Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 79.1 % |
End of Life Instructions: | 9AKK108468A2361 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108468A1902 9AKK108468A1909 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | 5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy (IT) |
Ordering | |
Order Code US and Canada: | ZBNSEJAD000A000000XX |
EAN: | 8015644768249 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 407 mm |
Product Net Height: | 425 mm |
Product Net Depth / Length: | 383 mm |
Product Net Weight: | 55 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 515 mm |
Package Level 1 Height: | 610 mm |
Package Level 1 Depth / Length: | 615 mm |
Package Level 1 Gross Weight: | 60 kg |
Package Level 1 EAN: | 8015644768249 |
Additional Information | |
Product Main Type: | SACE Emax 2 |
Product Name: | Air Circuit Breaker |
Product Type: | Air Circuit Breaker |
Version: | W |
CAD Dimensional Drawing: | 1SDH001252R0432 |
Technical | |
Current Type: | AC |
Electrical Durability: | Ue =< 440 V 12000 cycle Ue = 500 … 690 V 10000 cycle 30 cycles per hour |
Mechanical Durability: | 25000 cycle 60 cycles per hour |
Neutral Pole Current ([%Iu]): | 100 % |
Number of Poles: | 4 |
Power Loss: | 288 W |
Rated Current (In): | 1600 A |
Rated Impulse Withstand Voltage (Uimp): | acc. to IEC 60947-2 12 kV |
Rated Insulation Voltage (Ui): | AC 1000 V |
Rated Operational Voltage: | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 66 kA (230 V AC) 66 kA (380 V AC) 66 kA (400 V AC) 66 kA (415 V AC) 66 kA (440 V AC) 66 kA (500 V AC) 66 kA (660 V AC) 66 kA (690 V AC) 66 kA |
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics): | 100 % |
Rated Short-time Withstand Current Low Voltage (Icw): | for 1 s 66 kA for 3 s 50 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (400 V AC) 66 kA (415 V AC) 66 kA (440 V AC) 66 kA (500 V AC) 66 kA (525 V AC) 66 kA (690 V AC) 66 kA |
Rated Uninterrupted Current (Iu): | 1600 A |
Rated Voltage (Ur): | 690 V |
Release: | Ekip Touch LI |
Release Type: | EL |
Short-Circuit Performance Level: | N |
Standards: | IEC |
Sub-type: | E2.2 |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
CSA Certificate: | No certification needed |
CSA Certificate (Intrinsic Safe): | No certification needed |
Data Sheet, Technical Information: | 1SDC200023D0209 |
Declaration of Conformity – CE: | 9AKK106713A5902 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Mechanical Drawings: | 1SDH001000R0102 |
Wiring Diagram: | 1SDM000091R0001 |
Instructions and Manuals: | 1SDH001000R0002 |
Instructions and Manuals (Part 2): | 1SDH001316R1002 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
IDEA Granular Category Code (IGCC): | 4926 >> Air circuit breakers |
Object Classification Code: | Q |
UNSPSC: | 39121615 |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |