Description
ABB EcoSolutions | |
ABB EcoSolutions: | Yes |
Circular Value | |
Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 55.70 % |
End of Life Instructions: | 9AKK108468A2348 |
Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
Eco Transparency | |
Environmental Product Declaration – EPD: | 9AKK108469A1856 9AKK108468A1891 |
Environmental | |
Environmental Information: | 9AKK108467A6707 |
Material Compliance | |
REACH Declaration: | 9AKK108466A1425 |
RoHS Information: | 9AKK108466A1424 |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
SCIP: | cc233e8f-9e6b-4c6a-a22b-c410abdcb24d Italy (IT) |
Simplified SCIP: | d8f2dadc-f429-4da1-a8c5-8617dfe63b4b Belgium (BE) 528d53a4-9562-455f-8f7e-e5545aaae728 Hungary (HU) 2619f1fe-a142-4e94-bc6a-e47b473adf32 Spain (ES) 1ddddd93-aebe-4cd7-aca4-65d99a87f84e Germany (DE) c31d42f7-75b9-4004-8ee7-a5230093b6b0 Denmark (DK) 73e75842-f1a3-41c8-a843-78a3ac986dab Sweden (SE) 8e6202ac-7dc3-41d7-9df8-18294155659d Germany (DE) 5d0b26b3-6024-45f2-bbdb-ba55d2bfcbf6 France (FR) e85e869d-4dd8-432a-ae5c-bac37698316a Portugal (PT) a3e96bb0-ff5d-49cb-ba62-2798c2788631 Croatia (HR) 280b06a4-2590-48fe-97e8-72c2a42065b7 Germany (DE) 05156b4c-8804-4dd6-8cb2-e9377e92869b Germany (DE) 8a320b36-6794-4fd1-8eb5-3d34fe697664 Czech Republic (CZ) 73201c1d-f1e0-48a0-bfd5-c854748afcbc France (FR) 0219c419-f810-4161-8608-63ae7ceb0f31 Poland (PL) 9d6a4bcd-13ce-453c-a0f2-7be88f72ddbb Poland (PL) 841fc56d-5fd5-4020-b0bb-229a15784dd9 Germany (DE) 4808af2d-7c7e-4d6e-8763-f86ddc6947a0 Greece (GR) 76bfa5d7-7904-4e81-9039-475ebaf549b1 Estonia (EE) 14be1c63-ed8f-4434-80cd-32e1bb57ca99 Belgium (BE) e15033fc-9f9a-4734-a7c1-977ffb4b5c1b Finland (FI) a07481e7-f7b8-460e-9b94-670eafdb61de Poland (PL) c0caa3d1-fc13-47b0-9d98-e4fcaeb4e2b0 Hungary (HU) 207d62db-bf1f-49f8-99f5-36a58d032e9b Bulgaria (BG) 1ed7dbbe-192f-41cc-9c25-bb76890295e6 Netherlands (NL) a6457aa2-bc90-42f1-bfe9-11eb11912f28 Sweden (SE) 87a38a25-d7a5-42a6-8960-216377e073ed Norway (NO) |
Ordering | |
Order Code US and Canada: | XT2SE4032AFF000XXX |
EAN: | 8015644014704 |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362090 |
Dimensions | |
Product Net Width: | 120 mm |
Product Net Height: | 130 mm |
Product Net Depth / Length: | 82.5 mm |
Product Net Weight: | 1.6 kg |
Container Information | |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 130 mm |
Package Level 1 Height: | 208 mm |
Package Level 1 Depth / Length: | 145 mm |
Package Level 1 Gross Weight: | 2.117 kg |
Package Level 1 EAN: | 8015644014704 |
Additional Information | |
Circuit Breaker Type to be Associated: | Power Distribution |
Product Main Type: | SACE Tmax XT |
Product Name: | Moulded Case Circuit Breaker |
Product Type: | Automatic Circuit Breaker |
Version: | F |
CAD Dimensional Drawing: | 1SDH002230A1002 |
Technical | |
Connecting Capacity Main Circuit: | Busbar 32.5..100 mm² |
Current Type: | AC/DC |
Electrical Durability: | 120 cycles per hour 8000 cycle |
Mechanical Durability: | 240 cycles per hour 25000 cycle |
Number of Poles: | 4 |
Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple: | 1 piece |
Power Loss: | at Rated Operating Conditions per Pole 2.57 W |
Rated Current (In): | 32 A |
Rated Frequency (f): | 50 / 60 Hz |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii): | 320 A |
Rated Insulation Voltage (Ui): | 1000 V |
Rated Operational Voltage: | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
Rated Uninterrupted Current (Iu): | 160 A |
Rated Voltage (Ur): | 690 V |
Recommended Screw Driver: | Main Circuit M6 |
Release: | TMD |
Release Type: | TM |
Setting Range: | 22.4…32 A |
Short-Circuit Performance Level: | S |
Standards: | IEC60947-2 |
Sub-type: | XT2 |
Terminal Connection Type: | Front |
Terminal Type: | Bolt |
Tightening Torque: | 6 N·m |
Certificates and Declarations | |
ATEX Certificate: | No certification needed |
Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
Declaration of Conformity – CE: | 9AKK106713A5901 |
GL Certificate: | 1SDL000163R0093 |
LR Certificate: | 1SDL000163R0100 |
UL Certificate: | No certification needed |
VDE Certificate: | No certification needed |
Dimension Diagram: | 1SDH000721R0100 |
Mechanical Drawings: | 1SDH000721R0100 |
Wiring Diagram: | 1SDM000068R0001 |
Instructions and Manuals: | 1SDH000721R0001 |
Classifications | |
ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code: | Q |
UNSPSC: | 39120000 |
WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass: | V11.1 : 27370409 |