Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
End of Life Instructions: | 9AKK108468A2347 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | 6774955b-d880-4def-9c74-19a93e0bae4c Italy (IT) |
Simplified SCIP: | c9218e91-3702-48c7-bafc-2a74747ba1b2 Germany (DE) 0d2150b0-2b95-48d1-ab50-aaa310de7cb0 Poland (PL) cee9d778-423b-4301-9f27-16e26d8be184 Norway (NO) 6b8f38c8-1ec2-4c2b-beeb-31ed145d161d Finland (FI) dcaf512d-d6f7-4e34-8d7c-982d94a7f49c Netherlands (NL) 97a89143-ee64-45d0-a21b-cfae8450263a Germany (DE) 2f5e5e2f-ab8d-4466-a2bd-3cb87ff7223e Denmark (DK) 2a4f90b7-7165-43c0-87f0-06e205cbb250 Germany (DE) 556152b5-5ed1-4bb6-90d2-a8846f692834 Croatia (HR) 5d2ea5a0-3812-4d07-bc83-e7557e2c20cd Czech Republic (CZ) 340d33d7-db60-4da5-8988-3d97adf34e40 Poland (PL) 6f662a23-c2f2-45aa-8b67-7622964ab8e6 Netherlands (NL) c6796a85-e78d-406b-86fd-9d50ed361761 Netherlands (NL) 642eed60-ab43-438e-b29b-d2b83a1d1d0a Estonia (EE) 710d4b07-1223-4202-8a2a-8f2c8a75f77e Greece (GR) 27624ad5-a53c-4371-b226-08015a416947 Portugal (PT) 36b5dfe7-336d-4134-952e-28633cf67e81 Bulgaria (BG) 37bea7dc-eb4c-4a6d-a626-31b8e1a6ac35 Sweden (SE) 8e83dd65-51f4-470f-a07f-c2e48c91cd0c Poland (PL) c5e5f6cf-d260-44c6-aac5-44b3514c85b0 France (FR) 247f3a3c-b0a8-42bf-aae0-452961210a71 Sweden (SE) 635ad7c9-532f-4f1d-a1a1-5137b6daac93 Germany (DE) 1ecf956f-f5a6-4ebb-b28c-be0db3d867c8 Germany (DE) f525384a-8929-44a6-aa0d-3ea572ba0573 France (FR) 360273d7-50aa-43b3-8eef-efbe04b1f63c Netherlands (NL) 827c34ff-479a-4864-9411-9b7485068d3b Spain (ES) 529713d3-e7e2-46e2-ad21-1ee6884c5827 Netherlands (NL) |
Ordering | |
Order Code US and Canada: | XT1BE3125AFF000XXX |
E-Number (Finland): | 3640496 |
EAN: | 8015644007157 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 76.2 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 70 mm |
Product Net Weight: | 1.1 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 128 mm |
Package Level 1 Height: | 135 mm |
Package Level 1 Depth / Length: | 143 mm |
Package Level 1 Gross Weight: | 1.137 kg |
Package Level 1 EAN: | 8015644007157 |
Additional Information | |
Circuit Breaker Type to be Associated: | Power Distribution |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Version: | F |
CAD Dimensional Drawing: | 1SDH001295R0008 |
Technical | |
Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour 8000 cycle |
Mechanical Durability: | 240 cycles per hour 25000 cycle |
Number of Poles: | 3 |
Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 10.7 W |
Rated Current (In): | 125 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 1250 A |
Rated Insulation Voltage (Ui): | 800 V |
Rated Operational Voltage: | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.25 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
Rated Uninterrupted Current (Iu): | 160 A |
Rated Voltage (Ur): | 690 V |
Recommended Screw Driver: | Main Circuit M6 |
Release: | TMD |
Release Type: | TM |
Setting Range: | 87.5…125 A |
Short-Circuit Performance Level: | B |
Standards: | IEC60947-2 |
Sub-type: | XT1 |
Terminal Connection Type: | Front |
Terminal Type: | Bolt |
Tightening Torque: | 6 N·m |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
Declaration of Conformity – CE: | 9AKK106713A5532 |
GL Certificate: | 1SDL000163R0103 |
LR Certificate: | 1SDL000163R0100 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Dimension Diagram: | 1SDH000719R0100 |
Mechanical Drawings: | 1SDH000719R0100 |
Wiring Diagram: | 1SDM000068R0001 |
Instructions and Manuals: | 1SDH000719R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |