ABB XT1N 160 TMD 40-450 3p F F

General Information

Extended Product Type: XT1N 160 TMD 40-450 3p F F
Product ID: 1SDA067412R1
EAN: 8015644013066
Catalog Description: XT1N 160 TMD 40-450 3p F F
Long Description: C.BREAKER TMAX XT1N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 40-450 A

Description

ABB EcoSolutions
ABB EcoSolutions: Yes
Circular Value
Circular Design Principles Recyclability Rate: Design for Closing Resource Loops – Standard EN45555 – 55.9 %
End of Life Instructions: 9AKK108468A2347
Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
Eco Transparency
Environmental Product Declaration – EPD: 9AKK108468A1890
9AKK108468A7793
Environmental
Environmental Information: 9AKK108467A6707
Material Compliance
REACH Declaration: 9AKK108466A1425
RoHS Information: 9AKK108466A1424
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
Toxic Substances Control Act – TSCA: 9AKK108467A8326
SCIP: 848fe73d-3ecc-4485-bbef-f2dec965f3a5 Italy (IT)
Simplified SCIP: 420b6837-de7d-4bd1-9b36-33bb9784cf52 Belgium (BE)
dd86a351-c853-4974-861b-1cfac369457b Spain (ES)
154d20fb-5c46-44dd-8ac8-a0b427001ce2 France (FR)
c6104aa2-5e11-448e-8dc7-0625a9587a81 Denmark (DK)
4dce0847-a9d7-4ef5-be92-d25bf5bd5abb Sweden (SE)
1a1116b9-2f0d-47c7-bc03-e330b4f6ed05 Germany (DE)
d4851bc2-3e98-4339-832b-5aaec40f4f87 Croatia (HR)
c03712dc-bed8-4751-8170-8c71892a13f0 Germany (DE)
265df65c-9459-4bb0-b3c8-d109ae59a186 Czech Republic (CZ)
b624c864-c9b6-4e70-97aa-6eeb5070a281 Germany (DE)
ef479331-30d5-437b-a278-5cbc9b945a9d Germany (DE)
9fef5a66-1712-4946-9e76-ac21b568edfd Hungary (HU)
bc71b1e7-e458-460d-98f3-a122bb230cd9 Portugal (PT)
d9a7f657-2b46-4804-a7da-99ff774bea68 Poland (PL)
44639bb5-7fcf-422b-8e2b-5e7deeb5af01 Bulgaria (BG)
21411aac-cb8a-4a0d-95c2-979a92878952 Poland (PL)
c731cdd8-14e9-44b4-900b-490e2fce8db6 Germany (DE)
2a8f7c1c-a8d7-4fc6-b20c-7f82aec243a3 Estonia (EE)
35bc22fd-33d7-4641-8228-947203a00961 Belgium (BE)
d801a270-4410-4546-9cad-0c679bd4d03e Greece (GR)
87b6d777-b996-470b-a703-53e5010a590d France (FR)
f5bd22de-f07b-42cd-9052-3f5d890a532a Poland (PL)
b7794e80-d1c0-4840-940f-6f4fc3aad3e6 Hungary (HU)
4f0c67dd-f132-4c60-8c54-26c21ed62a24 Finland (FI)
d78ad1ad-48e4-4a0e-ae8a-d02fea224f6a Sweden (SE)
515bff57-ce73-49ee-88a2-b45fb6668cc9 Norway (NO)
aa7c55c8-ee4d-468d-9403-20b0fc1474ad Netherlands (NL)
Ordering
Order Code US and Canada: XT1NE3040AFF000XXX
E-Number (Finland): 3640523
EAN: 8015644013066
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 76.2 mm
Product Net Height: 130 mm
Product Net Depth / Length: 70 mm
Product Net Weight: 1.1 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Depth / Length: 143 mm
Package Level 1 Gross Weight: 1.137 kg
Package Level 1 EAN: 8015644013066
Additional Information
Circuit Breaker Type to be Associated: Power Distribution
Product Main Type: SACE Tmax XT
Product Name: Moulded Case Circuit Breaker
Product Type: Automatic Circuit Breaker
Version: F
CAD Dimensional Drawing: 1SDH001295R0008
Technical
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: 240 cycles per hour
25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Order Multiple: 1 piece
Power Loss: at Rated Operating Conditions per Pole 2.6 W
Rated Current (In): 40 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 450 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 50 kA
(230 V AC) 50 kA
(240 V AC) 50 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 18 kA
(500 V AC) 15 kA
(525 V AC) 11 kA
(690 V AC) 5 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 65 kA
(230 V AC) 65 kA
(240 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(525 V AC) 22 kA
(690 V AC) 6 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 28…40 A
Short-Circuit Performance Level: N
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m
Certificates and Declarations
ATEX Certificate: No certification needed
Data Sheet, Technical Information: 1SDC210100D0206
1SDC210099D0206
Declaration of Conformity – CE: 9AKK106713A5532
GL Certificate: 1SDL000163R0103
LR Certificate: 1SDL000163R0100
UL Certificate: No certification needed
VDE Certificate: No certification needed
Dimension Diagram: 1SDH000719R0100
Mechanical Drawings: 1SDH000719R0100
Wiring Diagram: 1SDM000068R0001
Instructions and Manuals: 1SDH000719R0001
Classifications
ETIM 8: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
UNSPSC: 39120000
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
eClass: V11.1 : 27370409