Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | 87da4ae5-d281-4cf7-89ae-08ea1f34c520 Italy (IT) |
| Simplified SCIP: | e1a75a7e-0f06-4343-b305-b0bb07d627d7 Germany (DE) 9136ee1a-0225-4485-8008-9b9b4f898003 France (FR) baa691e3-fb96-4aa9-9079-885f0ce9ffc7 Netherlands (NL) 19009d20-fe0a-406e-a6c7-754e2ce79a04 Spain (ES) 0d017bbc-bd89-4cba-9c40-ce382b69c941 Netherlands (NL) 1ac23e01-8938-4cfa-9554-5dc725569cd9 Estonia (EE) 3caf7a98-6d33-4e3d-9e3c-3696071c018c Greece (GR) b4a8fa85-471c-4024-9dfa-2b3b8002b1fd Portugal (PT) 40ae467e-12cd-4ff4-9b7b-0b06c10682c8 Bulgaria (BG) 34e0ba7e-9ada-4036-a46c-78818d351a10 Sweden (SE) 7688f27b-0303-4931-a1b9-201ec758eed9 Poland (PL) 2973e92d-a825-4905-b178-8271043cd3fc Netherlands (NL) 88dd4d2a-48ef-40e5-a5a4-8777e0caf1ae Poland (PL) 28af0011-3352-4568-ae2e-5c6f712f69ce Norway (NO) 139a4e60-c144-4385-9f47-109d95a5e80f Finland (FI) fdaa062c-f086-4a1a-84ad-e07827068768 Netherlands (NL) b45b713c-aac6-486d-860d-62c7bd566c76 Germany (DE) 7cd9e27b-8379-4d1d-9c10-2494ae68a5e5 Denmark (DK) b5672789-5124-44cd-b9aa-10e3f35aba7a Germany (DE) 4b159a82-b08b-4bd6-9325-11ce5cdf5448 Croatia (HR) dde32885-1587-472c-b2dd-1326e5aad4e2 Czech Republic (CZ) f4f530b5-c734-46f4-9e51-1699fa3f6f95 Poland (PL) 7684609b-1286-40fa-be35-8e161c571a09 Netherlands (NL) 53567a62-c858-4312-a586-9c3dff2aeb2a France (FR) 97a62aeb-f463-485d-802c-da5b271e1915 Sweden (SE) 706a0ec2-b9e6-48d8-a2e7-e213302d4bc2 Germany (DE) 6f865dc7-914e-4ee1-bd3b-f9f2de603622 Germany (DE) |
| Ordering | |
| Order Code US and Canada: | XT1BE3100AFF000XXX |
| E-Number (Finland): | 3640495 |
| EAN: | 8015644694487 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 76.2 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.1 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.134 kg |
| Package Level 1 EAN: | 8015644694487 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0008 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 3 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 7 W |
| Rated Current (In): | 100 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 1000 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.25 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 70…100 A |
| Short-Circuit Performance Level: | B |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |