ABB XT1B 160 TMD 125-1250 3p F F

General Information

Extended Product Type: XT1B 160 TMD 125-1250 3p F F
Product ID: 1SDA066808R1
EAN: 8015644007157
Catalog Description: XT1B 160 TMD 125-1250 3p F F
Long Description: C.BREAKER TMAX XT1B 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 125-1250 A

Description

ABB EcoSolutions
ABB EcoSolutions: Yes
Circular Value
Circular Design Principles Recyclability Rate: Design for Closing Resource Loops – Standard EN45555 – 55.9 %
End of Life Instructions: 9AKK108468A2347
Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
Eco Transparency
Environmental Product Declaration – EPD: 9AKK108468A1890
9AKK108468A7793
Environmental
Environmental Information: 9AKK108467A6707
Material Compliance
REACH Declaration: 9AKK108466A1425
RoHS Information: 9AKK108466A1424
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
Toxic Substances Control Act – TSCA: 9AKK108467A8326
SCIP: 6774955b-d880-4def-9c74-19a93e0bae4c Italy (IT)
Simplified SCIP: c9218e91-3702-48c7-bafc-2a74747ba1b2 Germany (DE)
0d2150b0-2b95-48d1-ab50-aaa310de7cb0 Poland (PL)
cee9d778-423b-4301-9f27-16e26d8be184 Norway (NO)
6b8f38c8-1ec2-4c2b-beeb-31ed145d161d Finland (FI)
dcaf512d-d6f7-4e34-8d7c-982d94a7f49c Netherlands (NL)
97a89143-ee64-45d0-a21b-cfae8450263a Germany (DE)
2f5e5e2f-ab8d-4466-a2bd-3cb87ff7223e Denmark (DK)
2a4f90b7-7165-43c0-87f0-06e205cbb250 Germany (DE)
556152b5-5ed1-4bb6-90d2-a8846f692834 Croatia (HR)
5d2ea5a0-3812-4d07-bc83-e7557e2c20cd Czech Republic (CZ)
340d33d7-db60-4da5-8988-3d97adf34e40 Poland (PL)
6f662a23-c2f2-45aa-8b67-7622964ab8e6 Netherlands (NL)
c6796a85-e78d-406b-86fd-9d50ed361761 Netherlands (NL)
642eed60-ab43-438e-b29b-d2b83a1d1d0a Estonia (EE)
710d4b07-1223-4202-8a2a-8f2c8a75f77e Greece (GR)
27624ad5-a53c-4371-b226-08015a416947 Portugal (PT)
36b5dfe7-336d-4134-952e-28633cf67e81 Bulgaria (BG)
37bea7dc-eb4c-4a6d-a626-31b8e1a6ac35 Sweden (SE)
8e83dd65-51f4-470f-a07f-c2e48c91cd0c Poland (PL)
c5e5f6cf-d260-44c6-aac5-44b3514c85b0 France (FR)
247f3a3c-b0a8-42bf-aae0-452961210a71 Sweden (SE)
635ad7c9-532f-4f1d-a1a1-5137b6daac93 Germany (DE)
1ecf956f-f5a6-4ebb-b28c-be0db3d867c8 Germany (DE)
f525384a-8929-44a6-aa0d-3ea572ba0573 France (FR)
360273d7-50aa-43b3-8eef-efbe04b1f63c Netherlands (NL)
827c34ff-479a-4864-9411-9b7485068d3b Spain (ES)
529713d3-e7e2-46e2-ad21-1ee6884c5827 Netherlands (NL)
Ordering
Order Code US and Canada: XT1BE3125AFF000XXX
E-Number (Finland): 3640496
EAN: 8015644007157
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 76.2 mm
Product Net Height: 130 mm
Product Net Depth / Length: 70 mm
Product Net Weight: 1.1 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Depth / Length: 143 mm
Package Level 1 Gross Weight: 1.137 kg
Package Level 1 EAN: 8015644007157
Additional Information
Circuit Breaker Type to be Associated: Power Distribution
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: Automatic Circuit Breaker
Version: F
CAD Dimensional Drawing: 1SDH001295R0008
Technical
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: 240 cycles per hour
25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Order Multiple: 1 piece
Power Loss: at Rated Operating Conditions per Pole 10.7 W
Rated Current (In): 125 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 1250 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 25 kA
(230 V AC) 25 kA
(240 V AC) 25 kA
(380 V AC) 18 kA
(415 V AC) 18 kA
(440 V AC) 11.25 kA
(500 V AC) 8 kA
(525 V AC) 6 kA
(690 V AC) 3 kA
(250 V DC) 2 Poles in Series 18 kA
(500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 25 kA
(230 V AC) 25 kA
(240 V AC) 25 kA
(380 V AC) 18 kA
(415 V AC) 18 kA
(440 V AC) 15 kA
(500 V AC) 8 kA
(525 V AC) 6 kA
(690 V AC) 3 kA
(250 V DC) 2 Poles in Series 18 kA
(500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 87.5…125 A
Short-Circuit Performance Level: B
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m
Certificates and Declarations
ATEX Certificate: No certification needed
Data Sheet, Technical Information: 1SDC210100D0206
1SDC210099D0206
Declaration of Conformity – CE: 9AKK106713A5532
GL Certificate: 1SDL000163R0103
LR Certificate: 1SDL000163R0100
UL Certificate: No certification needed
VDE Certificate: No certification needed
Dimension Diagram: 1SDH000719R0100
Mechanical Drawings: 1SDH000719R0100
Wiring Diagram: 1SDM000068R0001
Instructions and Manuals: 1SDH000719R0001
Classifications
ETIM 8: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
eClass: V11.1 : 27370409