Description
| Technical | |
| Standards: | IEC/EN 61009-1, IEC/EN 61009-2-1 |
| Tripping Characteristic: | C |
| Type of Residual Current: | Type AC |
| Rated Operational Voltage: | acc. to IEC 60898-1 240 V |
| Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 500 V |
| Test Voltage (Ut): | 170 … 264 V |
| Rated Impulse Withstand Voltage (Uimp): | 4 kV |
| Dielectric Test Voltage: | 2 kV |
| Input Voltage Type: | AC |
| Rated Current (In): | 13 A |
| Rated Residual Current: | 30 mA |
| Rated Short-Circuit Capacity: | 6 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | 10 kA |
| Rated Residual Breaking Capacity (IΔm): | EN 61009-1 6000 A IEC 61009-1 6000 A |
| Rated Conditional Short-Circuit Current (Inc): | 10 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics): | 7.5 kA |
| Maximum Surge Current: | 0 kA |
| Rated Frequency (f): | 50 €¦ 60 Hz |
| Power Loss: | Average per Pole 1.7 W Phase Pole 2.7 W Neutral Pole 0.8 W Total 3.5 W |
| Power Supply Connection: | Arbitrary |
| Contact Position Indication: | Red ON / Green OFF |
| Energy Limiting Class: | 3 |
| Electrical Endurance: | 10000 cycle |
| Mechanical Endurance: | 20000 cycle |
| Number of Protected Poles: | 1 |
| Number of Poles: | 2 |
| Number of Modular Spacings per DIN Rail: | 2 |
| Fault Indication: | Blue flag on toggle |
| Operating Characteristic: | Instantaneous |
| Overvoltage Category: | III |
| Position of Neutral Terminals: | Right |
| Tightening Torque: | 2.8 N·m |
| Accessory Type: | Auxiliary contact, Signal contact / auxiliary contact, Shunt trip, Auxiliary contact for bottom fitting, Overvoltage release, Motor operating device |
| Actuator Type: | Toggle – Insulation group II, Black RAL 9005, sealable in ON-OFF positions |
| Housing Type: | Insulation group I – II, RAL 7035 |
| Mounting Type: | DIN-Rail |
| Screw Terminal Type: | Failsafe Bi-directional Cylinder-lift Terminal |
| Mounting Position: | Any |
| Accessories Available: | Yes |
| Number of Batteries: | 0 |
| Connecting Capacity: | Busbar 10 … 10 mm² Stranded 0.75 … 25 mm² Flexible with Ferrule 0.75 … 16 mm² Flexible 0.75 … 16 mm² |
| Wire Stripping Length: | 12 mm |
| Terminal Type: | Screw Terminals |
| Material Compliance | |
| RoHS Information: | 9AKK106713A5588 |
| RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date: | 20211115 |
| REACH Declaration: | 9AKK108467A9482 |
| REACH Information: | True – contains substances > 0.1 mass percentage |
| REACH Date: | 20240429 |
| Conflict Minerals Reporting Template (CMRT): | 9AKK108468A3363 |
| Environmental | |
| Ambient Air Temperature: | Operation -25 €¦ 55 °C |
| Reference Ambient Air Temperature: | 30 °C |
| Degree of Protection: | IP20 IP40 |
| Pollution Degree: | 2 |
| Environmental Conditions: | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
| Resistance to Vibrations: | 20 Cycles with Load 0.8 In: 1g or 1mm 50 €¦ 150 €¦ 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27: | 25g 2 shocks 13 ms |
| Environmental Information: | 2CSC422002K2701 |
| Dimensions | |
| Width in Number of Modular Spacings: | 2 |
| Product Net Width: | 0.035 m |
| Product Net Height: | 0.085 m |
| Product Net Depth / Length: | 0.069 m |
| Product Net Weight: | 0.200 kg |
| Built-In Depth (t2): | 69 mm |
| Ordering | |
| Package Level 1 Units: | box 1 piece |
| Package Level 1 Gross Weight: | 225 g |
| Certificates and Declarations | |
| ABS Certificate: | 9AKK107991A2823 |
| CB Certificate: | 9AKK107492A6060 |
| CCC Certificate: | 9AKK107492A6067 |
| Declaration of Conformity – CE: | 9AKK106713A5588 |
| DNV GL Certificate: | 9AKK107680A3457 9AKK107680A3456 |
| EAC Certificate: | 9AKK107492A6071 9AKK107991A7755 |
| GOST Certificate: | 9AKK107992A1640 |
| ÖVE Certificate: | 9AKK107492A6085 |
| RMRS Certificate: | 9AKK107680A3454 9AKK107680A3455 |
| Installation | |
| Instructions and Manuals: | 9AKK107492A6006 |
| Popular Downloads | |
| Data Sheet, Technical Information: | 9AKK107492A6187 |
| Classifications | |
| ETIM 8: | EC000905 – Earth leakage circuit breaker |
| ETIM 9: | EC000905 – Earth leakage circuit breaker |
| WEEE Category: | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B: | Business To Consumer |
| CN8: | 85363010 |
| eClass: | V11.0 : 27142207 |
| Object Classification Code: | F |