Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
| End of Life Instructions: | 9AKK108468A2347 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | bab57cb4-245d-44be-bf03-c5b43170495f Italy (IT) |
| Simplified SCIP: | 0ff67b66-9393-4f4b-8f5f-a17f64d2be5d Finland (FI) 33253106-5ca0-4526-9533-bdadea09e443 Hungary (HU) 498f8cb1-1144-4233-b2da-7f77194abdaa France (FR) bed42174-22d5-44c5-825f-930a509434d9 Spain (ES) c1e394ba-ae25-477b-b7eb-41d9bf76e9e1 Belgium (BE) e0dac05e-e1bd-4d4d-9b78-cd7f3819e5b2 Germany (DE) 3de44331-1772-443c-92d5-420b325fac62 Czech Republic (CZ) b93fbbdb-806b-4f85-ad2e-e80a1115ec1a Croatia (HR) 15fbfd28-b2e7-4b5d-a137-b6f169f1de24 Germany (DE) 4051a5d0-7a42-4fde-822b-ab36eacae1e5 Sweden (SE) f5024ea2-de39-45f6-aea7-22a156c7bcd4 Germany (DE) 7766981b-f293-417d-8b77-4664d575a931 Denmark (DK) 90530b91-c871-4067-8c24-b38668043f31 Germany (DE) 8b716e70-3566-446c-a452-4d7d4fa36d8b Hungary (HU) 5f241e40-ba8d-46ac-9bee-578c560ace2e Portugal (PT) b24c2a99-4952-4ac7-b469-2dc063c115f3 Poland (PL) 22cf4870-2a6b-418e-99b6-5478ece1d46d Bulgaria (BG) fa4c15fc-e5c5-49de-bc87-f0352eb68ef8 Poland (PL) ba3f723e-560c-46ec-a4d5-2528743cbf58 Germany (DE) 91044a1f-bf91-4a05-a740-a940a4d580a9 Greece (GR) fc389803-df5d-4fc1-899f-ec9386da37c6 France (FR) b73a9713-b996-43fe-8b64-b301598e1df4 Estonia (EE) 96aa8a9b-18fb-4323-abe1-c46b4a275506 Belgium (BE) 8a6089c7-f76b-47ab-a558-5b3e91f2160f Norway (NO) c4f93059-ee47-47ae-87ca-6196e662f86b Sweden (SE) ccd75dfb-28c8-4a3c-8c48-6b229ce02d1b Netherlands (NL) 3f24730a-504f-4421-ab70-11492729f4ec Poland (PL) |
| Ordering | |
| Order Code US and Canada: | XT1NE3016AFF000XXX |
| E-Number (Finland): | 3640531 |
| EAN: | 8015644873455 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 76.2 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 70 mm |
| Product Net Weight: | 1 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 128 mm |
| Package Level 1 Height: | 135 mm |
| Package Level 1 Depth / Length: | 143 mm |
| Package Level 1 Gross Weight: | 1.1 kg |
| Package Level 1 EAN: | 8015644873455 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001295R0008 |
| Technical | |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 3 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Rated Current (In): | 16 A |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 450 A |
| Rated Insulation Voltage (Ui): | 800 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Release: | TMF |
| Release Type: | TM |
| Setting Range: | 16 A |
| Short-Circuit Performance Level: | N |
| Standards: | IEC60947-2 |
| Sub-type: | XT1 |
| Terminal Connection Type: | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5532 |
| Mechanical Drawings: | 1SDH000719R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000719R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |