ABB XT1B 160 TMD 63-630 4p F F

General Information

Extended Product Type: XT1B 160 TMD 63-630 4p F F
Product ID: 1SDA066816R1
EAN: 8015644007232
Catalog Description: XT1B 160 TMD 63-630 4p F F
Long Description: C.BREAKER TMAX XT1B 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 63-630 A

Description

ABB EcoSolutions
ABB EcoSolutions: Yes
Circular Value
Circular Design Principles Recyclability Rate: Design for Closing Resource Loops – Standard EN45555 – 55.9 %
End of Life Instructions: 9AKK108468A2347
Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
Eco Transparency
Environmental Product Declaration – EPD: 9AKK108468A1890
9AKK108468A7793
Environmental
Environmental Information: 9AKK108467A6707
Material Compliance
REACH Declaration: 9AKK108466A1425
RoHS Information: 9AKK108466A1424
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
Toxic Substances Control Act – TSCA: 9AKK108467A8326
SCIP: 7e73f8c2-9fcf-46fd-8ce8-8ff3065446c7 Italy (IT)
Simplified SCIP: 44cb4be4-a1b4-471c-80e4-5307577945cb Germany (DE)
2b4cd088-0d46-4c30-bb6a-fb441b7fb7fb Poland (PL)
b7062f07-5e00-42af-9950-e858adf3f3bd Norway (NO)
3f87f6c9-8b2b-4ba3-84e7-e4bf7c4dbc7c Finland (FI)
b0f1fc93-a34d-458d-8e5e-7e6c7fda2025 Netherlands (NL)
0994645c-6924-49ce-aa7d-e31f5e03f896 Germany (DE)
11a258b4-39ac-46b4-8a4c-aeed35ebf9da Denmark (DK)
7998dd24-22f6-40bf-90a9-f95105e027b1 Germany (DE)
1380dbaa-9f5b-4c5a-a7f2-568dc4c78999 Croatia (HR)
5ffe1b0a-3c9a-42c4-861e-3d907b4f9fa3 Czech Republic (CZ)
6abaabeb-16c8-4cb6-aef2-7390cbe2b1da Poland (PL)
32be922d-f98f-47fe-9186-edcf13f4f64b Netherlands (NL)
54b32461-e46b-4996-bcf2-3f2b76dbdd71 Netherlands (NL)
43eb203d-6065-412f-b732-744eae5e5eb0 Estonia (EE)
c4908d83-b7ef-4b8d-8997-e74109d80de6 Greece (GR)
320d11f0-a17d-4e87-a794-375d391e75f4 Portugal (PT)
e6eb8d27-f481-4de3-a533-d3fe70af7f6a Bulgaria (BG)
34915fc1-7263-488f-b83f-da09bdd995be Sweden (SE)
a540bb0a-5c6d-479d-8984-36b5f089d8a7 Poland (PL)
c3e3417c-d555-4879-9f50-f327aba9cc45 France (FR)
cf23ebf3-cbe3-4128-a848-761e96a2adb6 Sweden (SE)
89e58f18-2822-40de-b715-47eeb3764a40 Germany (DE)
4f114a61-8884-4a65-a44a-0c453d2e1ada Germany (DE)
8e0863a3-ad22-4ce7-983c-ea3d4580aac7 France (FR)
61686ad8-6b0e-43f3-b96a-9777eabf3f98 Netherlands (NL)
1f1f32e9-0f0b-4294-84ff-23fee2cdc5ab Spain (ES)
72846ad8-efea-488f-9610-a0ce79670d85 Netherlands (NL)
Ordering
Order Code US and Canada: XT1BE4063AFF000XXX
E-Number (Finland): 3638196
EAN: 8015644007232
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 101.6 mm
Product Net Height: 130 mm
Product Net Depth / Length: 70 mm
Product Net Weight: 1.4 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Depth / Length: 143 mm
Package Level 1 Gross Weight: 1.43 kg
Package Level 1 EAN: 8015644007232
Additional Information
Circuit Breaker Type to be Associated: Power Distribution
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: Automatic Circuit Breaker
Version: F
CAD Dimensional Drawing: 1SDH001295R0080
Technical
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: 240 cycles per hour
25000 cycle
Number of Poles: 4
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Order Multiple: 1 piece
Power Loss: at Rated Operating Conditions per Pole 4.3 W
Rated Current (In): 63 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 630 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 25 kA
(230 V AC) 25 kA
(240 V AC) 25 kA
(380 V AC) 18 kA
(415 V AC) 18 kA
(440 V AC) 11.25 kA
(500 V AC) 8 kA
(525 V AC) 6 kA
(690 V AC) 3 kA
(250 V DC) 2 Poles in Series 18 kA
(500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 25 kA
(230 V AC) 25 kA
(240 V AC) 25 kA
(380 V AC) 18 kA
(415 V AC) 18 kA
(440 V AC) 15 kA
(500 V AC) 8 kA
(525 V AC) 6 kA
(690 V AC) 3 kA
(250 V DC) 2 Poles in Series 18 kA
(500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 44.1…63 A
Short-Circuit Performance Level: B
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m
Certificates and Declarations
ATEX Certificate: No certification needed
Data Sheet, Technical Information: 1SDC210100D0206
1SDC210099D0206
Declaration of Conformity – CE: 9AKK106713A5532
GL Certificate: 1SDL000163R0103
LR Certificate: 1SDL000163R0100
UL Certificate: No certification needed
VDE Certificate: No certification needed
Dimension Diagram: 1SDH000719R0100
Mechanical Drawings: 1SDH000719R0100
Wiring Diagram: 1SDM000068R0001
Instructions and Manuals: 1SDH000719R0001
Classifications
ETIM 8: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
UNSPSC: 39120000
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
eClass: V11.1 : 27370409

Downloads

Datasheet