Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
End of Life Instructions: | 9AKK108468A2347 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | 0d8bc7a2-0b2f-4c4e-b0d2-ae3184d07c12 Italy (IT) |
Simplified SCIP: | 2d38a763-4edd-4ec0-852e-8a7e7d01b167 Germany (DE) ab107f86-ac30-4f6a-a6bf-c4d8c77a0fd2 France (FR) 4ce86c8a-88a3-4668-b9fe-6d159b3b770c Poland (PL) 2b6d4e8f-9999-4183-a923-afbb4bdcec78 Finland (FI) 1b141b21-8bef-4f72-8f3e-ddd51c5ec259 Norway (NO) 974eeae4-e997-42f0-aa0d-58883071678c Netherlands (NL) c0df14b2-ce11-4e19-a2d5-72e2790aa9cc Netherlands (NL) b756e454-2ef3-4dc7-99e0-091b44577511 Germany (DE) 99c1470b-f1a5-48b0-8949-840c4be74894 Denmark (DK) e16d074d-620a-4ea1-8227-b05dc2e7d098 Germany (DE) dfb95055-9cf7-4ec6-b0e7-801c62ca7cc8 Croatia (HR) 9fc57840-b252-4713-8387-c3b5c39c2768 Czech Republic (CZ) 56162500-c94b-403f-a284-3e358af29456 Netherlands (NL) 82077ecd-9e46-4ba5-85c7-22fd9245ee2d Netherlands (NL) df47e79a-6de1-4aa8-83e4-3b4ebc60686b Estonia (EE) 91ca0d03-e2ae-40be-88e0-e06a7b181f24 Greece (GR) 21de00c2-cdbb-4cc5-a139-d1e3d26dffcb Portugal (PT) 91902059-0a7b-46c8-9eda-6bb7beb04a2b Bulgaria (BG) 83cedd21-6566-49aa-bd8f-fa5be6b586dd Sweden (SE) 4f0c602c-433f-4412-8704-722fe1de2a92 Poland (PL) 1b963a22-3a58-43d0-94c5-819ab7622567 France (FR) 5489a759-29a8-46b8-a5c0-42d61d45ed5d Sweden (SE) b8e985c9-c29a-4e6d-a0f0-f79c981441a9 Germany (DE) 0a6e7309-6bb1-4725-9934-8c06601b79c0 Germany (DE) 3daf304a-39bc-447c-a8cd-0e009652dae7 Spain (ES) 4a0eb37f-875b-48f5-ad3a-e2fe91f042c6 Netherlands (NL) c8b2a3ef-2fdc-48b9-9068-d7b46a9d3213 Poland (PL) |
Ordering | |
Order Code US and Canada: | XT1CE3160AFF000XXX |
E-Number (Finland): | 3638779 |
EAN: | 8015644012939 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 76.2 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 70 mm |
Product Net Weight: | 1.1 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 128 mm |
Package Level 1 Height: | 135 mm |
Package Level 1 Depth / Length: | 143 mm |
Package Level 1 Gross Weight: | 1.128 kg |
Package Level 1 EAN: | 8015644012939 |
Additional Information | |
Circuit Breaker Type to be Associated: | Power Distribution |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Version: | F |
CAD Dimensional Drawing: | 1SDH001295R0008 |
Technical | |
Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour 8000 cycle |
Mechanical Durability: | 240 cycles per hour 25000 cycle |
Number of Poles: | 3 |
Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 15 W |
Rated Current (In): | 160 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 1600 A |
Rated Insulation Voltage (Ui): | 800 V |
Rated Operational Voltage: | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
Rated Uninterrupted Current (Iu): | 160 A |
Rated Voltage (Ur): | 690 V |
Recommended Screw Driver: | Main Circuit M6 |
Release: | TMD |
Release Type: | TM |
Setting Range: | 112…160 A |
Short-Circuit Performance Level: | C |
Standards: | IEC60947-2 |
Sub-type: | XT1 |
Terminal Connection Type: | Front |
Terminal Type: | Bolt |
Tightening Torque: | 6 N·m |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
Declaration of Conformity – CE: | 9AKK106713A5532 |
GL Certificate: | 1SDL000163R0103 |
LR Certificate: | 1SDL000163R0100 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Dimension Diagram: | 1SDH000719R0100 |
Mechanical Drawings: | 1SDH000719R0100 |
Wiring Diagram: | 1SDM000068R0001 |
Instructions and Manuals: | 1SDH000719R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
UNSPSC: | 39120000 |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |