Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | 6963f79e-5b3e-491f-8111-ed51582b95f5 Italy (IT) |
| Simplified SCIP: | 03623cf1-c0d9-4f9d-a987-0129b1b5c4e3 Germany (DE) 0b897293-8966-400d-85d3-3adb67e5645e Netherlands (NL) 788f7ce1-ce81-46b1-b516-e8a1a5810a29 Netherlands (NL) aa1def39-a5e1-402c-a7fb-1f69c65bf0cf Germany (DE) 75a37be3-c5f2-48d2-921c-196f3e715fbb Denmark (DK) 2b729765-22b2-414d-96db-c45c85b86b34 Germany (DE) 73e3b539-3241-4e7c-b2e3-a271a8580cce Croatia (HR) f266fe7c-cd54-450c-984b-762ab9f9b7b5 Czech Republic (CZ) 01bac839-3a95-4abc-9842-01bf939126de Netherlands (NL) 6d189084-7c30-4847-b66c-12452df5457e Netherlands (NL) afbc9104-3742-44d7-8a17-ef24c66adf7e Estonia (EE) fa14a73d-5be7-45d6-bea7-eef52df9a461 Greece (GR) c090809c-f591-4fd0-8f91-3f7005422d41 Portugal (PT) 8c6a9e39-4f7d-4d91-a84a-7c5fae9fab39 Bulgaria (BG) a751af1f-ba16-4b16-bae1-88bd49a124fd Sweden (SE) 189d8f20-fd0b-4ae9-9160-02cedac39911 Poland (PL) dfa00889-9143-4640-beda-7b68e77263b4 France (FR) e2a75877-0b3c-423d-a60d-9205fd4b7277 Sweden (SE) 2ba6904a-b275-40a0-a662-5277d2f0e712 Germany (DE) dbbe5839-4af6-41b6-a0d9-d91eb8454cb5 Germany (DE) b8b8214a-1d31-430b-aa6b-829d2c2e0845 Spain (ES) 30e0bf90-1472-4e80-9b14-b35167a34379 Netherlands (NL) 3fc61ee0-7133-460e-943f-e79dba217b6d Poland (PL) 5e5400ef-76f0-49e1-9aff-19542ffb47e1 Poland (PL) 1bc8a6dc-76f2-4cd5-8b92-6cd0b382a8e5 Finland (FI) 46710f5a-a1b8-4e6f-92eb-28c07b84c61b Norway (NO) ecb4dd9f-7134-4b06-9ce6-ba53c0aceabe France (FR) |
| Ordering | |
| Order Code US and Canada: | XT1CE3050AFF000XXX |
| E-Number (Finland): | 3638609 |
| EAN: | 8015644695194 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 76.2 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.1 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.12 kg |
| Package Level 1 EAN: | 8015644695194 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0008 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 3 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 3.7 W |
| Rated Current (In): | 50 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 500 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 35…50 A |
| Short-Circuit Performance Level: | C |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |