Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
End of Life Instructions: | 9AKK108468A2347 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | 4ff9b03b-1cf2-4837-8d24-93dc6121834d Italy (IT) |
Simplified SCIP: | 376db5fd-877a-4d16-90ca-1445f9cc3141 Germany (DE) 4da9f204-50cc-48b7-b553-1da097a7c855 Finland (FI) d5ace655-c799-4282-b3ae-2598d9667b08 Netherlands (NL) a6bea1a2-aa2e-4fe2-bcab-e3f7f257dee4 Germany (DE) 9675f1d6-1131-47e6-bd74-fbc792671b86 Denmark (DK) 1c694b3b-5fe7-4a27-b730-11e35f757d5e Germany (DE) d7c05fd5-cc87-4458-8302-2f636925db52 Croatia (HR) ef885e92-d9b1-45c6-8cb6-c4ad6bb41325 Czech Republic (CZ) b47804c6-d053-4df3-b4c0-7c0fa2a57582 Poland (PL) 204e69d2-52b6-4c7b-82d5-984ad6f0f7a8 Norway (NO) 6b900579-62ee-4ae6-a47c-92aae85ceef4 Poland (PL) c5f40fc3-0ccb-4d26-9c25-78659538a6eb Germany (DE) 9c041414-51e7-418a-be70-326cd293602c Germany (DE) 3d472ef2-2bb2-43b6-ada4-c165d9ff695d France (FR) 6ab977b3-e668-479a-b7d7-7aafb217dbf7 Netherlands (NL) 83fa4ab8-1066-451f-a5c6-3227f47b9f96 Spain (ES) a788f342-f7f6-4916-be29-4fee5c9d7806 Netherlands (NL) 66fc5a77-91a7-4570-9d07-534457120ddc Netherlands (NL) 8bf595ce-3c04-4fb3-a7e8-898a7663ba35 Netherlands (NL) 66a3997e-83ef-40cf-ba5f-5ec5ca01372c Estonia (EE) ad0a0ab9-ebde-471a-9cb3-0296bc863d67 Greece (GR) ad2768e5-aa41-4d1e-8d83-bd13e0d23b34 Portugal (PT) 7b0da51d-f9cc-40f1-ac31-f8b0ab9af686 Bulgaria (BG) 8c92815f-fcb1-4f59-9a66-c01580e417a2 Sweden (SE) 845a2832-1626-48c6-b53d-7f7eaa93c390 Poland (PL) d1422ba9-8bd5-4eb1-a791-d8c3f4d6901f France (FR) e29f066c-15c8-4974-954d-4bc2a7fdaee4 Sweden (SE) |
Ordering | |
Order Code US and Canada: | XT1BE3160AFF000XXX |
E-Number (Finland): | 3638199 |
EAN: | 8015644694494 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 76.2 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 70 mm |
Product Net Weight: | 1.1 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 128 mm |
Package Level 1 Height: | 135 mm |
Package Level 1 Depth / Length: | 143 mm |
Package Level 1 Gross Weight: | 1.139 kg |
Package Level 1 EAN: | 8015644694494 |
Additional Information | |
Circuit Breaker Type to be Associated: | Power Distribution |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Version: | F |
CAD Dimensional Drawing: | 1SDH001295R0008 |
Technical | |
Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour 8000 cycle |
Mechanical Durability: | 240 cycles per hour 25000 cycle |
Number of Poles: | 3 |
Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 15 W |
Rated Current (In): | 160 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 1600 A |
Rated Insulation Voltage (Ui): | 800 V |
Rated Operational Voltage: | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.25 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
Rated Uninterrupted Current (Iu): | 160 A |
Rated Voltage (Ur): | 690 V |
Recommended Screw Driver: | Main Circuit M6 |
Release: | TMD |
Release Type: | TM |
Setting Range: | 112…160 A |
Short-Circuit Performance Level: | B |
Standards: | IEC60947-2 |
Sub-type: | XT1 |
Terminal Connection Type: | Front |
Terminal Type: | Bolt |
Tightening Torque: | 6 N·m |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
Declaration of Conformity – CE: | 9AKK106713A5532 |
GL Certificate: | 1SDL000163R0103 |
LR Certificate: | 1SDL000163R0100 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Dimension Diagram: | 1SDH000719R0100 |
Mechanical Drawings: | 1SDH000719R0100 |
Wiring Diagram: | 1SDM000068R0001 |
Instructions and Manuals: | 1SDH000719R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |