ABB XT1B 160 TMD 80-800 3p F F

General Information

Extended Product Type: XT1B 160 TMD 80-800 3p F F
Product ID: 1SDA066806R1
EAN: 8015644007133
Catalog Description: XT1B 160 TMD 80-800 3p F F
Long Description: C.BREAKER TMAX XT1B 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 80-800 A

Description

ABB EcoSolutions
ABB EcoSolutions: Yes
Circular Value
Circular Design Principles Recyclability Rate: Design for Closing Resource Loops – Standard EN45555 – 55.9 %
End of Life Instructions: 9AKK108468A2347
Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
Eco Transparency
Environmental Product Declaration – EPD: 9AKK108468A1890
9AKK108468A7793
Environmental
Environmental Information: 9AKK108467A6707
Material Compliance
REACH Declaration: 9AKK108466A1425
RoHS Information: 9AKK108466A1424
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
Toxic Substances Control Act – TSCA: 9AKK108467A8326
Ordering
Order Code US and Canada: XT1BE3080AFF000XXX
E-Number (Finland): 3640499
EAN: 8015644007133
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 76.2 mm
Product Net Height: 130 mm
Product Net Depth / Length: 70 mm
Product Net Weight: 1.1 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Depth / Length: 143 mm
Package Level 1 Gross Weight: 1.133 kg
Package Level 1 EAN: 8015644007133
Additional Information
Circuit Breaker Type to be Associated: Power Distribution
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: Automatic Circuit Breaker
Version: F
CAD Dimensional Drawing: 1SDH001295R0008
Technical
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: 240 cycles per hour
25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Order Multiple: 1 piece
Power Loss: at Rated Operating Conditions per Pole 4.8 W
Rated Current (In): 80 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 800 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 25 kA
(230 V AC) 25 kA
(240 V AC) 25 kA
(380 V AC) 18 kA
(415 V AC) 18 kA
(440 V AC) 11.25 kA
(500 V AC) 8 kA
(525 V AC) 6 kA
(690 V AC) 3 kA
(250 V DC) 2 Poles in Series 18 kA
(500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 25 kA
(230 V AC) 25 kA
(240 V AC) 25 kA
(380 V AC) 18 kA
(415 V AC) 18 kA
(440 V AC) 15 kA
(500 V AC) 8 kA
(525 V AC) 6 kA
(690 V AC) 3 kA
(250 V DC) 2 Poles in Series 18 kA
(500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 56…80 A
Short-Circuit Performance Level: B
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m
Certificates and Declarations
ATEX Certificate: No certification needed
Data Sheet, Technical Information: 1SDC210100D0206
1SDC210099D0206
Declaration of Conformity – CE: 9AKK106713A5532
GL Certificate: 1SDL000163R0103
LR Certificate: 1SDL000163R0100
UL Certificate: No certification needed
VDE Certificate: No certification needed
Dimension Diagram: 1SDH000719R0100
Mechanical Drawings: 1SDH000719R0100
Wiring Diagram: 1SDM000068R0001
Instructions and Manuals: 1SDH000719R0001
Classifications
ETIM 8: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
eClass: V11.1 : 27370409

Downloads

Datasheet