Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
EcoSolutions Profile: | 9AKK108469A3798 |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 90.6 % |
Offered with Extended Lifetime: | Product Durability |
Offered with Takeback Services: | Take Back for Recycling |
End of Life Instructions: | 9AKK108468A3132 |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108467A7833 |
Technical | |
Standards: | IEC/EN 60898-1 CSA 22.2 No. 235 IEC/EN 60947-2 UL 1077 |
Tripping Characteristic: | B |
Rated Operational Voltage: | acc. to IEC 60898-1 400 V AC acc. to IEC 60898-1 400 V acc. to IEC 60947-2 440 V AC |
Operational Voltage: | Maximum (Incl. Tolerance) 125 V DC Maximum (Incl. Tolerance) 440 V AC Minimum 12 V AC Minimum 12 V DC |
Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 440 V |
Rated Impulse Withstand Voltage (Uimp): | 4 kV at 2000 m 5 kV at Sea Level 6.2 kV |
Dielectric Test Voltage: | 50/60 Hz, 1 min: 2 kV |
Input Voltage Type: | AC/DC |
Rated Current (In): | 50 A |
Rated Short-Circuit Capacity: | (AC) 10 kA (230 V AC) 10 kA (400 V AC) 10 kA (400 V) 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (230 V AC) 25 kA (400 V AC) 15 kA (440 V AC) 15 kA (230 V) 25 kA (400 V) 15 kA |
Rated Conditional Short-Circuit Current (Inc): | (230 V) 10 kA (400 V) 20 kA |
Rated Service Short-Circuit Breaking Capacity (Ics): | (133 V AC) 15 kA (230 V AC) 7.5 kA |
Frequency (f): | 50 Hz |
Rated Frequency (f): | 50 / 60 Hz |
Power Loss: | 6.5 W at Rated Operating Conditions per Pole 3.25 W |
Power Supply Connection: | Arbitrary |
Contact Position Indication: | Red ON / Green OFF |
Energy Limiting Class: | 3 |
Electrical Endurance: | 20000 AC cycle 10000 AC cycle |
Mechanical Endurance: | 20000 cycle |
Number of Protected Poles: | 2 |
Number of Poles: | 2 |
Overvoltage Category: | III |
Tightening Torque: | 2.8 N·m |
Screw Terminal Type: | Failsafe Bi-directional Cylinder-lift Terminal |
Actuator Marking: | I / O |
Actuator Material: | Insulation Group II, Black, Sealable |
Housing Material: | Insulation Group II, RAL 7035 |
Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position: | any |
Recommended Screw Driver: | Pozidriv 2 |
Accessories Available: | Yes |
Connecting Capacity: | Busbar 10 / 10 mm² Flexible with Ferrule 0.75 … 25 mm² Flexible 0.75 … 25 mm² Flexible 0.75 … 25 mm² Rigid 0.75 … 35 mm² Rigid 0.75 … 35 mm² Stranded 0.75 … 35 mm² |
Installation Size: | acc. to DIN 43880 1 |
Terminal Type: | Screw Terminals |
Material Compliance | |
RoHS Information: | 2CDK400003K0203 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
RoHS Date: | 20161001 |
REACH Declaration: | 9AKK108468A9644 |
REACH Information: | True – contains substances > 0.1 mass percentage |
REACH Date: | 20231212 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108468A3363 |
SCIP: | 9008497a-14f6-4cfd-83c5-11cf3bc660d1 Germany (DE) |
Environmental | |
Ambient Air Temperature: | Operation -25 … +55 °C Storage -40 … +70 °C |
Reference Ambient Air Temperature: | 30 °C |
Degree of Protection: | IP20 IP40 Enclosure with Cover IP40 |
Pollution Degree: | 3 |
Environmental Conditions: | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
Resistance to Vibrations: | 20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz |
Resistance to Shock acc. to IEC 60068-2-27: | 25g 2 shocks 13 ms |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA: | 125 V DC 480Y/277 V AC |
Interrupting Rating acc. to UL1077: | (125 V DC) 10 kA (277 V AC) 6 kA (480Y / 277 V AC) 6 kA |
Connecting Capacity UL/CSA: | Busbar 14-8 AWG Conductor 14-4 AWG |
Tightening Torque UL/CSA: | 18 in·lb |
Dimensions | |
Width in Number of Modular Spacings: | 2.0 |
Product Net Width: | 35 mm |
Product Net Height: | 88 mm |
Product Net Depth / Length: | 69 mm |
Product Net Weight: | 0.25 kg |
Pole Net Weight: | 0.125 kg |
Built-In Depth (t2): | 69 mm |
Dimension Diagram: | 2CDC022007F0010 |
Ordering | |
Package Level 1 Units: | carton 5 piece |
Package Level 1 Gross Weight: | 1.3 kg |
E-Number (Finland): | 3210955 |
E-Number (Sweden): | 2101148 |
Certificates and Declarations | |
Certification Agency: | EN IEC |
Declaration of Conformity – CE: | 2CDK403001D0607 |
Declaration of Conformity – UKCA: | 9AKK108467A5053 |
I²t Characteristic: | 9AKK107992A5102 |
Installation | |
Instructions and Manuals: | 2CDS207104P0002 |
Popular Downloads | |
Data Sheet, Technical Information: | 9AKK107046A0423 |
I²t Characteristic: | 9AKK107992A5102 |
Classifications | |
ETIM 8: | EC000042 – Miniature circuit breaker (MCB) |
ETIM 9: | EC000042 – Miniature circuit breaker (MCB) |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
WEEE B2C / B2B: | Business To Business |
CN8: | 8536 20 10 |
UNSPSC: | 39121603 |
eClass: | V11.0 : 27141901 |
IDEA Granular Category Code (IGCC): | 4897 >> Miniature circuit breakers |
Object Classification Code: | F |