Description
Environmental | |
Environmental Information: | 9AKK10103A1058 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
Ordering | |
E-Number (Finland): | 3655427 |
EAN: | 8015644627454 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 280 mm |
Product Net Height: | 268 mm |
Product Net Depth / Length: | 103.5 mm |
Product Net Weight: | 12 kg |
Container Information | |
Package Level 1 Units: | 1 piece |
Package Level 1 Width: | 305 mm |
Package Level 1 Height: | 285 mm |
Package Level 1 Depth / Length: | 370 mm |
Package Level 1 Gross Weight: | 14 kg |
Package Level 1 EAN: | 8015644627454 |
Additional Information | |
Product Main Type: | SACE Tmax T |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Suitable For: | T6 |
Suitable for Product Class: | Moulded Case Circuit Breakers |
Version: | F |
Technical | |
Electrical Durability: | 5000 cycle 60 cycles per hour |
Mechanical Durability: | 20000 cycle 120 cycles per hour |
Number of Poles: | 4 |
Power Loss: | at Rated Operating Conditions per Pole 32 W |
Rated Current (In): | 800 A |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Insulation Voltage (Ui): | 1000 V |
Rated Operational Voltage: | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 16.5 kA |
Rated Short-time Withstand Current Low Voltage (Icw): | for 1 s 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 22 kA |
Rated Uninterrupted Current (Iu): | 800 A |
Release: | PR221DS-LS/I |
Release Type: | EL |
Short-Circuit Performance Level: | S |
Standards: | IEC |
Sub-type: | T6 |
Terminal Connection Type: | Fixed Circuit-Breakers Front |
Test Voltage Max (Utest): | 3500 V |
Certificates and Declarations | |
Data Sheet, Technical Information: | 1SDC210015D0201 |
Declaration of Conformity – CE: | 9AKK106713A5538 |
Instructions and Manuals: | 1SDH000511R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
UNSPSC: | 39121100 |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |