Description
| Technical | |
| Standards: | IEC 61643-11 / EN 61643-11 |
| Type of Low Voltage Distribution System: | TT TN-S |
| Suitable For: | To protect the systems against the transient overvoltage (lightning) |
| Rated Voltage (Ur): | 230 V AC |
| Nominal AC Voltage of the System (Uo): | 230 / 400 V |
| Voltage Rating DC: | 350 V |
| Voltage Protection Level ( Up): | 1.4 kV (L-N) 1.4 kV (N-PE) 1.4 kV |
| Maximum Continuous Operating Voltage (Uc): | (L-PE) 275 V |
| Temporary Overvoltage Test Value (UT): | (L-N) 337 V (N-PE) 1200 V |
| Rated Service Short-Circuit Breaking Capacity (Ics): | 100 kA |
| Discharge Current: | Nominal (8 / 20 µs) 20 kA I (max, 8 / 20 µs) 80 kA |
| Impulse Current: | I (imp, 10 / 350 µs) 2 kA |
| Short Circuit Withstand Icc: | 100 kA |
| Power Loss: | 28 mW |
| Arrester Class: | II |
| Number of Protected Poles: | 2 |
| Number of Auxiliary Contacts NC: | 1 |
| Number of Auxiliary Contacts NO: | 1 |
| Number of Poles: | 2 |
| Number of Conductors: | 2 |
| Position of Neutral Terminals: | Right |
| Transmission Standard: | Optic |
| Version: | Plug-in |
| Mounting Type: | DIN-Rail |
| Product Type: | QS |
| Options Provided: | Industry, commercial building |
| Auxiliary Circuit Load: | Minimum 12Vdc – 10mA Maximum 250Vac – 1A |
| Preventive Maintenance Feature: | Yes |
| Status Indicator: | Yes |
| Fuse Size: | 2 modular spacing |
| Material Compliance | |
| RoHS Information: | 9AKK108466A4617 |
| RoHS Status: | Following EU Directive 2011/65/EU |
| RoHS Date: | 20220317 |
| REACH Declaration: | 9AKK108468A9644 |
| REACH Information: | False – does not contain substances > 0.1 mass percentage |
| REACH Date: | 20231212 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108468A3363 |
| Environmental | |
| Degree of Protection: | IP20 |
| Maximum Operating Altitude Permissible: | Without Derating 5000 |
| Dimensions | |
| Width in Number of Modular Spacings: | 2 |
| Product Net Width: | 35.6 mm |
| Product Net Height: | 95.8 mm |
| Product Net Depth / Length: | 76.7 mm |
| Product Net Weight: | 0.3 kg |
| Ordering | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Gross Weight: | 320 g |
| Certificates and Declarations | |
| CQC Certificate: | 9AKK107680A1974 |
| Declaration: | 2CTC432056G1701 |
| Declaration of Conformity – CE: | 9AKK108466A4617 |
| Installation | |
| Instructions and Manuals: | 2CTC432106M1701 |
| Popular Downloads | |
| Data Sheet, Technical Information: | 2CTC432313D0201 |
| Mechanical Drawings: | 2CTC800015F0900.pdf 2CTC800015F0901.dxf 2CTC800015F0902.stp 2CTC800015F0903.igs |
| Classifications | |
| ETIM 8: | EC000941 – Surge protection device for power supply systems |
| ETIM 9: | EC000941 – Surge protection device for power supply systems |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B: | Business To Business |
| CN8: | 85363090 |
| eClass: | V11.0 : 27130805 |
| Object Classification Code: | 141DCC |





