ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.70 % |
End of Life Instructions: | 9AKK108468A2348 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108469A1856 9AKK108468A1891 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | 01957bb2-d604-48b2-a2e1-50857b7b64fb Italy (IT) |
Simplified SCIP: | 6cf4007d-7377-4620-bf71-bb2ebfb8139e Spain (ES) b97116df-e458-4bba-abf2-6ef281595902 Hungary (HU) ed4e22aa-68ca-4777-b4a3-9a7707e660a7 Belgium (BE) 2ee5ac5d-2089-489a-bc81-a27283b6a9f5 France (FR) 2059c5b2-4ac5-457f-bbfd-e7a64624a00e Germany (DE) 9113dc5a-7d1b-4ba0-b42f-5c3aad75a719 Czech Republic (CZ) 60c32cd6-3bb5-499c-a2ff-ac53a0e9ee96 Portugal (PT) 7d5e121e-4036-4866-bca5-9669e1b6aa96 Denmark (DK) 19a3b1f0-c617-477e-a82a-b06c5a5ada60 Germany (DE) 339468d7-c350-48e1-ae79-c8824d81dd69 Sweden (SE) 60d4882a-fb2e-45bd-9a25-c977bf022219 Germany (DE) fbcb5e15-7f17-4ec8-a643-ad76a192e56e Croatia (HR) b3344b4b-dd95-4b8f-ac56-bc55a64e7145 France (FR) e79caf94-a678-44d2-b167-ccd62089f529 Greece (GR) cbdaf91b-fc37-4d44-bc24-1b84f8b98589 Estonia (EE) 0e163568-64b1-45c3-ab3c-8a1bf267d2c0 Belgium (BE) 02103868-adaa-4982-9bb7-910cc86142d1 Finland (FI) dde684a3-60de-42cd-8fe1-f519a19f95e3 Poland (PL) a97f8077-2b79-41ef-aacf-546fa724843b Hungary (HU) 5c0bf06a-3071-46b7-9cf6-2e017c00ad8c Sweden (SE) 651ec6b9-af35-42a6-a44f-2e7bf9de6186 Germany (DE) 25ea3b9c-a250-40d0-ab4d-a5ee6f855790 Norway (NO) 7b1d9aba-e4e1-47e1-b92e-6549d454ea1f Netherlands (NL) 033d7a16-0c77-45ae-bcdd-8641cae11075 Poland (PL) fbc82c32-a5ca-44b9-b720-8beb14dc2c52 Poland (PL) 38cc79c8-82f9-42b9-a19e-983ed2688685 Bulgaria (BG) c219e422-f6f7-467c-806d-a14a0ad81bed Germany (DE) |
Ordering | |
Order Code US and Canada: | XT2NE4063BFF000XXX |
EAN: | 8015644009434 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 120 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 82.5 mm |
Product Net Weight: | 1.6 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 130 mm |
Package Level 1 Height: | 208 mm |
Package Level 1 Depth / Length: | 145 mm |
Package Level 1 Gross Weight: | 2.114 kg |
Package Level 1 EAN: | 8015644009434 |
Additional Information | |
Circuit Breaker Type to be Associated: | Power Distribution |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Version: | F |
CAD Dimensional Drawing: | 1SDH002230A1002 |
Technical | |
Connecting Capacity Main Circuit: | Busbar 32.5..100 mm² |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour 8000 cycle |
Mechanical Durability: | 240 cycles per hour 25000 cycle |
Number of Poles: | 4 |
Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 4.85 W |
Rated Current (In): | 63 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 300€¦630 A |
Rated Insulation Voltage (Ui): | 1000 V |
Rated Operational Voltage: | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
Rated Uninterrupted Current (Iu): | 160 A |
Rated Voltage (Ur): | 690 V |
Recommended Screw Driver: | Main Circuit M6 |
Release: | TMA |
Release Type: | TM |
Setting Range: | 44.1…63 A |
Short-Circuit Performance Level: | N |
Standards: | IEC60947-2 |
Sub-type: | XT2 |
Terminal Connection Type: | Front |
Terminal Type: | Bolt |
Tightening Torque: | 6 N·m |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
Declaration of Conformity – CE: | 9AKK106713A5901 |
GL Certificate: | 1SDL000163R0093 |
LR Certificate: | 1SDL000163R0100 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Dimension Diagram: | 1SDH000721R0100 |
Mechanical Drawings: | 1SDH000721R0100 |
Wiring Diagram: | 1SDM000068R0001 |
Instructions and Manuals: | 1SDH000721R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
UNSPSC: | 39120000 |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |