Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | 8acd1baa-b059-4d51-abdc-ea46defeb35e Italy (IT) |
| Simplified SCIP: | d1aaf08d-e25f-4668-a057-4628057c8769 Germany (DE) a3cb6bff-8410-4229-8646-6cccfa9434c2 Poland (PL) 9ff0f6b4-a69c-43a0-ba19-92bc124a3464 Norway (NO) 2b859db5-b8d7-4582-9f9e-a714dfb57603 Finland (FI) 2c089ba4-fd3a-4e3d-b3da-8607a803d823 Netherlands (NL) d265c6de-5560-448d-be55-8b6e38c8e47e Germany (DE) e0d795ac-e812-48bb-93ae-39c2b1fe2aa8 Denmark (DK) b9b12f17-54ef-40cc-8b89-a4e1a85e6f16 Germany (DE) c6298b97-9d9e-42ed-b595-bc5572008f7f Croatia (HR) 49905c59-d051-4933-aee8-957313e7c76b France (FR) 49a55cdf-4a0f-48db-a710-1f0b682d75da Sweden (SE) ba601371-442d-4856-91e4-aed91c4397a6 Germany (DE) 96e8b14b-e8c2-4ff3-b457-9d321b80a48c Germany (DE) f834e079-b952-4094-819d-77fa6c5c2e9f France (FR) ef2515cc-3f80-4037-9726-465563cd6237 Netherlands (NL) 755304cd-f665-4b13-9cf6-10f93e474874 Spain (ES) efe35e1a-4e77-4211-bebc-18b4ca05a992 Estonia (EE) c6675afb-be78-4a8f-9a37-e2fbbce32849 Greece (GR) f105555f-afc7-4bfc-8428-6db856df2c98 Portugal (PT) 243cc790-2e64-4328-97df-dd54d53fbcd3 Bulgaria (BG) f8571fb3-a76a-45f5-b32b-a8fb8bc01539 Sweden (SE) 0f189183-bc01-4cac-acea-7637fb6a169a Poland (PL) dbf95c07-c982-4c67-8a65-b5087833b881 Netherlands (NL) f099941a-3638-4e46-bc58-30dd8b7335ab Czech Republic (CZ) 29ca709b-7996-405d-bd6d-5d766c178307 Poland (PL) 8a2dc3a6-691e-442a-b562-b5f3081e360d Netherlands (NL) ed75ce49-731b-4a2c-a2aa-48b67198a8ec Netherlands (NL) |
| Ordering | |
| Order Code US and Canada: | XT1BE3025AFF000XXX |
| E-Number (Finland): | 3640497 |
| EAN: | 8015644003289 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 76.2 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.1 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.126 kg |
| Package Level 1 EAN: | 8015644003289 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0008 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 3 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 2 W |
| Rated Current (In): | 25 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 450 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.25 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 17.5…25 A |
| Short-Circuit Performance Level: | B |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |