Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | 848fe73d-3ecc-4485-bbef-f2dec965f3a5 Italy (IT) |
| Simplified SCIP: | 420b6837-de7d-4bd1-9b36-33bb9784cf52 Belgium (BE) dd86a351-c853-4974-861b-1cfac369457b Spain (ES) 154d20fb-5c46-44dd-8ac8-a0b427001ce2 France (FR) c6104aa2-5e11-448e-8dc7-0625a9587a81 Denmark (DK) 4dce0847-a9d7-4ef5-be92-d25bf5bd5abb Sweden (SE) 1a1116b9-2f0d-47c7-bc03-e330b4f6ed05 Germany (DE) d4851bc2-3e98-4339-832b-5aaec40f4f87 Croatia (HR) c03712dc-bed8-4751-8170-8c71892a13f0 Germany (DE) 265df65c-9459-4bb0-b3c8-d109ae59a186 Czech Republic (CZ) b624c864-c9b6-4e70-97aa-6eeb5070a281 Germany (DE) ef479331-30d5-437b-a278-5cbc9b945a9d Germany (DE) 9fef5a66-1712-4946-9e76-ac21b568edfd Hungary (HU) bc71b1e7-e458-460d-98f3-a122bb230cd9 Portugal (PT) d9a7f657-2b46-4804-a7da-99ff774bea68 Poland (PL) 44639bb5-7fcf-422b-8e2b-5e7deeb5af01 Bulgaria (BG) 21411aac-cb8a-4a0d-95c2-979a92878952 Poland (PL) c731cdd8-14e9-44b4-900b-490e2fce8db6 Germany (DE) 2a8f7c1c-a8d7-4fc6-b20c-7f82aec243a3 Estonia (EE) 35bc22fd-33d7-4641-8228-947203a00961 Belgium (BE) d801a270-4410-4546-9cad-0c679bd4d03e Greece (GR) 87b6d777-b996-470b-a703-53e5010a590d France (FR) f5bd22de-f07b-42cd-9052-3f5d890a532a Poland (PL) b7794e80-d1c0-4840-940f-6f4fc3aad3e6 Hungary (HU) 4f0c67dd-f132-4c60-8c54-26c21ed62a24 Finland (FI) d78ad1ad-48e4-4a0e-ae8a-d02fea224f6a Sweden (SE) 515bff57-ce73-49ee-88a2-b45fb6668cc9 Norway (NO) aa7c55c8-ee4d-468d-9403-20b0fc1474ad Netherlands (NL) |
| Ordering | |
| Order Code US and Canada: | XT1NE3040AFF000XXX |
| E-Number (Finland): | 3640523 |
| EAN: | 8015644013066 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 76.2 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1.1 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.137 kg |
| Package Level 1 EAN: | 8015644013066 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0008 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 3 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 2.6 W |
| Rated Current (In): | 40 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 450 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMD |
| Release Type: | TM |
| Setting Range: | 28…40 A |
| Short-Circuit Performance Level: | N |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| GL Certificate: | 1SDL000163R0103 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000719R0100 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |