoHS Information: | 9AKK106713A5606 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date: | 20211115 |
| REACH Declaration: | 9AKK108467A9482 |
| REACH Information: | True – contains substances > 0.1 mass percentage |
| REACH Date: | 20240429 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108468A3363 |
| SCIP: | 941b7388-e5f6-48ed-bf9e-6d5653c1c989 Italy (IT) |
| Environmental | |
| Ambient Temperature: | -25…40 °C |
| Ambient Air Temperature: | Operation -25…40 °C |
| Degree of Protection: | IP2X |
| Pollution Degree: | 2 |
| Environmental Information: | Refer to RoHS |
| Technical UL/CSA | |
| Short-Circuit Current Rating (SCCR): | 100 mA |
| Dimensions | |
| Width in Number of Modular Spacings: | 4 |
| Product Net Width: | 0.072 m |
| Product Net Height: | 0.085 m |
| Product Net Depth / Length: | 0.069 m |
| Product Net Weight: | 0.500 kg |
| Built-In Depth (t2): | 69 mm |
| Ordering | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Gross Weight: | 0.545 kg |
| Certificates and Declarations | |
| Declaration of Conformity – CE: | 9AKK106713A5606 |
| Installation | |
| Instructions and Manuals: | 9AKK107991A6132 |
| Popular Downloads | |
| Data Sheet, Technical Information: | 9AKK107991A8329 |
| Classifications | |
| ETIM 8: | EC000003 – Residual current circuit breaker (RCCB) |
| ETIM 9: | EC000003 – Residual current circuit breaker (RCCB) |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B: | Business To Consumer |
| CN8: | 85363030 |
| eClass: | V11.0 : 27142201 |
| Object Classification Code: | F |