| ABB EcoSolutions | |
| ABB EcoSolutions: | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate: | Design for Closing Resource Loops – Standard EN45555 – 56.30 % |
| End of Life Instructions: | 9AKK108468A2351 |
| Group Waste to Landfill Target: | UL 2799 Zero Waste To Landfill Validation available |
| Eco Transparency | |
| Environmental Product Declaration – EPD: | 9AKK108469A1857 9AKK108468A1892 |
| Environmental | |
| Environmental Information: | 9AKK108467A6707 |
| Material Compliance | |
| REACH Declaration: | 9AKK108466A1425 |
| RoHS Information: | 9AKK108466A1424 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108467A5658 |
| Toxic Substances Control Act – TSCA: | 9AKK108467A8326 |
| SCIP: | 0f75806c-038e-427c-a419-1e619ead7330 Italy (IT) |
| Simplified SCIP: | bbf3de98-513f-44e4-800b-3554879d61db Germany (DE) 80771390-3c90-4704-ba7b-7ad00bdcaaac Germany (DE) 24f0072f-f737-47e8-bf8f-a7da542de573 France (FR) fa6bf96d-401d-4e5a-9037-3f1be0e99ff0 Netherlands (NL) 2238a3b5-a625-4e86-a72f-b1a2bf518299 Spain (ES) 59a70feb-bd3c-4c18-a39c-77dac537e6c3 Netherlands (NL) b08a9cad-9f06-4367-b311-d07225fb1ebd Netherlands (NL) a924a9af-9a13-428f-b70d-9c7c89090db7 Germany (DE) 3d326f4b-0f76-4365-aad1-a6b5e227cc44 Sweden (SE) dc4ea025-3e43-44d4-a948-daf1de7163e0 Denmark (DK) 47a697a1-294f-402c-9d6b-8d4bc72e3337 Germany (DE) 1d33418a-b4bb-4ca0-ba0d-39dfaf977e6d Poland (PL) 16d8165e-690a-4042-87c4-85f69f0b4288 Norway (NO) 1c4ace83-d732-4906-9421-76fae14054e0 Finland (FI) 0b84f289-8294-42b3-8d69-e269bfd1929a Netherlands (NL) 0a328f25-806b-4442-b8b4-f6dc12bcbeda Croatia (HR) aaf0d27c-68f9-4a06-a505-2b477dfd0c30 Czech Republic (CZ) ef4bf7a7-a3f3-4488-a35d-8b9db53b0e18 Poland (PL) f164363d-7972-4af1-a7c9-0fca68892918 Netherlands (NL) 47aab088-da02-4a97-a865-79f7b51aee06 Estonia (EE) 454a9ac2-5efa-4740-9bbb-0b609138bccb Greece (GR) 9343a443-38ba-4bc0-b403-83c6b57f3537 Portugal (PT) f0b014c5-5a87-4a28-a309-ba88ce1bf902 Bulgaria (BG) e400fc61-0699-47c7-ba49-0160152400d6 Sweden (SE) ef14ac71-e36e-44d0-b642-a2ef43214fbc Poland (PL) 7e3f11d9-dead-45cc-9d62-4a150cee4a28 France (FR) 04d02c11-98e0-49a2-9196-7e23a112b2f9 Germany (DE) |
| Ordering | |
| Order Code US and Canada: | XT4NE3200BFF000XXX |
| E-Number (Finland): | 3641036 |
| EAN: | 8015644695828 |
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362090 |
| Dimensions | |
| Product Net Width: | 105 mm |
| Product Net Height: | 160 mm |
| Product Net Depth / Length: | 82.5 mm |
| Product Net Weight: | 2.253 kg |
| Container Information | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Width: | 151 mm |
| Package Level 1 Height: | 214 mm |
| Package Level 1 Depth / Length: | 171 mm |
| Package Level 1 Gross Weight: | 2.372 kg |
| Package Level 1 EAN: | 8015644695828 |
| Additional Information | |
| Circuit Breaker Type to be Associated: | Power Distribution |
| Product Main Type: | SACE Tmax XT |
| Product Name: | Moulded Case Circuit Breaker |
| Product Type: | Automatic Circuit Breaker |
| Version: | F |
| CAD Dimensional Drawing: | 1SDH002230A1003 |
| Technical | |
| Connecting Capacity Main Circuit: | Busbar 85..200 mm² |
| Current Type: | AC/DC |
| Electrical Durability: | 120 cycles per hour 8000 cycle |
| Mechanical Durability: | 240 cycles per hour 25000 cycle |
| Number of Poles: | 3 |
| Opening Time: | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple: | 1 piece |
| Power Loss: | at Rated Operating Conditions per Pole 11.88 W |
| Rated Current (In): | 200 A |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii): | 1000€¦2000 A |
| Rated Insulation Voltage (Ui): | 1000 V |
| Rated Operational Voltage: | 690 V AC 750 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Uninterrupted Current (Iu): | 250 A |
| Rated Voltage (Ur): | 690 V |
| Recommended Screw Driver: | Main Circuit M8 |
| Release: | TMA |
| Release Type: | TM |
| Setting Range: | 140…200 A |
| Short-Circuit Performance Level: | N |
| Standards: | IEC60947-2 |
| Sub-type: | XT4 |
| Terminal Connection Type: | Front |
| Terminal Type: | Bolt |
| Tightening Torque: | 8 N·m |
| Certificates and Declarations | |
| ATEX Certificate: | No certification needed |
| Data Sheet, Technical Information: | 1SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity – CE: | 9AKK106713A5529 |
| GL Certificate: | 1SDL000163R0095 |
| LR Certificate: | 1SDL000163R0100 |
| UL Certificate: | No certification needed |
| VDE Certificate: | No certification needed |
| Dimension Diagram: | 1SDH000722R0100 |
| Mechanical Drawings: | 1SDH000722R0100 |
| Wiring Diagram: | 1SDM000068R0001 |
| Instructions and Manuals: | 1SDH000722R0001 |
| Classifications | |
| ETIM 8: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9: | EC000228 – Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code: | Q |
| UNSPSC: | 39120000 |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass: | V11.1 : 27370409 |