ABB XT1N 160 TMD 32-450 3p F F

General Information

Extended Product Type: XT1N 160 TMD 32-450 3p F F
Product ID: 1SDA067411R1
EAN: 8015644013059
Catalog Description: XT1N 160 TMD 32-450 3p F F
Long Description: C.BREAKER TMAX XT1N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32-450 A

Description

ABB EcoSolutions
ABB EcoSolutions: Yes
Circular Value
Circular Design Principles Recyclability Rate: Design for Closing Resource Loops – Standard EN45555 – 55.9 %
End of Life Instructions: 9AKK108468A2347
Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
Eco Transparency
Environmental Product Declaration – EPD: 9AKK108468A1890
9AKK108468A7793
Environmental
Environmental Information: 9AKK108467A6707
Material Compliance
REACH Declaration: 9AKK108466A1425
RoHS Information: 9AKK108466A1424
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
Toxic Substances Control Act – TSCA: 9AKK108467A8326
SCIP: b8ba1754-58ff-4887-8f7b-ac517add86e1 Italy (IT)
Simplified SCIP: 45f47fd6-9223-46fa-a768-bcd646930445 Bulgaria (BG)
826467e8-cc7a-454f-9954-b24a70a33722 Poland (PL)
64d2a653-cc56-47a4-8907-40c4975df2c5 France (FR)
0c9508b2-5f63-4738-9f37-95ee249dd923 Croatia (HR)
bfd52cf6-137a-4f1c-baa4-198c7ddd4e77 Poland (PL)
a8ce4899-c258-4bc9-aac4-7af7a288685d Denmark (DK)
7525be68-6981-41b5-91d3-5fed25e2a835 Germany (DE)
c10aa335-ed19-44b1-b311-abe8c0213e31 Belgium (BE)
5b53a997-ff88-4eb7-afb6-07ddef9a2176 Germany (DE)
78a1611c-b08c-4b82-a760-a9bc7da23dfb Norway (NO)
cbe9d242-d2db-4e53-b93d-35a5d1c6bb74 Finland (FI)
4e709cd3-5143-4be6-a525-7d85629d9946 Czech Republic (CZ)
cdbdc825-e361-4240-9349-5061d288185e Poland (PL)
c514384a-039c-426f-a521-b1eac9b56b6e Netherlands (NL)
b9688eb6-71ae-4c47-92ee-dc1425ce896b Greece (GR)
701d79bb-51d3-4b42-aafd-33bade3eabd2 Portugal (PT)
1417ae19-1649-44f6-9231-412343027262 Hungary (HU)
c9f14d1c-7394-4cab-b753-be55508ca065 Estonia (EE)
70b057a8-566a-41a8-ad52-08518207790a Hungary (HU)
8e4aab66-7fa7-422e-9cc3-8ab43447bab1 France (FR)
f08d0540-cdf9-4632-802e-19ce412839a5 Spain (ES)
fab47967-e60a-4ffe-ae3c-f3174b9c57d0 Germany (DE)
f0447bee-d0c0-469b-9fd1-36c1a459b32b Germany (DE)
6b50316f-e96a-457c-aa45-af0a945b8d9d Belgium (BE)
f85f968d-05e4-4d0f-afa2-a32373a91645 Sweden (SE)
999f1b32-9c39-4e8c-8d78-2eb9c626385c Sweden (SE)
96e93a98-4c84-47e2-a83c-afd5fe9a555b Germany (DE)
Ordering
Order Code US and Canada: XT1NE3032AFF000XXX
E-Number (Finland): 3640522
EAN: 8015644013059
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 76.2 mm
Product Net Height: 130 mm
Product Net Depth / Length: 70 mm
Product Net Weight: 1.1 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Depth / Length: 143 mm
Package Level 1 Gross Weight: 1.134 kg
Package Level 1 EAN: 8015644013059
Additional Information
Circuit Breaker Type to be Associated: Power Distribution
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: Automatic Circuit Breaker
Version: F
CAD Dimensional Drawing: 1SDH001295R0008
Technical
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: 240 cycles per hour
25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Order Multiple: 1 piece
Power Loss: at Rated Operating Conditions per Pole 2.1 W
Rated Current (In): 32 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 450 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 50 kA
(230 V AC) 50 kA
(240 V AC) 50 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 18 kA
(500 V AC) 15 kA
(525 V AC) 11 kA
(690 V AC) 5 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 65 kA
(230 V AC) 65 kA
(240 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(525 V AC) 22 kA
(690 V AC) 6 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 22.4…32 A
Short-Circuit Performance Level: N
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m
Certificates and Declarations
ATEX Certificate: No certification needed
Data Sheet, Technical Information: 1SDC210100D0206
1SDC210099D0206
Declaration of Conformity – CE: 9AKK106713A5532
GL Certificate: 1SDL000163R0103
LR Certificate: 1SDL000163R0100
UL Certificate: No certification needed
VDE Certificate: No certification needed
Dimension Diagram: 1SDH000719R0100
Mechanical Drawings: 1SDH000719R0100
Wiring Diagram: 1SDM000068R0001
Instructions and Manuals: 1SDH000719R0001
Classifications
ETIM 8: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
UNSPSC: 39120000
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
eClass: V11.1 : 27370409

Downloads