Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
End of Life Instructions: | 9AKK108468A2347 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | a10a99fa-25ac-433d-b62d-7689b50c5c6c Italy (IT) |
Simplified SCIP: | 41cd25de-2393-4a57-97ea-cc906e39537c Germany (DE) 69cd6212-a899-4286-a772-8f474dc6c2bb Poland (PL) 37f17624-f471-4fd3-9b01-4c3625894ed3 Norway (NO) 4a34c8c8-9faf-4d2f-a59b-f51d5cdd4e8d Finland (FI) 5537a32c-26dc-4c9d-bc95-cb9905d66cfc Netherlands (NL) ef53c3b5-bc52-49fb-b855-7a8f21515267 Germany (DE) 56d03ad1-bd96-4376-9736-79e2ef64f4ab Denmark (DK) b3206c37-260c-4ebf-b240-4996b994f65d Germany (DE) ddb77a11-e6f5-4b70-bf76-a947793ddf48 Croatia (HR) 2c66013a-028e-4ca1-ac7d-2a830f47a45b Czech Republic (CZ) 6dcf4af9-a40a-4f40-9d60-663b40bbfdc5 Poland (PL) 614bc1e9-9182-4efb-aa78-e6e9372fd979 Netherlands (NL) e9e72111-5dc6-449c-afad-bfb9bf049e48 Netherlands (NL) b9ea0014-b614-4eed-a49a-4a83d350ab8b Estonia (EE) f45570f0-233c-43c3-9f60-758b79f8fb85 Greece (GR) 2d3090e5-4296-4969-815a-fc359c86aeef Portugal (PT) ef329402-0bc6-458f-adc4-ca0f59af1e1c Bulgaria (BG) 025d7c1b-8c66-4efe-8e49-75d8efc43eba Sweden (SE) 5be09893-83ce-4487-b2ec-d9a313525d19 Poland (PL) fcfc9e57-aec8-4b59-a24d-f90af6d29625 France (FR) 338fd03f-9159-443a-9b5a-4a9e4e3be02e Sweden (SE) a0316fa6-51b1-46f4-ae1e-139caf62298e Germany (DE) 149a8272-3a2b-4d5c-8608-5789a28b417d Germany (DE) c4ea13ca-23b7-43e3-afbb-04d28a093f11 France (FR) 3e5bb53d-feda-4a12-a764-6f9cf645e4c7 Netherlands (NL) 513eef80-bdee-472a-815e-31c738e5c4da Spain (ES) bff7649f-dcc0-4167-b394-414dac45600a Netherlands (NL) |
Ordering | |
Order Code US and Canada: | XT1BE3050AFF000XXX |
E-Number (Finland): | 3640498 |
EAN: | 8015644007119 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 76.2 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 70 mm |
Product Net Weight: | 1.1 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 128 mm |
Package Level 1 Height: | 135 mm |
Package Level 1 Depth / Length: | 143 mm |
Package Level 1 Gross Weight: | 1.134 kg |
Package Level 1 EAN: | 8015644007119 |
Additional Information | |
Circuit Breaker Type to be Associated: | Power Distribution |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Version: | F |
CAD Dimensional Drawing: | 1SDH001295R0008 |
Technical | |
Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour 8000 cycle |
Mechanical Durability: | 240 cycles per hour 25000 cycle |
Number of Poles: | 3 |
Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 3.7 W |
Rated Current (In): | 50 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 500 A |
Rated Insulation Voltage (Ui): | 800 V |
Rated Operational Voltage: | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.25 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA |
Rated Uninterrupted Current (Iu): | 160 A |
Rated Voltage (Ur): | 690 V |
Recommended Screw Driver: | Main Circuit M6 |
Release: | TMD |
Release Type: | TM |
Setting Range: | 35…50 A |
Short-Circuit Performance Level: | B |
Standards: | IEC60947-2 |
Sub-type: | XT1 |
Terminal Connection Type: | Front |
Terminal Type: | Bolt |
Tightening Torque: | 6 N·m |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
Declaration of Conformity – CE: | 9AKK106713A5532 |
GL Certificate: | 1SDL000163R0103 |
LR Certificate: | 1SDL000163R0100 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Dimension Diagram: | 1SDH000719R0100 |
Mechanical Drawings: | 1SDH000719R0100 |
Wiring Diagram: | 1SDM000068R0001 |
Instructions and Manuals: | 1SDH000719R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |