Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.9 % |
End of Life Instructions: | 9AKK108468A2347 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108468A1890 9AKK108468A7793 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | 4e599235-d926-4615-a71c-1de7040d6726 Italy (IT) |
Simplified SCIP: | 77fcc699-7c06-40f6-9ee3-735c153c6dcd Germany (DE) 3fa2a954-0ff2-424c-8c38-69cffccb7e71 Poland (PL) 016eb8d1-70d2-428e-8610-6b17e417e722 Bulgaria (BG) 0515a311-cda7-4cb2-a92b-07e795ccb927 Sweden (SE) c41feba3-dcbe-4ff6-aa7d-3c65f17f6527 Spain (ES) e4a49827-b15d-4bf7-b12a-d07f41d3c670 Belgium (BE) 375df1ca-6156-42c0-8276-cf8d061e29e5 Germany (DE) 7de2ae1c-0dc5-4e4d-afbf-4dc18e4510dd Poland (PL) 8af8e392-4e25-48bf-a038-1c261e0fdbfe Norway (NO) 02595f39-f557-4a1a-869d-d447af948a58 Finland (FI) 7eade347-a4c7-4ae5-8109-1427d50ed287 Belgium (BE) 2fe2bc3e-fc12-446b-b7fe-318b44a1054a Denmark (DK) 87a04bcd-f6f5-4ded-86b8-93f3056d19e6 Greece (GR) 29ad1ea9-b920-490a-b737-100152dc7a18 Estonia (EE) 71d6aef1-f628-456a-a211-3e53829c15c8 Portugal (PT) 738ae6df-0753-4c0c-b1ed-075d6de5b990 Germany (DE) 8a780108-c8dd-441d-ae51-4bef2592234b Croatia (HR) 90390158-17bd-4b8b-b09e-df85907f43c6 Czech Republic (CZ) 2ae1704b-4034-423f-af47-5dc82d06826d Germany (DE) cb447a4b-0808-4c35-96bd-9c0adb63c697 Hungary (HU) fe90101c-9836-42b3-97a7-974d84e65396 Germany (DE) 611f72f5-49de-432e-ad9c-2760a05032de France (FR) 8d2b95c3-158d-4a08-a7f9-296f71ae1a45 Sweden (SE) 8087afeb-1934-4ed7-be66-48018a2e3f11 Netherlands (NL) 56c61503-9112-4d77-9173-d119116e6188 Poland (PL) 8ee92488-322f-4cc1-b31b-c49e4cd8e124 Hungary (HU) |
Ordering | |
Order Code US and Canada: | XT1CE3032AFF000XXX |
E-Number (Finland): | 3638774 |
EAN: | 8015644695187 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 76.2 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 70 mm |
Product Net Weight: | 1.1 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 128 mm |
Package Level 1 Height: | 135 mm |
Package Level 1 Depth / Length: | 143 mm |
Package Level 1 Gross Weight: | 1.12 kg |
Package Level 1 EAN: | 8015644695187 |
Additional Information | |
Circuit Breaker Type to be Associated: | Power Distribution |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Version: | F |
CAD Dimensional Drawing: | 1SDH001295R0008 |
Technical | |
Connecting Capacity Main Circuit: | Busbar 45.5 … 80 mm² |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour 8000 cycle |
Mechanical Durability: | 240 cycles per hour 25000 cycle |
Number of Poles: | 3 |
Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 2.1 W |
Rated Current (In): | 32 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 450 A |
Rated Insulation Voltage (Ui): | 800 V |
Rated Operational Voltage: | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
Rated Uninterrupted Current (Iu): | 160 A |
Rated Voltage (Ur): | 690 V |
Recommended Screw Driver: | Main Circuit M6 |
Release: | TMD |
Release Type: | TM |
Setting Range: | 22.4…32 A |
Short-Circuit Performance Level: | C |
Standards: | IEC60947-2 |
Sub-type: | XT1 |
Terminal Connection Type: | Front |
Terminal Type: | Bolt |
Tightening Torque: | 6 N·m |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
Declaration of Conformity – CE: | 9AKK106713A5532 |
GL Certificate: | 1SDL000163R0103 |
LR Certificate: | 1SDL000163R0100 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Dimension Diagram: | 1SDH000719R0100 |
Mechanical Drawings: | 1SDH000719R0100 |
Wiring Diagram: | 1SDM000068R0001 |
Instructions and Manuals: | 1SDH000719R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
UNSPSC: | 39120000 |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |