Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.70 % |
| End of Life Instructions: | 9AKK108468A2348 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108469A1856 9AKK108468A1891 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | 1356d4aa-8ac0-4c90-a0a6-7bd20dbf382e Italy (IT) |
| Simplified SCIP: | 5c697f83-ca81-4283-a9be-611d4112911a Germany (DE) 904e26e1-b4f8-446c-bcad-9aa8f98e42b9 Netherlands (NL) 1664f057-cbae-4159-8779-ec95f143db2a Spain (ES) 4fc7a468-c5ba-4bff-a584-8685ec52f288 Netherlands (NL) b44ff0ce-ec9f-428c-9384-adbfb0d3a081 Bulgaria (BG) 4b295e8e-2540-41ab-8e3b-baee28071515 Sweden (SE) 00fba872-10c1-45b1-9422-6fa193bcf6c2 Poland (PL) 424f2299-cff1-4f85-8472-b9b9d8454dcd France (FR) 3389ba5f-3328-46ab-b5a0-db2105f1e8e4 Croatia (HR) 1dc918cc-06e4-46de-9766-201bea1beb1b Czech Republic (CZ) ad59485a-8d3c-4d59-93ba-2c60c2a7a508 Poland (PL) 8b836f51-1f94-497d-a2de-1f6e8d352126 Sweden (SE) 761e6038-a9f8-492f-a604-350f95784e3e Germany (DE) 8ce021f5-d2fc-4312-bce1-35abcf47b93f Germany (DE) 19ca41ae-ae94-4c94-8b1c-3db95f936525 France (FR) fb53d5fa-faa9-4ad6-a19c-240b80f79df6 Poland (PL) 34d65c78-b470-4060-952a-7b62093cb521 Norway (NO) a93a0f59-3251-4210-ae7d-9294ba2854fa Finland (FI) b13374ee-6f72-4e10-ae12-33e81bcfc856 Netherlands (NL) aafcd53f-4f76-4a48-991b-3c70373b814f Germany (DE) 08750b2c-f6f5-4cbc-af6e-920b98268ae9 Netherlands (NL) 8699cdd4-d2d2-46a9-8bf6-ca7a24c69be5 Netherlands (NL) a49b2555-f610-49c5-be8a-a6368bfb46c1 Estonia (EE) e34dc943-512d-492d-8de5-8df021f436d6 Greece (GR) f8083088-0978-4053-95e8-05bd971aba66 Portugal (PT) 96c89ff8-eb84-4285-bbd1-3879d6bc3b49 Denmark (DK) 7de00697-df77-43ea-8dfd-a6576ad93b54 Germany (DE) |
| Ordering | |
| Order Code US and Canada: | XT2SE3063BFF000XXX |
| E-Number (Finland): | 3638183 |
| EAN: | 8015644014520 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 90 mm |
| Product Net Height: | 130 mm |
| Product Net Depth / Length: | 82.5 mm |
| Product Net Weight: | 1.4 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 130 mm |
| Package Level 1 Height: | 208 mm |
| Package Level 1 Depth / Length: | 145 mm |
| Package Level 1 Gross Weight: | 1.64 kg |
| Package Level 1 EAN: | 8015644014520 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH002230A1001 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 32.5..100 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 3 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 4.85 W |
| Rated Current (In): | 63 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 300€¦630 A |
| Rated Insulation Voltage (Ui): | 1000 V |
| Rated Operational Voltage: | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
| Rated Uninterrupted Current (Iu): | 160 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M6 |
| Release: | TMA |
| Release Type: | TM |
| Setting Range: | 44.1…63 A |
| Short-Circuit Performance Level: | S |
| Standards: | IEC60947-2 |
| Sub-type: | XT2 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5901 |
| GL Certificate: | 1SDL000163R0093 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000721R0100 |
| Mechanical Drawings: | 1SDH000721R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000721R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |