Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | f9bd9468-5125-4431-8584-a57b00bea951 Italy (IT) |
| Simplified SCIP: | a6cdfadd-e966-4693-b691-e54ccb40925a Belgium (BE) a90c82eb-b939-4187-9eb5-541db46c0370 France (FR) b6e43b65-ba0d-4289-8c2f-fec23cb26b73 Spain (ES) e89f486c-28e2-4e40-bd40-34ee27366375 Germany (DE) 8fa8b81b-84ed-4353-a426-5d89492bd813 Czech Republic (CZ) 325b21bf-6b47-47b3-876c-e43123a11e41 Germany (DE) d2dd1ec9-bc62-4226-9658-2220ad1a4204 Croatia (HR) 0b06b3b9-00c8-4421-b742-67fc2c9bb176 Germany (DE) 94dac7fb-2160-4d83-9374-1a7a08924203 Sweden (SE) 62f1a221-6a1a-4f97-abe6-478502816b25 Hungary (HU) ce10055e-1964-442f-b72a-c68b67c2495e Germany (DE) 0f806b46-eb93-46d8-9f3e-909ad906e508 Portugal (PT) 827ba498-b24a-4ade-a6d7-07aabe245409 Poland (PL) 23a869b6-9efb-4426-9fbd-0e9c66238e8b Poland (PL) 19c6c082-7a0f-43f7-b23f-76ec4a9f4e33 Bulgaria (BG) 998fabec-f3f1-423e-b293-941c68e3d327 France (FR) e03713e9-d8fa-4413-bef5-f80de83f8837 Germany (DE) 9ce5449e-6dec-4eb9-be25-3d0ebd8ac527 Greece (GR) d1ade6f7-8b28-4c13-b4f0-3911ee7648e8 Denmark (DK) 0db44ebf-bb02-44a7-a0ed-84a75cd1f43b Estonia (EE) 747672de-9ea5-4e0c-83bf-d44dc599a20d Belgium (BE) 1b40320d-ce6a-4bb7-bc0a-95aa81fae957 Hungary (HU) f22229db-3fe4-46e9-b7fc-51079f8a6102 Poland (PL) c01722b9-e994-42b1-a489-df33c5b0dbf2 Finland (FI) 3f871474-4709-46ac-a549-0741e68ce02d Netherlands (NL) 89f15a33-e498-4a1b-ba2a-67b747aa7a50 Norway (NO) 88a860a6-8abb-43a2-8500-84ad904739da Sweden (SE) |
| Ordering | |
| Order Code US and Canada: | XT1NE4032AFF000XXX |
| E-Number (Finland): | 3640539 |
| EAN: | 8015644013134 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 101.6 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.4 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.446 kg |
| Package Level 1 EAN: | 8015644013134 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0080 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 4 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 2.1 W |
| Rated Current (In): | 32 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 450 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 22.4…32 A |
| Short-Circuit Performance Level: | N |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |