ABB XT1C 160 TMD 50-500 3p F F

General Information

Extended Product Type: XT1C 160 TMD 50-500 3p F F
Product ID: 1SDA067394R1
EAN: 8015644695194
Catalog Description: XT1C 160 TMD 50-500 3p F F
Long Description: C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 50-500 A

Description

ABB EcoSolutions
ABB EcoSolutions: Yes
Circular Value
Circular Design Principles Recyclability Rate: Design for Closing Resource Loops – Standard EN45555 – 55.9 %
End of Life Instructions: 9AKK108468A2347
Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
Eco Transparency
Environmental Product Declaration – EPD: 9AKK108468A1890
9AKK108468A7793
Environmental
Environmental Information: 9AKK108467A6707
Material Compliance
REACH Declaration: 9AKK108466A1425
RoHS Information: 9AKK108466A1424
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
Toxic Substances Control Act – TSCA: 9AKK108467A8326
SCIP: 6963f79e-5b3e-491f-8111-ed51582b95f5 Italy (IT)
Simplified SCIP: 03623cf1-c0d9-4f9d-a987-0129b1b5c4e3 Germany (DE)
0b897293-8966-400d-85d3-3adb67e5645e Netherlands (NL)
788f7ce1-ce81-46b1-b516-e8a1a5810a29 Netherlands (NL)
aa1def39-a5e1-402c-a7fb-1f69c65bf0cf Germany (DE)
75a37be3-c5f2-48d2-921c-196f3e715fbb Denmark (DK)
2b729765-22b2-414d-96db-c45c85b86b34 Germany (DE)
73e3b539-3241-4e7c-b2e3-a271a8580cce Croatia (HR)
f266fe7c-cd54-450c-984b-762ab9f9b7b5 Czech Republic (CZ)
01bac839-3a95-4abc-9842-01bf939126de Netherlands (NL)
6d189084-7c30-4847-b66c-12452df5457e Netherlands (NL)
afbc9104-3742-44d7-8a17-ef24c66adf7e Estonia (EE)
fa14a73d-5be7-45d6-bea7-eef52df9a461 Greece (GR)
c090809c-f591-4fd0-8f91-3f7005422d41 Portugal (PT)
8c6a9e39-4f7d-4d91-a84a-7c5fae9fab39 Bulgaria (BG)
a751af1f-ba16-4b16-bae1-88bd49a124fd Sweden (SE)
189d8f20-fd0b-4ae9-9160-02cedac39911 Poland (PL)
dfa00889-9143-4640-beda-7b68e77263b4 France (FR)
e2a75877-0b3c-423d-a60d-9205fd4b7277 Sweden (SE)
2ba6904a-b275-40a0-a662-5277d2f0e712 Germany (DE)
dbbe5839-4af6-41b6-a0d9-d91eb8454cb5 Germany (DE)
b8b8214a-1d31-430b-aa6b-829d2c2e0845 Spain (ES)
30e0bf90-1472-4e80-9b14-b35167a34379 Netherlands (NL)
3fc61ee0-7133-460e-943f-e79dba217b6d Poland (PL)
5e5400ef-76f0-49e1-9aff-19542ffb47e1 Poland (PL)
1bc8a6dc-76f2-4cd5-8b92-6cd0b382a8e5 Finland (FI)
46710f5a-a1b8-4e6f-92eb-28c07b84c61b Norway (NO)
ecb4dd9f-7134-4b06-9ce6-ba53c0aceabe France (FR)
Ordering
Order Code US and Canada: XT1CE3050AFF000XXX
E-Number (Finland): 3638609
EAN: 8015644695194
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 76.2 mm
Product Net Height: 130 mm
Product Net Depth / Length: 70 mm
Product Net Weight: 1.1 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Depth / Length: 143 mm
Package Level 1 Gross Weight: 1.12 kg
Package Level 1 EAN: 8015644695194
Additional Information
Circuit Breaker Type to be Associated: Power Distribution
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: Automatic Circuit Breaker
Version: F
CAD Dimensional Drawing: 1SDH001295R0008
Technical
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: 240 cycles per hour
25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Order Multiple: 1 piece
Power Loss: at Rated Operating Conditions per Pole 3.7 W
Rated Current (In): 50 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 500 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 40 kA
(230 V AC) 40 kA
(240 V AC) 40 kA
(380 V AC) 25 kA
(415 V AC) 25 kA
(440 V AC) 12.5 kA
(500 V AC) 9 kA
(525 V AC) 8 kA
(690 V AC) 4 kA
(250 V DC) 2 Poles in Series 25 kA
(500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 40 kA
(230 V AC) 40 kA
(240 V AC) 40 kA
(380 V AC) 25 kA
(415 V AC) 25 kA
(440 V AC) 25 kA
(500 V AC) 18 kA
(525 V AC) 8 kA
(690 V AC) 4 kA
(250 V DC) 2 Poles in Series 25 kA
(500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 35…50 A
Short-Circuit Performance Level: C
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m
Certificates and Declarations
ATEX Certificate: No certification needed
Data Sheet, Technical Information: 1SDC210100D0206
1SDC210099D0206
Declaration of Conformity – CE: 9AKK106713A5532
GL Certificate: 1SDL000163R0103
LR Certificate: 1SDL000163R0100
UL Certificate: No certification needed
VDE Certificate: No certification needed
Dimension Diagram: 1SDH000719R0100
Mechanical Drawings: 1SDH000719R0100
Wiring Diagram: 1SDM000068R0001
Instructions and Manuals: 1SDH000719R0001
Classifications
ETIM 8: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
UNSPSC: 39120000
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
eClass: V11.1 : 27370409

Downloads

Datasheet