Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
End of Life Instructions: | 9AKK108468A2347 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | 5cab19a8-a211-40c5-bc9a-598007736c08 Italy (IT) |
Simplified SCIP: | abcf1fa6-993f-40bd-948e-7031a129c6fd Spain (ES) 2909f5f6-ef26-4852-a421-00343f2a1bf8 Belgium (BE) 235f26cb-78ea-4142-86a8-40c6d9269936 Czech Republic (CZ) b696f5da-3bb1-4927-8e16-fbeb5af0d012 Hungary (HU) d0e32a4a-d6ae-4037-9851-caecdc49d0d1 France (FR) bb77a6d6-2708-474c-9f92-8318a5904431 Germany (DE) 617944fc-cc3f-4139-be4e-7081dda306fe Sweden (SE) 55adadea-3c4a-42ca-8e5b-951e0b147e82 Germany (DE) a7a3ee97-4148-4339-8171-d93ccb74797e Denmark (DK) f9f02b49-3f65-40ed-8d49-47307e1ed2cc Germany (DE) 67490311-ba58-4d42-b7a3-a1906ce91f7d Germany (DE) f99a2448-1391-42bf-a0b1-c2bc741303dd Croatia (HR) edb092a4-db53-4f4d-ac32-e7197c9fc30f Sweden (SE) 29bd069c-9cf7-451d-a67b-e19c26a6024f Netherlands (NL) 52315325-7b94-42a9-a354-6b77d2f4ecb3 Poland (PL) 8a890085-a4df-4f26-8327-093b43f9d1c2 Bulgaria (BG) f66a5efb-a803-42ba-866b-e1fecc118301 Norway (NO) 6133c899-40e7-4adc-8cd3-cfd3163257c9 Germany (DE) c6867efd-1d68-44fd-830a-c3cbfac0122a Portugal (PT) 8650c8bf-2467-49e7-9e5a-2a12ae456925 Poland (PL) bad829f3-7ca9-408f-b042-c31ab585e58e Greece (GR) c3fa5ce2-5f63-4b2e-a6c1-0b728aa19a97 France (FR) afa820e1-182b-4046-a65a-c721fbd0877f Estonia (EE) f2d51ade-ddb7-40d4-bc3f-bf975ca32912 Belgium (BE) 00ad4c8c-baf2-406d-aec8-f7ce17297da9 Hungary (HU) ecb413a7-766a-4b40-8eef-164b819c6b12 Poland (PL) 241539ed-acf4-4841-92dd-cb32075995b6 Finland (FI) |
Ordering | |
Order Code US and Canada: | XT1BE3040AFF000XXX |
E-Number (Finland): | 3638025 |
EAN: | 8015644003302 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 76.2 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 70 mm |
Product Net Weight: | 1.1 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 128 mm |
Package Level 1 Height: | 135 mm |
Package Level 1 Depth / Length: | 143 mm |
Package Level 1 Gross Weight: | 1.124 kg |
Package Level 1 EAN: | 8015644003302 |
Additional Information | |
Circuit Breaker Type to be Associated: | Power Distribution |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Version: | F |
CAD Dimensional Drawing: | 1SDH001295R0008 |
Technical | |
Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour 8000 cycle |
Mechanical Durability: | 240 cycles per hour 25000 cycle |
Number of Poles: | 3 |
Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 2.6 W |
Rated Current (In): | 40 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 450 A |
Rated Insulation Voltage (Ui): | 800 V |
Rated Operational Voltage: | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.25 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
Rated Uninterrupted Current (Iu): | 160 A |
Rated Voltage (Ur): | 690 V |
Recommended Screw Driver: | Main Circuit M6 |
Release: | TMD |
Release Type: | TM |
Setting Range: | 28…40 A |
Short-Circuit Performance Level: | B |
Standards: | IEC60947-2 |
Sub-type: | XT1 |
Terminal Connection Type: | Front |
Terminal Type: | Bolt |
Tightening Torque: | 6 N·m |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
Declaration of Conformity – CE: | 9AKK106713A5532 |
GL Certificate: | 1SDL000163R0103 |
LR Certificate: | 1SDL000163R0100 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Dimension Diagram: | 1SDH000719R0100 |
Mechanical Drawings: | 1SDH000719R0100 |
Wiring Diagram: | 1SDM000068R0001 |
Instructions and Manuals: | 1SDH000719R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |