Description
| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 77 % |
| End of Life Instructions: | 9AKK108468A2364 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108468A1905 9AKK108468A1913 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | cc3bd6d1-3114-4929-9498-ad2ae77b9b5e Italy (IT) |
| Simplified SCIP: | 2e107063-38cd-49e2-ac03-8420476c08b1 Germany (DE) fd746f3c-d41d-4315-84f5-416f2d3b9084 Germany (DE) 2b462966-444f-42d8-9fcb-1a4bc4a5d9a3 Germany (DE) f3e7d6dd-c1fd-4b31-821d-01e2e02cb40f Hungary (HU) 9232bfa3-36ca-4d37-b717-ede253ee5c49 Portugal (PT) 1d0b068a-8583-4f86-bdf1-1cc6903e6da3 Sweden (SE) 5881c944-ea0a-4f2b-a476-56819f91002c Poland (PL) c6b2c573-dbd9-4ec9-8c8a-ff7b7afa146f Poland (PL) bfb0b4dc-f835-41ed-89a3-7e13a457d3ed Czech Republic (CZ) 13060fd3-3417-4be7-9f75-dc2837866a9f Belgium (BE) a2d51d96-abd9-475e-b158-80ff60d1c558 Spain (ES) 976ceba1-efad-4508-a65b-20a5ac38e70a France (FR) 5c9eb462-fab8-44ae-badb-187681e9f0ff Poland (PL) 75cf90c0-2b12-4c2f-9ae6-bec93b6a6af5 Norway (NO) 55245274-c60c-4a51-ad21-a6b7da341d5e Hungary (HU) f4d5b993-02ae-475f-bc00-ab1f7a25d3fb Belgium (BE) 8581d7c0-89a5-455b-9b1c-fcac617c178f Sweden (SE) aa29d88b-1496-46b8-80c1-11b7c0960b0e Estonia (EE) 4d5299a9-ab2d-4fb7-a6a4-ad6645d989a5 Netherlands (NL) ae10de5a-093d-47e7-8961-d87c394fa68b France (FR) 08a81759-193a-4767-917b-17303b3b6efb Greece (GR) a1f532ad-2a4c-49f1-9312-fd7e823dc2d3 Finland (FI) 6fc91444-07d6-4bad-b0f1-863da86f9b9b Germany (DE) c0d87f7c-7b07-4715-a5e5-40c7903f1882 Croatia (HR) 13fd5ae4-c434-4450-a0a4-d93ddf34faeb Germany (DE) efee113d-3b11-4132-a8b9-81d03f23d168 Bulgaria (BG) 01927ec6-3c44-4481-a716-24611bc77a6a Denmark (DK) |
| Ordering | |
| Order Code US and Canada: | Z6HYETBD000A000000XX |
| EAN: | 8015644751449 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 762 mm |
| Product Net Height: | 371 mm |
| Product Net Depth / Length: | 270 mm |
| Product Net Weight: | 109 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 515 mm |
| Package Level 1 Height: | 610 mm |
| Package Level 1 Depth / Length: | 1000 mm |
| Package Level 1 Gross Weight: | 118 kg |
| Package Level 1 EAN: | 8015644751449 |
| Additional Information | |
| Product Main Type: | SACE Emax 2 |
| Product Name: | Air Circuit Breaker |
| Product Type: | Air Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH001252R0223 |
| Technical | |
| Current Type: | AC |
| Electrical Durability: | Ue =< 440 V 2000 cycle Ue = 500 … 690 V 2000 cycle 10 cycles per hour |
| Mechanical Durability: | 12000 cycle 60 cycles per hour |
| Number of Poles: | 3 |
| Power Loss: | 767 W |
| Rated Current (In): | 6300 A |
| Rated Impulse Withstand Voltage (Uimp): | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui): | AC 1000 V |
| Rated Operational Voltage: | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 100 kA (230 V AC) 100 kA (380 V AC) 100 kA (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 100 kA (500 V AC) 100 kA (660 V AC) 100 kA (690 V AC) 100 kA |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics): | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw): | for 1 s 100 kA for 3 s 100 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 100 kA (500 V AC) 100 kA (525 V AC) 100 kA (690 V AC) 100 kA |
| Rated Uninterrupted Current (Iu): | 6300 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M12 |
| Release: | Ekip Touch LI |
| Release Type: | EL |
| Short-Circuit Performance Level: | H |
| Standards: | IEC |
| Sub-type: | E6.2 |
| Terminal Connection Type: | Rear flat Horizontal |
| Terminal Type: | Bolt |
| Tightening Torque: | 70 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| CSA Certificate: | No certification needed |
| CSA Certificate (Intrinsic Safe): | No certification needed |
| Data Sheet, Technical Information: | 1SDC200023D0209 |
| Declaration of Conformity – CE: | 9AKK106713A5544 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Mechanical Drawings: | 1SDH001060R0100 |
| Wiring Diagram: | 1SDM000091R0001 |
| Instructions and Manuals: | 1SDH001000R0002 |
| Instructions and Manuals (Part 2): | 1SDH001316R1002 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC): | 4926 >> Air circuit breakers |
| Object Classification Code: | Q |
| UNSPSC: | 39121615 |
| WEEE Category: | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |